GE Industrial Motors M9407 Product Information Packet

Product Technical Information
June 24, 2020
Data shown is for the current revision model #. Ensure your nameplate model # matches.
Model Number:
5KS184XAA325B
Catalog Number:
M9407
Instruction Manual:
GEI-56128
Connection Diagram:
GEM2034E-FIG1
Outline Drawing:
4002B5818PDP5310
Accessory Connection Diagrams
Bearing Thermocouple:
None
Heater:
None
RTD:
None
Thermistor:
None
Thermostat:
None
Winding Thermocouple:
None
Bearing RTD:
None
Table of Contents
Specification
01
Performance Characteristics
02
Outline Drawing
03
Connection Drawing(s)
04
Spare parts
05
Model Number:5KS184XAA325B
June 24, 2020
Page | 1
Marks:
MODEL NUMBER:
5KS184XAA325B
Estimated Weight:
101 Lbs
Outline Drawing:
4002B5818PDP5310
Time Rating:
CONT
Connection Diagram:
GEM2034E-FIG1
Enclosure:
TEFC
Instruction Book:
GEI-56128
Encl Construction:
841
Design Code:
18BD3002A
Ambient Max(°C):
40
Type:
KS
Alt Ambient Max(°C):
--
Frame:
184TC
Insulation Class:
H
Phases:
3
NEMA Design:
B
Poles:
6
Nominal Efficiency:
88.5 %
Output Power:
2HP 1.5KW
Guaranteed Efficiency:
87.5 %
RPM:
1170
3/4 Load Efficiency:
88.6 %
Voltage:
460
KVA Code:
L
Hertz:
60
Max KVAR:
1.2
Amps - FL:
3.0
Power Factor:
69.5
Service Factor:
1.15
Bearing - DE:
6307ZC3
Alt Service Factor:
--
Bearing - ODE:
6206ZC3
Enclosure is Totally Enclosed Fan-Cooled Stamped Nameplate Notes:
IEEE-STD-841-2009 DE BRG 35BC03JP30 ODE BRG 30BC02JP30 STAMP NP249A5564P051 AS BELOW: MODEL:5KS184XAA325B S/N: XXX CSA CERTIFIED CSA09.2216219 FOR EX NA IIC 200C GC CL 1 ZONE2 AEX NA IIC 200C;CL 1 DIV2 GRP ABCD 200C IN -25C <= AMB <= 40C, 1.0 SF ON SINE-WAVE PWR SURF TEMP 200C AT 1.15SF ON SINE-WAVE PWR OR 200 C VT OR 200 C CT OR 200 C CHP PWM CONTROL ALTERNATE RATING FOR PWM CONTROL 1.0SF 40C AMB VT 0-60 HZ, CT 3-60 HZ, CHP 60-90 HZ.
Model Number:5KS184XAA325B
June 24, 2020
Page | 2
Additional Information:
6P - T EXTN C/BOX 55 CU IN-1.00 NPT "C" FACE AT DE ENDSHIELD ROUND FRAME VERTICAL MOUNT SHAFT DOWN WITH DRIPCOVER PAINTED FRAME ID & SHAFT, FAN COVER INSIDE & ODE E/S OUTSIDE ROUTINE AND 5 POINT VIBRATION TESTS INCL IN C/BOX INPRO SEAL BOTH ENDS BURNDY SERVIT POST ON FRAME SHAFT RUNOUT LIMIT .001" TIR COPPER WASHER UNDER HEADS OF BEARING CAP BOLTS APPLY TITE-SEAL (A50CD427A) ON BEARING CAP SCREWS, RABBETS, AND PLUG THREADS OIL RESISTANT SLEEVING ON LEADS
Loading...
+ 4 hidden pages