GE Industrial Motors M9586 Product Information Packet

Product Technical Information
June 25, 2020
Data shown is for the current revision model #. Ensure your nameplate model # matches.
Model Number:
5KS365XAA404D4
Catalog Number:
M9586
Instruction Manual:
GEI-56128
Connection Diagram:
GEM2034E-FIG7
Outline Drawing:
239C6200RC
Accessory Connection Diagrams
Bearing Thermocouple:
None
Heater:
None
RTD:
None
Thermistor:
None
Thermostat:
None
Winding Thermocouple:
None
Bearing RTD:
None
Table of Contents
Specification
01
Performance Characteristics
02
Outline Drawing
03
Connection Drawing(s)
04
Spare parts
05
Model Number:5KS365XAA404D4
June 25, 2020
Page | 1
Marks:
MODEL NUMBER:
5KS365XAA404D4
Estimated Weight:
1020 Lbs
Outline Drawing:
239C6200RC
Time Rating:
CONT
Connection Diagram:
GEM2034E-FIG7
Enclosure:
TEFC
Instruction Book:
GEI-56128
Encl Construction:
841
Design Code:
36BD4026B
Ambient Max(°C):
40
Type:
KS
Alt Ambient Max(°C):
--
Frame:
365T
Insulation Class:
H
Phases:
3
NEMA Design:
B
Poles:
8
Nominal Efficiency:
92.4 %
Output Power:
40HP 29.6KW
Guaranteed Efficiency:
91.7 %
RPM:
885
3/4 Load Efficiency:
--
Voltage:
575
KVA Code:
G
Hertz:
60
Max KVAR:
22.0
Amps - FL:
45.3
Power Factor:
71.5
Service Factor:
1.15
Bearing - DE:
6314ZC3
Alt Service Factor:
--
Bearing - ODE:
6314ZC3
Enclosure is Totally Enclosed Fan-Cooled Stamped Nameplate Notes:
IEEE-STD-841-2009 DE BRG 70BC03JP30, ODE BRG 70BC03JP30 STAMP NP249A5564P051 AS BELOW: MODEL:5KS365XAA404D4 S/N: XXX CSA CERTIFIED CSA09.2216219 FOR EX NA IIC 200 C GC CL 1 ZONE2 AEX NA IIC 200C;CL 1 DIV2 GRP ABCD 200C IN -25C <= AMB <= 40C, 1.0 SF ON SINE-WAVE PWR SURF TEMP 230C AT 1.15SF ON SINE-WAVE PWR OR 200C VT OR 230C CT OR 200C CHP PWM CONTROL ALTERNATE RATING FOR PWM CONTROL 1.0SF 40C AMB VT 0-60 HZ, CT 15-60 HZ, CHP 60-90 HZ.
Model Number:5KS365XAA404D4
June 25, 2020
Page | 2
Additional Information:
8P - T EXTN PAINTED FRAME ID & SHAFT, FAN COVER INSIDE & ODE E/S OUTSIDE 346 CU IN - 3.00" NPT INPRO SEAL BOTH ENDS OIL RESISTANT SLEEVING ON LEADS .0015" TIR SHAFT RUNOUT ROUTINE TEST REPORT AND 5 POINT VIBRATION TEST REPORT INCLUDED IN C/B COPPER WASHER UNDER HEADS OF BEARING CAP BOLTS, APPLY TITE-SEAL (A50CD427A) ON BEARING CAP SCREWS, RABBETS AND PLUG THREADS. GROUND PAD F1 MOUNTING
Loading...