Accessory Connection Diagrams
Performance Characteristics
Model Number:5KS449SAA2143A
Enclosure is Totally Enclosed Fan-Cooled
Stamped Nameplate Notes:
TEMP CONT HTR LDS HE1-HE2 115V 125W
FOR DIRECT COUPLED LOAD ONLY
GE SELF DECLARED CLASS I DIV2 GROUP A,B,C,D MOTOR
MAX EXPOSED INTERNAL AND EXTERNAL SURFACE
TEMPERATURES UNDER USUAL SERVICE CONDITIONS
AT 1.00 S.F. DO NOT EXCEED 200 DEG C
MAX SPACE HEATER SURFACE TEMPERATURE 160 DEG C
4P - T EXTN
C/BOX 2500 CU IN - 2(4.00" NPT)
OIL RESISTANT SLEEVING ON LEADS
TWO SETS OF 100 OHM WINDING RTDS
RTD LEADS EXIT TO ACCESSORY BOX W/ TERM BOARD
115V TSTAT CTRLD HTR LDS TO ACCESSORY BOX W/ TERM BOARD
GROUND PAD
F1 MOUNTING, OFFSET CORE - DO NOT ASSEMBLE F2
FORMED COIL
SUGGESTED WINDING RTD SETTINGS
ALARM 165C TRIP 175C
Model Number:5KS449SAA2143A
Performance Characteristics
1st Winding 1st Connection
This motor is capable of two cold or one hot start with a maximum connected load inertia of 4399 Lb-Ft Sq (185.2 Kgmeter Sq)at 100% voltage, where the load torque varies with the square of the speed. Acceleration time with maximum
inertia and the above load type is 65 seconds. Safe stall time at 100% voltage is 209 seconds cold, 111 seconds hot.
Rotor inertia is 84.72 Lb-Ft Sq (3.57 Kg-meter Sq).