GE - General Electric Series EP100ULH Tripping Curves

ElfaPlus with UL approvals
Characteristic tripping values Let-through I2t values
time (s)
10000
1000
100
10
1
0.1
Characteristic tripping values
B C D
Lower limit
2
I
t (A2s)
100000
10000
B curve / I2t characteristics
B63 B50 B40 B32 B25 B20 B16 B10 B6
Line protection
Intro
A
B
C
D
X
0.01
0.001
Tripping characteristic acc. to UL 489
1. Conventional non tripping current Rated Current = 1.0 (T
2. Conventional tripping current Rated Current = 1.35 In t<1h (T
3. 2.0 In (Ta 25°C)
0.5A < Rated Current ≤ 30A t < 120s 30A < Rated Current ≤ 50A t < 240s 50A < Rated Current ≤ 63A t < 360s
a
25°C)
101 100
current (x In)
Instantaneous tripping acc. to IEC 60898-1
Type B 3 Rated Current t > 0.1s 5 Rated Current t < 0.1s
a
25°C)
Type C 5 Rated Current t > 0.1s 10 Rated Current t < 0.1s Type D 3 Rated Current t > 0.1s 5 Rated Current t < 0.1s
Internal resistances and power losses per pole, loads with rated current
Power losses - Series EP100ULH
B curve - Power loss (W) C-D curve - Power loss (W)
Rated
Current (A)
0.5 - - - 1.18 2. 35 3.53 1 - - - 1.33 2.67 4.00 2 - - - 1.30 2.60 3.91 3 - - - 1.64 3.28 4.91 4 - - - 1.56 3.13 4.69 5 1.65 3.30 4.95 1.65 3.30 4.95 6 1.65 3.30 4.95 1.65 3.30 4.95 8 1.30 2.60 3.91 1.30 2.60 3.91
10 1.64 3.28 4 .91 1.64 3.28 4.91 13 2.11 4.22 6.33 2.11 4.22 6 .33 15 2.70 5.40 8.10 2.70 5.40 8.10 16 2.70 5.40 8.10 2.70 5.40 8.10 20 2.90 5.80 8.69 2.90 5.80 8.69 25 3.35 6 .70 10.05 3.35 6 .70 10.05 30 3.22 6.45 9.67 3.22 6.45 9.67 32 3.22 6.45 9.67 3.22 6.45 9.67 35 3.57 7.14 10.71 3.57 7.14 10.71 40 4.20 8.40 12.60 4.20 8.40 12.60 50 4.73 9.45 14.18 4.73 9.45 14.18 60 5.42 10.84 16.25 5.42 10.84 16.25 63 5.42 10.84 16.25 5.42 10.84 16.25
1P 2P 3P 1P 2P 3P
1000
1 2 3 4 5 6 7 8 9 10 Icc kA
2
I
t (A2s)
100000
10000
1000
1 2 3 4 5 6 7 8 9 10 Icc kA
I2t (A2s)
100000
10000
1000
1 2 3 4 5 6 7 8 9 10
C curve / I2t characteristics
D curve / I2t characteristics
Icc kA
C63 C40 C25 C16 C6 C2
D63 D50 D40 D32 D25 D20 D16 D10 D6 D4 D2