Molded Case Circuit Breakers
Section 6
Molded Case Switches
100-1200A
Molded Case Switches Spectra™RMS
UL File E-57546, CSA LR 91464, Includes fixed, high-set Instantaneous trip suitable for reverse feed.
1
Switch
Frame Ampere
Type Rating Product Number Product Number Wire Range 240 Vac 480 Vac 600 Vac
SE150
SF250
SG600
SK1200 1000 SKDA36AN1000 TCAL125 Aluminum: (4) 250-500 kcmil
100 SEDA36AN0100 TCAL18 Aluminum: #12-3/0 200 100 25
150 SEDA36AN0150 Copper: #14-3/0
250 SFDA36AN0250 TCAL29 Aluminum: #8-350 kcmil 200 100 25
400 SGDA36AN0400 3-pole lug kit Aluminum: (2) 2/0-500 kcmil 200 100 65
600 SGDA36AN0600 TCLK365
800 SKDA36AN0800 TCAL81 Aluminum: (3) 3/0-500 kcmil
1200 SKDA36AN1200 Copper: (4) 250-500 kcmil
Molded Case Switches Nonautomatic Trip, Includes Cu/Al line and load lugs. For optional lugs, see page 6-103 and 6-104.
Type Ampere Rating Number of Poles Voltage Rating Product Number
TEB 100 1 120 Vac, 125 Vdc TEB111Y100
TEB 100 2 240 Vac, 250 Vdc TEB122Y100
TEB 100 3 240 Vac TEB132Y100
TEB 100 3 240Vac TEB132Y T100
TED 100 1 277 Vac, 125 Vdc TED113Y100
TED 100 2 480 Vac, 250 Vdc TED124Y100
TED 100 3 480Vac, 250Vdc TED134YT100
TED 100 3 600Vac TED136YT100
TED 100 3 600Vac TED136YT100A
TED 150 2 480 Vac, 250 Vdc TED124Y150
TED 150 3 480Vac, 250Vdc TED134YT150
TED 150 3 600Vac TED136YT150
TFJ 225 2 600 Vac TFJ226Y225
TFJ 225 3 600 Vac TFJ236Y225
TJJ 400 2 600 Vac, 250 Vdc TJJ426Y400
TJJ 400 3 600 Vac TJJ436Y400
Type Ampere Rating Number of Poles Voltage Rating Product Number
TFK 225 2 600 Vac, 250 Vdc TFK226Y225
TFK 225 3 600 Vac, 250 Vdc TFK236Y225
TJK 400 2 600 Vac, 250 Vdc TJK426Y400
TJK 400 3 600 Vac, 250 Vdc TJK436Y400
TJK 600 2 600 Vac, 250 Vdc TJK626Y600
TJK 600 3 600 Vac, 250 Vdc TJK636Y600
TKM 800 2 600 Vac, 250 Vdc TKMA826Y800
TKM 800 3 600 Vac, 250 Vdc TKMA836Y800
TKM 1000 2 600 Vac, 250 Vdc TKMA2Y1000
TKM 1000 3 600 Vac, 250 Vdc TKMA3Y1000
TKM 1200 2 600 Vac, 250 Vdc TKMA2Y1200
TKM 1200 3 600 Vac, 250 Vdc TKMA3Y1200
1
No rating plug required.
2
The maximum withstand rating is limited by the application to the value set forth in this table or the short circuit rating of the upstream fuse or circuit breaker, whichever is
less. The upstream protective device must have an instantaneous trip function or element and its rated ampacity may not exceed the ampere rating of the switch.
3
Order one kit for either line or load end; two kits required for both.
4
Internal accessory requires factory installed dummy trip. Specify on order. Accessories not available for one-pole TEB, TED.
5
Not UL listed.
6
600 Volts max.
7
Internal accessory requires factory installed dummy trip unit. See page 6-44 for additional details. Nonautomatic trip unit and dummy trip not UL listed for field installation.
8
UL listed only when ordered as a complete switch.
9
Includes factory installed dummy trip for accessory installation.
10
Includes factory installed dummy trip and TCAL12A lugs.
11
Limited availability. Obsolete when inventory is depleted.
Terminal Lugs for Maximum Short Circuit Withstand Rating
Front Connection (Cu/Al) (kA rms symmetrical)
Copper: #8-350 kcmil
3
or (1) #8-600 kcmil
Copper: (2) 2/0-500 kcmil
or (1) #8-600 kcmil
Copper: (3) 3/0-500 kcmil 100 65 42
4
4
4
9
4
4
9
9
4,5
9
9
4,6,11
6,11
7
7
6,7,8,11
7,8,11
7
7
7
7
7,11
7,11
7,11
7,11
7,11
7,11
10
2
6-90
BuyLog™Catalog
Rev. 11/13
Data subject to change