Model Number:5KS444DAJ6022C
Enclosure is Weather Protected One
NEMA ENCLOSURE WP-I, CSA ENCL DP
HTR LDS HE1-HE2 115V 145W
ROT CCW FACING ODE LEAD/PH SEQ 1-2-3/1-2-3
THERMOSTAT LEADS TB1-TB2 TRIP
INVERTER DUTY PER NEMA MG1 PART 31
ALTERNATE RATING FOR PWM CONTROL:1.0SF 40C AMBIENT
VAR TORQUE RANGE 5 -60 HZ
UPPER BRG LUBE OIL: 10.2 QTS
0 DEG C TO 40 DEG C : ISO 32(MINERAL OR SYNTHETIC)
-15 DEG C TO 0 DEG C : ISO 32 SYNTHETIC
SUITABLE FOR 150 HP, 380 V, 50 HZ WITH
210.0 AMPS AND 1485 RPM AT 1.0 SF
Model Number:5KS444DAJ6022C
4P, VERT HOLLOW SHAFT HIGH THRUST (2D)
C/BOX 700 CU IN - 3.00" NPT
OIL RESISTANT SLEEVING ON LEADS
(3) N.C. CL.F TRIP TSTAT LDS TO MAIN CONDUIT BOX
115V HTR LDS TO MAIN CONDUIT BOX
GROUND PAD
INSULATED UPPER BEARING CARRIER
SHAFT GROUNDING RING MOUNTED ON DE BRG CAP
BEARING LIFE 8760 HRS AT 22551 LB THRUST
PART WINDING START
CG:22.60 IN FROM P-BASE FACE,STAT DEF:= 0.004 IN
RCF: 2971 CPM
NON-REVERSE BALL CARRIER,
BOLTED COUPLING, BX = 1.688, KEY = 0.375