GE - General Electric IEC Power Devices Part Numbering Designation

EC Power Devices
I
IEC Assembled Starters Nonreversing AC
C-2000
Step-By-Step Selection and Pricing
ection 5
S
This step-by-step process will allow you to select and price your assembled starter.
In each step, find the options—contactor, coil, overload relay, etc.—you need. Transfer the product number digits and price components to the corresponding boxes at the bottom of page 5-102.
When you have finished the appropriate number of steps for your starter, you will have built a complete product number and established the prices that add up to a total list price, GO-10CA.
Not all starters require completion of all steps; note minimum and optional steps required for various starters in the product number and price line form. (Photocopying this form will allow for its repeated use.)
Select
Contactor
Select contactor and enclosure. Transfer the product number digits to the boxes marked in the product number line and the price to the box marked in the price line.
sepower (60 Hertz)
Hor
Single-Phase Three-Phase
Contact
or
CL00 10
CL01
CL02
CL25
CL04
CL45
CL06
CL07
CL08
CL09
CL10
CK75
CK08
CK09
CK95
CK10
CK11
CK12
1
C10C
KA
Max.
115 V
FLA Open
13.8
17.5
22
32
34
48
62
68
80
96
140
156
192
302
398
480
602
C11C are for use with maximum fuse 1000A, and maximum breaker 600A. For higher ratings, substitute “C” version with “B” version in product digit six.
and KA
230 V 200 V 230 V 460 V 575 V
Product No.
Digits
ev. 8/15
R
and data subject to
Contr
ol Catalog
5-99
EC Power Devices
beginning with
KAC
60 Hz 50 Hz
60/50 Hz
(AC/DC)
For Prod. Nos. For Prod. Nos.
beginning
with LAC
beginning
with KAC
2424
1
24-28
D
48
42 42-48 F
120
110 110-127 J
208 L2
08
277
220/230 220-250 N 220-240
240 S
480
380/400 380-415 U 480
415
W
600
500 440-500 Y 600
beginning with
LAC
Primary Circuit Voltage (for CPT)
Product Number Digit
Coil (control circuit voltage)
Prod.
No.
Digit
Primary
Volts
For Product Nos. For Product Nos.
beginning LAC beginning KAC
None
Class 10
Class 30
F
ZZ
WW
Manual/ Automatic Reset
Product Number Digit
Overload Type
Ove
r-
load
Amp
Range
Over-
load
Amp
Range
Over-
load
Amp
Range
Over-
load
Amp
Range
Over-
load
Amp
Rang e
Over-
load Amp
Range
Over-
load
Amp
Range
——
11.5-15
—— ——
120-190
——
120-190 A
0.16-.26 14.5-19 55-80
——
175-280
——
175-280 B
0.25-.41 18.5-25 63-90
——
250-400
——
250-400
C
0.4-.65 24-32 90-120
——
315-500
——
315-500 D
——
30-43 110-140
——
430-650
——
430-650 E
.65-1.1
——
140-190
—— —— —— ——
F
1-1.5 42-55
—— —— —— — — ——
G
1.3-1.9 54-65
—— —— —— — — ——
H
1.8-2.7 64-82
—— —— —— — — ——
J
2.5-4.1
—— —— —— ——
45-70
——
K
4-6.3 78-97
—— —— ——
60-90
——
L
5.5-8.5 90-110
—— —— ——
80-125
——
M
8-12
—— ——
120-190
——
120-190
——
N
10-16
—— ——
175-280
——
175-280
——
P
—— —— ——
200-310
——
200-310
——
R
14.5-18
—— —— —— —— —— ——
S
17.5-22
—— —— —— —— —— ——
T
21-26
—— —— —— —— —— ——
U
25-32
—— —— —— —— —— ——
V
30-40
—— —— —— —— —— ——
W
None 0 None 0 None 0
——
None 0 None 0 None 0 Z
For Product Nos. For Product Nos. For Product Nos. For Product Nos. For Product Nos. For Product Nos. For Product Nos.
beginning
LAC00-LAC45
beginning
LAC06-LAC10
beginning
KAC75-KAC08
Class 10
beginning
KAC09-KAC95
beginning
KAC10-KAC12
Product No.
Digi t
Class 30
beginning
KAC09-KAC95
beginning
KAC10-KAC12
I
IEC Assembled Starters Nonreversing AC
C-2000
Step-By-Step Selection and Pricing
Coil Voltage
Select
À
Select coil based on control circuit voltage or, if you plan to add a control power transformer (step ), on primary circuit voltage instead. Transfer the product number digit to the boxes marked À in the product number line. Note that there is no price component to this step.
Select
Ã
Select overload type. Transfer the product number digit to the box marked à in the product number line. Note that there is no price component to this step.
Overload Type
ection 5
S
Select
Õ
Overload Rating
From among the columns that correspond both to your product number from step and to the overload class (10 or 30) from step Ã, select the specific amp range (be sure to observe the maximum FLA rating for your starter as indicated in step ). Transfer
the product number digit to the box marked Õ in the product number line and the price to the box marked Õ in the price line.
5-100
Contr
ol Catalog
ev. 8/15
R
and data subject to
EC Power Devices
Contacts Product Number Digit
None A
1NO-1NC B
C
2NO
This is the last step in selection of open star
ters.
No.
Digit
No
.
Digit
None A A
START/STOP push button B B
HOA selector switch C C
ON-OFF selector switch D D
Operator
For Prod. Nos. beginning LAC in Type 1 enclosures
For Prod. Nos. beginning
LAC in Type 12/3R or
Type 4 enclosures or
KAC in any enclosure
Prod. Prod.
Indicating Light
Pro
d. Prod.
No.
Digit
No.
Digit
None A A
Red RUN across coil B B
Red RUN across NO auxiliary contact
C C
Red RUN across coil & green STOP across NC auxiliary contact
D
Red RUN acr
oss NO auxiliary contact & green STOP across NC auxiliary contact
E
Green STOP across NC auxiliary contact
F
Green RUN across coil G
For Prod. Nos.
beginning
LAC in
Type 1 enclosur
es
For Prod. Nos. beginning
LA
C in Type 12/3R or
Type 4 enclosures or
KA
C in any enclosure
NEMA Type 1
NEMA Types
12/3R NEMA Type 4
With reset 1 2 4
Without reset 5 6 8
Pr
oduct No. Digit
I
IEC Assembled Starters Nonreversing AC
C-2000
Step-By-Step Selection and Pricing
Auxiliary Contacts
Select
Œ
Select additional auxiliary contacts. Transfer the product number digit to the box marked Œ in the product number line and the price to the box marked Œ in the price line. A holding interlock is standard.
Enclosure
Select
œ
Select enclosure. Transfer the product number digit to the box marked œ in the product number line and the price to the box marked œ in the price line. Note that your enclosure selection here MUST agree with that made in step ∂. Note, too, that the price component for this step is $0.00 for units with reset and an $8.00 subtraction for units without reset.
Select
Select operator. Transfer the product number digit to the box marked – in the product number line and the price to the box marked – in the price line. Be sure your selection agrees with your contactor selection in step ∂.
Select
Select indicating light. Transfer the product number digit to the box marked in the product number line and the price to the box marked in the price line. Be sure your selection agrees with your contactor selection in step .
Operator
Indicating Light
ection 5
S
This is the last step required for selection of enclosed starters. If desired, select operators, indicating lights and CPTs in steps – to .
ev. 8/15
R
and data subject to
Contr
ol Catalog
5-101
EC Power Devices
For Product Numbers For Product Numbers
beginning with LAC beginning with KAC
Standard 50 250
Extra VA 150 300
I
ection 5
S
IEC Assembled Starters Nonreversing AC
C-2000
Step-By-Step Selection and Pricing
Control Power Transformer
Select
Select control power transformer. Transfer the product number digit to the box marked in the product number line and the price to the box marked in the price line. Be sure your selection agrees with your contactor selection in step .
CPT VA
For Prod. Nos. For Prod. Nos.
beginning LAC beginning KAC
Prod. No. Prod. No..
Control Power Transformer
None
Fused control circuit (without control transformer)—one fuse
Separate control circuit C C
Fused separate control circuit (one fuse)
Control transformer, standard capacity, 110-120 V 50/60 Hz secondary voltage, one secondary fuse, two primary fuses
Control transformer, extra capacity, 110-120 V 50/60 Hz secondary voltage, one secondary fuse, two primary fuses
Digit GO-10CA Digit
B B
D
F F
H H
D
-------------------------------------------Minimum steps for enclosed starter-----------------------------------------------------
---------------------------------Maximum steps for open starter------- -------------- --------------- -------------- ---
------------------------------------Minimum steps for open starter------- -------------- --------------- -
Pr
oduct
Price +0 +0
e: Product Number should not end in a “None” option.
Not
For example, KAC08CJZZA should be KAC08CJ.
Contr
ol Circuit Fusing
er the NEC and UL508 Section 18.2 - Control Circuit Fuses must be used when the
P branch circuit protective device rating is too large to serve as protection for the con­trol circuit. This depends on the control wire size and whether all control circuit wires are within the enclosure. See table below:
ovide supplemental control circuit protection if control circuits with wires longer
Pr
12 inches are connected to branch circuit protection exceeding the ratings below
than
Control Maximum Branch Circuit Maximum Supplemental
Circuit Protection Rating (Amperes) Control Circuit
Wire Size Conductors Conductors Protection Rating
WG) within Enclosure outside Enclosure (Amperes)
(A
22 12 33 20 20 55 18 25 77 16 40 10 10 14 100 45 20 12 120 60 25
Optional steps
for enclosed
--------------starter---------- ---
=
Complete Prod. No.
T
he factory must provide this protection, if the circuit provided by the factory requires
the fuses. The factory will provide control circuit fuses in enclosed starters and con­tactors with pilot devices, control relays or other control components that are factory wired; when used with line voltage control; when the size listed below is being supplied.
Non-combination starters (LAC, LAR, LAD, KAC, KAR, KAD)
Supplied with: —CL10 Contactors and Larger —Overload Relays 90 amps and larger
Control Circuit fuses must be added to the enclosed starter or contactor pricing.
All CPTs in enclosed control will be supplied with primary fuses. CPTs without primary
fuses are no longer available.
When control circuit fuses are not factory supplied, customer provided wiring
or branch circuit protection sizing to these contactors and starters may still require that the customer/installer add the fusing in the field. It will be the customer/installer’s responsibility to ensure code compliance under these conditions.
= $$
5-102
Contr
ol Catalog
ev. 8/15
R
and data subject to
IEC Power Devices
Using contactor with CL prefix
Using contactor with CK prefix
11
Family Name
Starter
Size
Contactor
Family Version
Coil
Selection
Overload Selection
Overload
Amp Range
Auxiliary
Contacts
Enclosure
Operator
Lights
CPT
Using contactor with CL prefix
Using contactor with CK prefix
11
Family Name
Starter
Size
Contactor
Family Version
Coil
Selection
Overload Selection
Overload
Amp Range
Auxiliary
Contacts
Enclosure
Operator
Lights
CPT
Using contactor with CL prefix
Using contactor with CK prefix
11
Family Name
Starter
Size
Contactor
Family Version
Coil
Selection
Overload Selection
Overload
Amp Range
Auxiliary
Contacts
Enclosure
Operator
Lights
CPT
LAD
KAD
Reversing using contactor with CL prefix
Nonreversing using contactor with CL prefix
11
Family Name
Starter
Size
Contactor
Family Version
Coil
Selection
Overload Selection
Overload
Amp Range
Auxiliary
Contacts
Enclosure
Operator
Lights
CPT
LDR
LDC
For Contactor
with CK prefix
60 Hz 50 Hz 60/50 Hz or DC
1
D
F
J
L
N
S
U
W
Y
Number
or Digit
For Contactor with CL Prefix
Digit Class
W Class 10
F
1
Class 30
Overload Type/Class
Manual/Automatic
1
Class 30 overloads available with CK09-CK12 contactors only.
Digits Description Contactor Prefix
LAC Assembled nonreversing starters CL
KAC Assembled nonreversing starters CK
LAR Assembled reversing starters CL
KAR Assembled reversing starters CK
LAD Assembled wye-delta starters CL
KAD Assembled wye-delta starters CK
LDC Assembled nonreversing starters (DC controll ed) CL
LDR Assembled rev ersing starters (DC controlled) CL
115 V 230 V 200 V 230 V 460 V 575 V
380-
415 V
00 10 0.5 1.5 3 3 5 7.5 4
01 13.8 0.75 2 3 3 7.5 10 5.5
02 17.5 1 3 5 5 10 15 7.5
25 22 1.5 3 5 7.5 15 15 11
04 32 2 5 10 10 20 25 16
45 34 3 5 10 10 25 25 18.5
06 48 3 7.5 15 15 30 40 22
07 62 5 102020405030
08 68 5 152025506037
09 80 7.5 15 25 30 60 75 45
10 96 10 20 30 40 75 75 55
75 140 10 25 40 50 100 125 75
08 156 15 30 50 60 125 125 90
09 192 60 75 150 150 132
95 302 100 100 250 300 160
10 398 125 150 300 400 220
11 480 150 200 400 500 280
12 602 200 250 500 600 375
KW
50 Hz
Single-Phase
CL
CK
Max.
Amps
@460 V
Horsepower (60 Hz)
Three-Phase
Contactor
No.
Digits Description
A
Contactor with CL prefix
B
Contactor with CK prefix
C
Contactor with CK prefix
IEC Assembled Starters Selection Guide
C-2000
Nonreversing Starters - AC
Reversing Starters - AC
Nonreversing Starters - Wye-delta
Reversing/Nonreversing Starters - DC controlled
Section 5
Family Name
Starter Size
À
Rev. 8/15
Prices and data subject to change without notice
Contactor Family Version
Ã
Coil Selection
Õ
Overload Selection
Œ
Control Catalog
5-97
IEC Power Devices
Digits Description
BControl Circuit Fusing
CWired For Separate Control
D Separate Control and CCF
FStandard CPT, 110-120 V Sec (One Sec Fuse, Two Primary Fuses)
HCPT + ExtraVA, 110-120 V Sec (One Sec Fuse, Two Primary Fuses)
Digit
Class 10 Class 10 Class 10
Class 10
and
Class 30
Class 10
and
Class 30
CL00-CL45 CL05-CL10 CK75-08 CK09-95 CK10-12
A 11.5-15 120-190
B 0.16-0.26 14.5-19 55-80 175-280
C 0.25-.41 18.5-25 63-90 250-400
D 0.4-.65 24-32 90-120 315-500
E 30-43 110-140 430-650
F .65-1.1 140-190
G 1-1.5 42-55
H 1.3-1.9 54-65
J 1.8-2.7 64-82
K 2.5-4.1
L 4-6.3 78-97
60-90
(Class 30 only)
M 5.5-8.5 90-110
80-125
(Class 30 only)
N 8-12 120-190
P 10-16 175-280
R 200-310
S 14.5-18
T 17.5-22
U 21-26
V 25-32
W 30-40
For wye-delta starters, overload current rating is determined by multiplying motor amps x .58.
Amp Range
Digits Description
A
B1NO-1NC
C2NO-0NC
None
Digits or Number Description
NEMA 1 w/Reset
2N
1
EMA 12/3R w/Reset
4NEMA 4 w/Reset
5NEMA 1, no Reset
6NEMA 12/3R, no Reset
8NEMA 4, no Reset
Digits Description
A
BStart/Stop Push Button
None
C H-O-A Selector Switch
D On/Off Selector Switch
EForward/Off/R everse Selector Switch
FForward/R everse Selector Switch with Start/Stop Push Button
GForward/Stop/Reverse Push Buttons
Digits Description
A
B RIL X-Coil
None
C RIL NO Aux.
D RIL X-Coil, GIL NC Aux.
E RIL NO Aux., GIL NC Aux.
F GIL NC Aux.
G GIL X-Coil
Digits Description
BRIL/Forward, WIL/Rev. X-Coil
CRIL/Forwa rd, WIL/Rev. X NO
D RIL/Forward, WIL/Rev. X-Coil, GIL NC Aux. (2 in series)
ERIL/Forward, WIL/Rev. X-NO, GIL NC Aux. (2 in series)
F GIL NC Aux. (2 in series)
Digits Description
B
RIL X-Coil
D RIL X-Coil, GIL NC Aux.
HRed/Run, Y/Start X-Coil
JRed/Run, Y/Start X-Coil, GIL NC Aux.
IEC Assembled Starters Selection Guide
C-2000
Section 5
Overload Amp Range
œ
Lights
For Starters
For Reversers Only
For Wye-Delta Only
Auxiliary Contacts
Enclosure
Operator
5-98
Control Catalog
11
CPT
Rev. 8/15
Prices and data subject to change without notice
Loading...