GE Industrial Motors M9800 Product Information Packet

Product Technical Information
June 23, 2020
Data shown is for the current revision model #. Ensure your nameplate model # matches.
Model Number:
5KS449SAA1053A
Catalog Number:
M9800
Instruction Manual:
GEI-56128
Connection Diagram:
GEM2034E-FIG2
Outline Drawing:
239C6800ACV
Accessory Connection Diagrams
Bearing Thermocouple:
None
Heater:
3027JE-1C
RTD:
235A3027XY
Thermistor:
None
Thermostat:
None
Winding Thermocouple:
None
Bearing RTD:
None
Table of Contents
Specification
01
Performance Characteristics
02
Outline Drawing
03
Connection Drawing(s)
04
Spare parts
05
Model Number:5KS449SAA1053A
June 23, 2020
Page | 1
Marks:
MODEL NUMBER:
5KS449SAA1053A
Estimated Weight:
2560 Lbs
Outline Drawing:
239C6800ACV
Time Rating:
CONT
Connection Diagram:
GEM2034E-FIG2
Enclosure:
TEFC
Instruction Book:
GEI-56128
Encl Construction:
X$D
Design Code:
49BD0228E
Ambient Max(°C):
40
Type:
KS
Alt Ambient Max(°C):
--
Frame:
449TS
Insulation Class:
F
Phases:
3
NEMA Design:
B
Poles:
2
Nominal Efficiency:
94.5 %
Output Power:
125HP 92.5KW
Guaranteed Efficiency:
94.1 %
RPM:
3580
3/4 Load Efficiency:
94.3 %
Voltage:
2300/4000
KVA Code:
G
Hertz:
60
Max KVAR:
23.0
Amps - FL:
27.1/15.6
Power Factor:
91.0
Service Factor:
1.15
Bearing - DE:
6314ZC3
Alt Service Factor:
--
Bearing - ODE:
6314ZC3
Enclosure is Totally Enclosed Fan-Cooled Stamped Nameplate Notes:
TEMP CONT HTR LDS HE1-HE2 115V 125W FOR DIRECT COUPLED LOAD ONLY GE SELF DECLARED CLASS I DIV2 GROUP A,B,C,D MOTOR MAX EXPOSED INTERNAL AND EXTERNAL SURFACE TEMPERATURES UNDER USUAL SERVICE CONDITIONS AT 1.00 S.F. DO NOT EXCEED 200 DEG C MAX SPACE HEATER SURFACE TEMPERATURE 160 DEG C
Additional Information:
2P - TS EXTN C/BOX 2500 CU IN - 2(4.00" NPT) OIL RESISTANT SLEEVING ON LEADS TWO SETS OF 100 OHM WINDING RTDS RTD LEADS EXIT TO ACCESSORY BOX W/ TERM BOARD TSTAT CTRLD HTR LDS TO ACCESSORY BOX W/ TERM BOARD GROUND PAD F1 MOUNTING, OFFSET CORE - DO NOT ASSEMBLE F2 FORMED COIL SUGGESTED WINDING RTD SETTINGS ALARM 165C TRIP 175C
Model Number:5KS449SAA1053A
June 23, 2020
Page | 2
Performance Characteristics
1st Winding 1st Connection
Design: 49BD0228E
Marks:
LOAD %
125.0
115.0
100.0
75.0
50.0
25.0
0.0
% EFF
94.03
94.2
94.58
94.36
93.52
89.79
0.00
% PF
90.86
90.96
90.82
89.44
84.84
68.78
9.29
AMPS
19.68
18.06
15.66
11.96
8.48
5.45
3.71
TORQ(FL)#FT
183.3
TORQ(LR)%FL
146.9
TORQ(BD)%FL
291.46
AMPS(LR)
100.7
PF AT START
0.25
This motor is capable of two cold or one hot start with a maximum connected load inertia of 675 Lb-Ft Sq (28.42 Kg-meter Sq)at 100% voltage, where the load torque varies with the square of the speed. Acceleration time with maximum inertia and the above load type is 54 seconds. Safe stall time at 100% voltage is 110 seconds cold, 65 seconds hot. Rotor inertia is 38.76 Lb-Ft Sq (1.63 Kg-meter Sq).
Open Circuit A-C:
2.06 Short Circuit D-C:
0.026
Short Circuit A-C:
0.078 X/R Ratio:
9.975
Stator Slots:
48 Rotor Slots:
38