TT series Surge Protective Device (SPD)
GB Recognized DIN Rail Mount
Verify Correct Connection and Line Voltage
ᇏࠗൻᇏᄡᤣଣௌ֮ፊႚԤ
Backup protection MCB** or fuse must be installed
ঐᮣࠎᜠPFE--ྔٿϋધ
SPD: 20 kA
SPD: 45 kA
SPD: 65 kA
SPD: 80 kA
SPD: 100 kA
MCB: 16 A type B ”preferred”
MCB: 20 A type B ”preferred”
MCB: 32 A type B ”preferred”or C
MCB: 40 A type B ”preferred”
MCB: 63 A type B ”preferred”
TNS System TNC & IT System TT System
L1
L2
L3
N
Diagram : Recommended to maximize the
SPD* performance ( up to 40A )
ڦᶙଥᕲݏVSGᝒೂᶇ˗ݏ73Dᶈ
Torque value of the terminal screws 4N*m
ଣፊኂ߬ઌҾᆕ7Q-p
Connector lugs sized for wire range 6 mm2-25 mm
ᤣଣࡅፊᅇ9pp2058pp
L1
L2
L3
2
L1
L2
L3
2
ଣፊน
4P
L1
L2
L3
N
ଣፊน
4P
Normal Operation
ࣹᤙᛸ
Single Pole or Multi Pole
ଣፊน
3P
L1
L1
L2
L2
L3
L3
N
ଣፊน
3P
Clear window = Normal Operation
ᎆᓻᜂᇿൻࣹΥ႐
Red window replacement required
ጱᓻᜂᇿࣚፚଆۅ
N
ଣፊน
3P+N
L1
L1
L2
L2
L3
L3
ଣፊน
3P+N
L1
L2
L3
N
GE Energy
Digital Energy
Customer Wiring Connections
႐ଣፊ
Clamping Volage of Surge Protective Device
Connected Via 6 sq mm Wire
2500
2000
1500
1000
500
Clamping Volage
0
0123
Wire Length in Meters
Optional Remote Monitor
ᤡቅનଣཙ
диཙ
ࣹ
ࣹ
Ѻኂ߬
ᤡቅનଣཙᝒೂ
NC
NO
C
NO
NC
C
Normally Open/
Common/
Normally Closed/
Output terminal/
Remote contact ratings
Nominal Voltage: 230VAC 50Hz
Max voltage: 250VAC 50Hz
Min voltage 200 VAC 50Hz
Max Amperage:1.5A AC
Remote contacts are not intended for use
in DC applications
Make sure the distance between the SPD and the protected equipment is less than 30 meters.
ᇏϋVSG֮ϋધႚٿ˿ᄡᤣፊᢇሦࡌ63p
If distance is greater than 30 meters, install an additional SPD by the equipment to protect.
ݷ౾ᢇሦݏ63p/ڱϋધႚٿ˕ܰӂˎ˫VSG
Make sure a high quality ground is in place to avoid ground loops.
ᇏϋᠦ᧱ᄡଣڸᬐൺଣڸ
Do not loop or coil wires; trim the wire to fit with the shortest length possible.
˗ᝍࡉᤣଣፊᎤ፠ઁګᶋࡡՒᑶᄡᎭᆘᤣଣፊ
Keep Connections as Direct & Straight as Possible
ࡡՒᑶᄡϋᤣଣ۞ᅇ
DO NOT Have Sharp Bends
˗ᝍళ
Caution: Install the output terminal as shown while unit is de-energized
( no power applied)
NO
NC
C
รᶙΥ႐௨ᶋѺኂ߬ঐᮣૢݷڦᇿࠎᜠ/#ർ௨ᜠᏍ˗ᑶ˔ႚ
output terminal
Torque value of the terminal screws 0.2N*m
ଣፊኂ߬ઌҾᆕ315Q-p
Connector lugs sized for wire range 0.13mm2-1.3mm
ᤣଣࡅፊᅇ3146pp20416pp
2
2
RCD Nuisance Tripping
ႚϋધទ݃ᒉઅ
L
Avoid ***RCD nuisance tripping by installing the SPD ahead of the
sensitive RCD ( <30mA )
ࡉVSGࠎᜠႚϋધទ݃ᄡҩኂ/#ᬐൺႚទ݃ᒉઅ
Replacement modules
7
ൌۈ2Prgxoh
M 385 20
M 385 40
M 385 65
G 255 20
G 255 40
G 255 65
Mounting
8
TT series SPD is designed to mount onto a 35mm DIN rail, as picture.
ݷڦᶋWWጞҌVSGࠎᜠڱ68ඪዲಭѥࡅᣕ˔Ǥ
ࠎᜠ
ଈൌۈ
ᝒೂ2Udwlqjv
MOV 385V 20KA
MOV 385V 40KA
MOV 385V 65KA
GDT 255V 20KA
GDT 255V 40KA
GDT 255V 65KA
Caution: Please select correctly the module;
otherwise you replacement modules will be incompatible.
Insert force of the model must be large than 45N,
less than 100N.
รᶙះรൌۈ֮ᄡӳᦸৄᶋ᪉ឿૐՒଈൌۈࡉนӳᦸǤ
######ൌۈбҾঐᮣݏ78Qᶋ΅˗ᑶᡫᤖ433Q
N
Definitions: *SPD=Surge Protective Device · **MCB=Miniature Circuit Breaker · ***RCD=Residual Current Device
Information subject to change without notice. Please verify all details with
L
N
RCD RCD
© 2010 General Electric Company All Rights Reserved2020010301 (12/10)
GE Digital Energy – Power Quality
830 W 40th Street, Chicago, IL 60609
800 637 1738 www.gepowerquality.com
USA