Logic Control
IEC Electronic Timers
Multivoltage Electronic Timers
Technical Data
Section 10
**Available Input Voltages
Direct supply Supplied with internal transformer
Current AC (50/60 Hz)/DC AC (50/60Hz)
Voltage 24-240 110-125 200-240 380-400
Product Number Code None AJ AM AU
NMETV
NMETVT
NMICV
NMIFV
NMIVV
NMMFV
NMRDV
NMRDV2
NMRDVT •• ••
NMTCIV
NMTCV
NMTCV2
NMTCVT
NMTDV
available
•
recommended stock
••
••
•• ••
••
••
••
••
••
••
••
••
••
•• ••
••
Rev. 8/15
Prices and data subject
to change without notice
Control Catalog
10-17
Section 10Logic Control
IEC Electronic Timers
Multivoltage Electronic Timers
Technical Data
NMTCV Delayed ON Timer
Electronic relay whose output contact connects with a certain adjustable delay from
the moment voltage is applied to supply terminals A1-A2. It has four timing ranges:
see drawing. Range selection is made by dip-switches located on the front of the relay.
Times are set by front potentiometer controlling an Application Specific Integrated
Circuit (ASIC) specially designed for this group of relays. This allows for excellent
precision and repeatability features.
Product Number NMTCV NMTCV2 NMTCVT
Number of Selectable NO-NC Contacts 121
Output Contacts Rated Insulation Voltage: Ui AC 250V 250V 250V
Output Contacts Rated Insulation Voltage: Ui DC 250V 250V 250V
Output Contacts Thermal Current Ith 6A 6A 6A
Utilization Category AC15 Rated Voltage Ue 120/230V 120/230V 120/230V
Utilization Category AC15 Rated Current Ie 2.5/1.3A 2.5/1.3A 2.5/1.3A
Utilization Category DC13 Rated Voltage Ue 120/230V 110/230V 110/230V
Utilization Category DC13 Rated Current Ie 0.2/0.1A 0.2/0.1A 0.2/0.1A
Supply Voltage: AC (with transformer) Un --110-125V, 200-240V, 380-440V
Supply Voltage: DC/AC (direct) 24-240V 24-240V -
Line Voltage Frequency 50/60 Hz 50/60 Hz 50/60 Hz
Supply Voltage Tolerance +10/-20% +10/-20% +10/-15%
Consumption (mA) 60 (24V), 15 (240V) 60 (24V), 15 (240V) -
Consumption (VA) --3.5
Input Circuit Test Voltage 2 kV 4 kV 4 kV
Switch ON Response Time 0.06 sec.-100 hrs. 0.06 sec.-100 hrs. 0.06 sec.-100 hrs.
Switch OFF Response Time 150 ms 150 ms 150 ms
Reset Time Between 2 Cycles 100 ms 100 ms 100 ms
Repeat Accuracy with 0.85 - 1.1 Un 1% 1% 1%
Weight 0.120, .26 lbs. 0.120, .26 lbs. 0.120, .26 lbs.
Approval & Standards VDE 0106, VDE 0110, EN 50001, EN 50002, CSA C 22.2 N° 14, UL 94, UL 508, IEC 255.5
For ambient conditions data see page 10-24, Table 2. The relays have a green LED that lights when the relay is energized (flashing during the timing) and a red LED that
lights when the output contact is made.
10-18
Control Catalog
Rev. 8/15
Prices and data subject
to change without notice