GE’s VH Series UPS is a true VFI (Voltage and Frequency
Independent) on line, double conversion range providing
the highest and most secure level of power protection for all
business-critical applications. With a tower and/or rackmount
design, the UPS adapts to adjusting network congurations
as facility load requirements change. Delivering 0.9 output
power factor, an MTBF of 730,000 hours and provided with a
three year warranty as standard on both UPS and battery, the
user can be assured of a high performance, high power and
highly reliable level of power protection.
• True Double Conversion VFI (Voltage and
Frequency Independent) technology
• Unique Superior Battery Management
• Hot swappable batteries
• Rack and/or tower assembly
• 3 year warranty
• High output power factor
Features & benets
• Voltage and Frequency Independent (VFI) double
conversion, true on line technology
Even when the quality of the utility is poor, the UPS will
deliver a constant voltage and frequency to the critical
load. When the utility fails, the UPS transfers seamlessly to
battery.
• 0.9 output power factor
Delivers more actual power to the load; highly suited for
today’s power-dense servers and data centers.
• Easy, fast user battery replacement
Hot swappable battery replacement. UPS may remain live,
supporting the critical load, during the battery replacement
period (<1 minute).
• Tower and/or rackmount, small footprint
2U high across range to maximise rack space. All assembly
parts for tower and rack assembly delivered in packing box.
• Failsafe bypass
The fully isolated bypass, designed with a fast and reliable
static switch, provides a seamless transition from UPS to
bypass if multiple fault conditions (e.g. overtemperature or
overload) occur.
• Superior Battery Management
Unique 7-level battery management providing protection
to the battery and extending the battery life.
• Matching battery cabinets
Longer battery life available with the addition of extra
battery cabinet(s).
• Unique high peak load handling
The VH Series standard design allows the user to support
a laser printer type load on the UPS without risking UPS or
battery performance.
New
VCL Series
800/1100/2000/3000 VA
Uninterruptible Power Supply (UPS)
GE’s VCL Series Uninterruptible Power Supply (UPS) is
designed with Automatic Voltage Regulation (AVR) including
buck/boost technology, suppressing or boosting the voltage
from the utility to provide conditioned power to the attached
load. Buck/boost minimizes the need to transfer to battery,
maximizing the battery life. When the grid power fails, the
battery steps in to continue the supply and allow for enough
time to nish the current process before gracefully initiating
an automatic shutdown of the load until the utility power
returns.
Features & benets
• High eciency
The VCL Series operates as standard at a >95% reducing
both energy and operational costs at site.
• Hot swappable, user replaceable batteries
Batteries can be replaced quickly, safely and simply while
the load remains connected, eliminating the need to power
o a critical load for standard maintenance and with zero
risk to the user.
• Wide input voltage window
Minimises battery use and extends the life of the battery.
Allows the VCL Series to run undisturbed, when other UPS
may have already switched to battery then shut down.
• Voltage Independent technology with
Automatic Voltage Regulation (AVR)
• Hot swappable batteries
• High efficiency
• Rack and/or tower assembly
• 2U rack height
• Graphic display
• Multiple outlets
For all ratings; several pieces of equipment can be
connected to the VCL Series without adding PDUs or
extension strips.
• Free automatic shutdown software
GE’s Automatic Shutdown Software is delivered with each
UPS, allowing for a graceful, controlled shutdown of the
connected load in the event of a lengthy mains failure.
Data protection software and connectivity solutions
GE’s UPS come standard with two software packages: UPSMAN and RCCMD.
UPSMAN is a complete protection software providing a graphical interface for monitoring the UPS. It communicates with the
UPS via the standard RS232 / USB interfaces or via an optional SNMP plug-in card. In order to avoid data corruption it enables
the computer on which it is installed to shutdown gracefully if the UPS is not able to supply the required power. UPSMAN can
also act as a “master computer” which can send remote shutdown commands to multiple remote computers/servers in
case of a UPS failure. These remote computers/servers, centrally controlled by a computer running UPSMAN, need to
run on their turn the light software package named RCCMD.
Small
networks
UPSMAN – description
• Data Protection Software
• Supports RS232 , USB & SNMP communication
• Free software license
• Written in native language
• Supports most popular OS, including virtualization
As an alternative for the solution above, with a “master
computer” controlling multiple remote computers in a
network, the UPS can be equipped with an SNMP card.
This card sends the required remote shutdown commands
directly to the remote network computers, which again all
run the software RCCMD.
RCCMD – description
• Light background protection software
• Native solution for more than 35 OS
• React on shutdown commands
Electronic
point of sale
(EPOS)
GE’s iUPSGuard is a remote monitoring solution for UPS,
providing status monitoring and alarm notication that
supports all GE UPS product lines, anytime, anywhere.
iUPSGuard provides current and detailed information about
UPS operation, including its conguration, internal alarms,
automatic reporting and operating conditions over the web.
• Highly secure and efficient data transmission
• SSL encrypted unidirectional communication
• Firewall friendly – no changes required to firewall
settings or proxy servers providing easy deployment and
addressing compliance objectives
• Supports various communications including IP and GPRS
PCs
Servers
CCTV
Servers
VCL Series
Telecom
Medical
VHSeries
Process
Control
VH Series - Technical specications
Model
Rating VA/W
Part number25510255112551225513
AC input voltage window60 - 140 Vac
Input frequency range45 - 66 Hz
AC output voltage100 / 110 / 115 / 120 / 127 Vac (selectable)
AC output voltage tolerance± 2%
Output frequencyauto-selectable or 50/60 Hz (front selectable)
Output frequency stability± 0.15%
Output wave formsine wave
Output power factor0.9
Crest factor6:1
Output THD< 2% (typical 1%) with linear load
Battery type12V, sealed lead acid, maintenance free
Number x capacity of battery3 x 7Ah3 x 9Ah6 x 7Ah6 x 9Ah
Runtime at typical load (75%), minutes12121112
Battery recharge time3 hours for 90% capacity, std. battery
Input connectionIEC C14IEC C14IEC C20IEC C20
Output connection4x NEMA 5-20R6x NEMA 5-20R6x NEMA 5-20R6x NEMA 5-20R & 1x L5-20R
Weight35 Lbs (16 kg)37 Lbs (17 kg)64 Lbs (29 kg)71 Lbs (32 kg)
Dimensions (hxwxd)3.4 x 17.2 x 18.5 inch (87 x 438 x 470 mm)3.4 x 17.2 x 21.3 inch (87 x 438 x 540 mm)
Communication portUSB / RJ11
SafetyETL tested to UL1778 Standards
EMCEN 62040-2
Ambient temperature32 °F to 104 °F (0 °C to 40 °C)
Maximum relative humidity95% (non-condensing)
VH700 UL
700/630
VH1000 UL
1000/900
VH1500 UL
1500/1350
VH2000 UL
1920/1740
Option list for VH UPSPart number
Battery Pack UL 36V 14Ah (VH 700/1000)25268
Battery Pack UL 72V 14Ah (VH 1500/2000)25269
SNMP / Web Adapter Card 1-ph (for VH)1024747
RS232, USB & Relay Card18802
iUPSGuard 1 yr license26104
Rear panel VH Series
1000VA UPS
Fans
DC connector
for battery extension
Specications subject to change without prior notice
Input circuit breakerRJ11 communication port
Input socketUSB communication port
Appliance outlets
VCL Series - Technical specications
Model
Rating VA/W
VCL800 UL
800/640
VCL1100 UL
1100/880
VCL2000 UL
1920/1600
VCL3000 UL
2880/2400
Part number25926259272592825929
AC input voltage120 Vac
AC input voltage, window90 - 150 Vac
Frequency50 / 60 Hz ± 5 Hz (auto-sensing)
Power factor0.8
AC output voltage120 Vac
AC output voltage tolerance (until low battery)± 5%
Output frequency50 / 60 Hz ± 1% (auto-sensing)
Output frequency stability< ± 0.1 Hz (battery operation)
Output wave formsine wave
Crest factor3:1
Output THD< 8% with linear load
Input connectionNEMA 5-15PNEMA 5-20PNEMA L5-30P
Output connection6 x NEMA 5-15R6 x NEMA 5-20R
Runtime at typical load (60%), minutes8899
Weight30 Lbs (13.5 kg)33 Lbs (15 kg)55 Lbs (25 kg)73 Lbs (33 kg)
Dimensions (hxwxd)3.5x17.3x16.0 inch (88x440x405 mm) 3.5x17.3x24.4 inch (88x440x620 mm)
SafetyETL tested to UL1778 Standards
Ambient temperature32 °F to 104 °F (0 °C to 40 °C)
Sound at 1 meter<55 dB(A), load and temperature dependent
Maximum relative humidity95% (non-condensing)
Option list for VCL UPSPart number
Specications subject to change without prior notice
SNMP / Web Adapter Card 1-ph (for VCL)1024746
iUPSGuard 1 yr license26104
Front panels
VH SeriesVCL Series
Rear panel VCL Series
USB communication portOptional SNMP communication card
test
VH Series - Uninterruptible PowerSupply
Input thermal circuit breaker
Input cord
Output thermal circuit breakers
Digital Energy
%
100
75
50
25
Phone/fax protectionRS232 communication port
>
UPS status indicators
Keypads
Load LED bar
Runtime capacity
test
VCL Series - Uninterruptible Power Supply
3000VA UPS
Appliance outlets
Digital Energy
%
100
75
50
25
>
imagination at work
GEA-D 1057 US UL listed product version Rev. 12/15
1027712 / 151209
*Trademark of General Electric Company.
Copyright 2015 General Electric Company. All Rights Reserved.
GE reserves the right to make changes to specications of products
described at any time without notice and without obligation to notify
any person of such changes.