GE - General Electric IEC Contactors Thermal Overload Relays Catalog

IEC Power Devices
IEC Contactors Thermal Overload Relays
C-2000
Overload Relays Fixed Heater
Overload relays may be set for 4 different operational modes—manual reset only, automatic reset only, manual reset/stop, or automatic reset/stop. Stop is initiated by push­ing the reset button which interrupts the holding circuit in the latter two listed modes.
Overload relays feature visible trip indication, reset on the upstroke, weld check, and trip test.
Reference Publications
Instructions
GEH-6237 RT1* (Class 10) Overload DEH-040 RT12* (Class 20) Overload GEH-6238 RT2* (Class 10) Overload DEH-041 RT22* (Class 20) Overload GEH-6239 RT3* (Class 10) Overload DEH-042 RT32* (Class 20) Overload GEH-6240 RT4* (Class 10, 30) Overload GEH-6241 RT5* (Class 10, 30) Overload GEH-5520 RT5 Overload Connection Kit DEH-055 Remote Electrical Reset
Section 5
RT1 Overload Relay
RT2 Overload Relay
RT3 Overload Relay
RT4 Overload Relay
RT5 Overload Relay
Control Catalog
5-53
IEC Power Devices
IEC Contactors Thermal Overload Relays
C-2000
RT1 - Direct Mount Manual
Overload Relay for use Current Range Maximum Fuse Maximum Circuit Breaker with Contactors
CL00, CL01, CL02, CL25, CL04, CL45 0.16-0.26 Manual Class 10 1 15 RTN1B CL00, CL01, CL02, CL25, CL04, CL45 0.25-0.41 Manual Class 10 1 15 RTN1C CL00, CL01, CL02, CL25, CL04, CL45 0.4-0.65 Manual Class 10 3 15 RTN1D CL00, CL01, CL02, CL25, CL04, CL45 0.65-1.1 Manual Class 10 6 15 RTN1F CL00, CL01, CL02, CL25, CL04, CL45 1-1.5 Manual Class 10 6 15 RTN1G CL00, CL01, CL02, CL25, CL04, CL45 1.3-1.9 Manual Class 10 6 15 RTN1H CL00, CL01, CL02, CL25, CL04, CL45 1.8-2.7 Manual Class 10 10 15 RTN1J CL00, CL01, CL02, CL25, CL04, CL45 2.5-4.1 Manual Class 10 15 15 RTN1K CL00, CL01, CL02, CL25, CL04, CL45 4-6.3 Manual Class 10 20 15 RTN1L CL00, CL01, CL02, CL25, CL04, CL45 5.5-8.5 Manual Class 10 25 15 RTN1M CL00, CL01, CL02, CL25, CL04, CL45 8.0-12.0 Manual Class 10 40 30 RTN1N CL01, CL02, CL25, CL04, CL45 10.0-16.0 Manual Class 10 50 35 RTN1P CL02, CL25, CL04, CL45 14.5-18 Manual Class 10 60 40 RTN1S CL25, CL04, CL45 17.5-22 Manual Class 10 70 50 RTN1T CL04, CL45 21-26 Manual Class 10 80 60 RTN1U CL04, CL45 25-32 Manual Class 10 100 80 RTN1V CL45 30-40 Manual Class 10 100 80 RTN1W
RT1 - Direct Mount Manual/Auto
Overload Relay for use Current Range Maximum Fuse Maximum Circuit Breaker with Contactors
CL00, CL01, CL02, CL25, CL04, CL45 0.16-0.26 Manual/Auto w/wo stop Class 10 1 15 RT1B CL00, CL01, CL02, CL25, CL04, CL45 0.25-0.41 Manual/Auto w/wo stop Class 10 1 15 RT1C CL00, CL01, CL02, CL25, CL04, CL45 0.4-0.65 Manual/Auto w/wo stop Class 10 3 15 RT1D CL00, CL01, CL02, CL25, CL04, CL45 0.65-1.1 Manual/Auto w/wo stop Class 10 6 15 RT1F CL00, CL01, CL02, CL25, CL04, CL45 1-1.5 Manual/Auto w/wo stop Class 10 6 15 RT1G CL00, CL01, CL02, CL25, CL04, CL45 1.3-1.9 Manual/Auto w/wo stop Class 10 6 15 RT1H CL00, CL01, CL02, CL25, CL04, CL45 1.8-2.7 Manual/Auto w/wo stop Class 10 10 15 RT1J CL00, CL01, CL02, CL25, CL04, CL45 2.5-4.1 Manual/Auto w/wo stop Class 10 15 15 RT1K CL00, CL01, CL02, CL25, CL04, CL45 4-6.3 Manual/Auto w/wo stop Class 10 20 15 RT1L CL00, CL01, CL02, CL25, CL04, CL45 5.5-8.5 Manual/Auto w/wo stop Class 10 25 15 RT1M CL00, CL01, CL02, CL25, CL04, CL45 8.0-12.0 Manual/Auto w/wo stop Class 10 40 30 RT1N CL01, CL02, CL25, CL04, CL45 10.0-16.0 Manual/Auto w/wo stop Class 10 50 35 RT1P CL02, CL25, CL04, CL45 14.5-18 Manual/Auto w/wo stop Class 10 60 40 RT1S CL25, CL04, CL45 17.5-22 Manual/Auto w/wo stop Class 10 70 50 RT1T CL04, CL45 21-26 Manual/Auto w/wo stop Class 10 80 60 RT1U CL04, CL45 25-32 Manual/Auto w/wo stop Class 10 100 80 RT1V CL45 30-40 Manual/Auto w/wo stop Class 10 100 80 RT1W CL00, CL01, CL02, CL25, CL04, CL45 0.4-0.65 Manual/Auto w/wo stop Class 20 3 15 RT12D CL00, CL01, CL02, CL25, CL04, CL45 0.65-1.1 Manual/Auto w/wo stop Class 20 6 15 RT12F CL00, CL01, CL02, CL25, CL04, CL45 1-1.5 Manual/Auto w/wo stop Class 20 6 15 RT12G CL00, CL01, CL02, CL25, CL04, CL45 1.3-1.9 Manual/Auto w/wo stop Class 20 6 15 RT12H CL00, CL01, CL02, CL25, CL04, CL45 2.5-4.1 Manual/Auto w/wo stop Class 20 15 15 RT12K CL00, CL01, CL02, CL25, CL04, CL45 4-6.3 Manual/Auto w/wo stop Class 20 20 15 RT12L CL00, CL01, CL02, CL25, CL04, CL45 5.5-8.5 Manual/Auto w/wo stop Class 20 25 15 RT12M CL00, CL01, CL02, CL25, CL04, CL45 8.0-12.0 Manual/Auto w/wo stop Class 20 40 30 RT12N CL01, CL02, CL25, CL04, CL45 10.0-16.0 Manual/Auto w/wo stop Class 20 50 35 RT12P CL02, CL25, CL04, CL45 14.5-18 Manual/Auto w/wo stop Class 20 60 40 RT12S CL25, CL04, CL45 17.5-22 Manual/Auto w/wo stop Class 20 70 50 RT12T CL04, CL45 21-26 Manual/Auto w/wo stop Class 20 80 60 RT12U CL04, CL45 25-32 Manual/Auto w/wo stop Class 20 100 80 RT12V CL45 30-40 Manual/Auto w/wo stop Class 20 100 80 RT12W
1
Do not exceed contactor current rating when selecting and adjusting overload relays. For panel mount use base adapter RTXP.
1
1
Amps (min-max) Reset Type Trip Class Rating Amps Rating Amps Product Number
Amps (min-max) Reset Type Trip Class Rating Amps Rating Amps Product Number
Section 5
5-54
Product Number Selection Instructions: See page 5-37
Control Catalog
IEC Power Devices
IEC Contactors Thermal Overload Relays
C-2000
RT2 - Direct Mount Manual
Overload Relay for use Current Range Maximum Fuse Maximum Circuit Breaker with Contactors
CL06, CL07, CL08, CL09, CL10 11.5-15 Manual Class 10 35 25 RTN2A CL06, CL07, CL08, CL09, CL10 14.5-19 Manual Class 10 50 45 RTN2B CL06, CL07, CL08, CL09, CL10 18.5-25 Manual Class 10 70 60 RTN2C CL06, CL07, CL08, CL09, CL10 24-32 Manual Class 10 90 80 RTN2D CL06, CL07, CL08, CL09, CL10 30-43 Manual Class 10 100 100 RTN2E CL06, CL07, CL08, CL09, CL10 42-55 Manual Class 10 150 125 RTN2G CL07, CL08, CL09, CL10 54-65 Manual Class 10 175 150 RTN2H CL08, CL09, CL10 64-82 Manual Class 10 225 200 RTN2J CL10 78-97 Manual Class 10 225 225 RTN2L CL10 90-110 Manual Class 10 225 250 RTN2M
RT2 - Direct Mount Manual/Auto
Overload Relay for use Current Range Maximum Fuse Maximum Circuit Breaker with Contactors
CL06, CL07, CL08, CL09, CL10 11.5-15 Manual/Auto w/wo stop Class 10 35 25 RT2A CL06, CL07, CL08, CL09, CL10 14.5-19 Manual/Auto w/wo stop Class 10 50 45 RT2B CL06, CL07, CL08, CL09, CL10 18.5-25 Manual/Auto w/wo stop Class 10 70 60 RT2C CL06, CL07, CL08, CL09, CL10 24-32 Manual/Auto w/wo stop Class 10 90 80 RT2D CL06, CL07, CL08, CL09, CL10 30-43 Manual/Auto w/wo stop Class 10 100 100 RT2E CL06, CL07, CL08, CL09, CL10 42-55 Manual/Auto w/wo stop Class 10 150 125 RT2G CL07, CL08, CL09, CL10 54-65 Manual/Auto w/wo stop Class 10 175 150 RT2H CL08, CL09, CL10 64-82 Manual/Auto w/wo stop Class 10 225 200 RT2J CL10 78-97 Manual/Auto w/wo stop Class 10 225 225 RT2L CL10 90-110 Manual/Auto w/wo stop Class 10 225 250 RT2M CL06, CL07, CL08, CL09, CL10 24-32 Manual/Auto w/wo stop Class 20 90 80 RT22D CL06, CL07, CL08, CL09, CL10 30-43 Manual/Auto w/wo stop Class 20 100 100 RT22E CL06, CL07, CL08, CL09, CL10 42-55 Manual/Auto w/wo stop Class 20 150 125 RT22G CL07, CL08, CL09, CL10 54-65 Manual/Auto w/wo stop Class 20 175 150 RT22H CL08, CL09, CL10 64-82 Manual/Auto w/wo stop Class 20 225 200 RT22J CL10 78-97 Manual/Auto w/wo stop Class 20 225 225 RT22L CL10 90-110 Manual/Auto w/wo stop Class 20 225 250 RT22M
1
Do not exceed contactor current rating when selecting and adjusting overload relays. For panel mount use base adapter RT2XP.
1
1
Amps (min-max) Reset Type Trip Class Rating Amps Rating Amps Product Number
Amps (min-max) Reset Type Trip Class Rating Amps Rating Amps Product Number
Section 5
Control Catalog
5-55
IEC Power Devices
IEC Contactors Thermal Overload Relays
C-2000
RT3 - Direct or Panel Mount
Overload Relay for use Current Range Maximum Fuse Maximum Circuit Breaker with Contactors
CK75, CK08 55-80 Manual Class 10 225 200 RTN3B CK75, CK08 63-90 Manual Class 10 250 225 RTN3C CK75, CK08 90-120 Manual Class 10 350 300 RTN3D CK75, CK08 110-140 Manual Class 10 400 350 RTN3E CK08 140-190 Manual Class 10 450 500 RTN3F CK75, CK08 55-80 Manual/Auto Class 10 225 200 RT3B CK75, CK08 63-90 Manual/Auto Class 10 250 225 RT3C CK75, CK08 90-120 Manual/Auto Class 10 350 300 RT3D CK75, CK08 110-140 Manual/Auto Class 10 400 350 RT3E CK08 140-190 Manual/Auto Class 10 450 500 RT3F CK75, CK08 63-90 Manual/Auto Class 20 250 225 RT32C CK75, CK08 90-120 Manual/Auto Class 20 350 300 RT32D CK75, CK08 110-140 Manual/Auto Class 20 400 350 RT32E CK08 140-190 Manual/Auto Class 20 450 500 RT32F
1
Do not exceed contactor current rating when selecting and adjusting overload relays.
RT4 - Separate Mount
Overload Relay for use Current Range Terminal Maximum Fuse Maximum Circuit Breaker with Contactors
CK09, CK95 120-190 Manual Class 10 Bus bar CK09, CK95 175-280 Manual Class 10 Bus bar CK95 200-310 Manual Class 10 Bus bar CK09, CK95 120-190 Manual/Auto Class 10 Bus bar CK09, CK95 175-280 Manual/Auto Class 10 Bus bar CK95 200-310 Manual/Auto Class 10 Bus bar CK09, CK95 45-70 Manual/Auto Class 30 Clamp 225 175 RT4LK CK09, CK95 60-90 Manual/Auto Class 30 Clamp 300 225 RT4LL CK09, CK95 80-125 Manual/Auto Class 30 Clamp 400 350 RT4LM CK09, CK95 120-190 Manual/Auto Class 30 Bus bar CK09, CK95 175-280 Manual/Auto Class 30 Bus bar CK95 200-310 Manual/Auto Class 30 Bus bar
1
Do not exceed contactor current rating when selecting and adjusting overload relays.
2
Can be mounted to contactor with Overload Jumpers (listed on page 5-47) and Base Plate (CKXB01) (listed on page 5-47).
1
1
Amps (min-max) Reset Type Trip Class Rating Amps Rating Amps Product Number
Amps (min-max) Reset Type Trip Class Type Rating Amps Rating Amps Product Number
2 2 2 2 2 2
2 2 2
600 500 RTN4N 800 700 RTN4P 900 800 RTN4R 600 500 RT4N 800 700 RT4P 900 800 RT4R
600 500 RT4LN 800 700 RT4LP 900 800 RT4LR
Section 5
RT5 - Separate Mount
Overload Relay for use Current Range Maximum Fuse Maximum Circuit Breaker with Contactors
CK10, CK11, CK12 120-190 Manual Class 10 800 500 RTN5A CK10, CK11, CK12 175-280 Manual Class 10 1200 700 RTN5B CK10, CK11, CK12 250-400 Manual Class 10 1200 1000 RTN5C CK10, CK11, CK12 315-500 Manual Class 10 1200 1200 RTN5D CK11, CK12 4 30-650 Manual Class 10 1200 1200 RTN5E CK10, CK11, CK12 120-190 Manual/Auto Class 10 800 500 RT5A CK10, CK11, CK12 175-280 Manual/Auto Class 10 1200 700 RT5B CK10, CK11, CK12 250-400 Manual/Auto Class 10 1200 1000 RT5C CK10, CK11, CK12 315-500 Manual/Auto Class 10 1200 1200 RT5D CK11, CK12 4 30-650 Manual/Auto Class 10 1200 1200 RT5E CK10, CK11, CK12 120-190 Manual/Auto Class 30 800 500 RT5LA CK10, CK11, CK12 175-280 Manual/Auto Class 30 1200 700 RT5LB CK10, CK11, CK12 250-400 Manual/Auto Class 30 1200 1000 RT5LC CK10, CK11, CK12 315-500 Manual/Auto Class 30 1200 1200 RT5LD CK11, CK12 430-650 Manual/Auto Class 30 1200 1200 RT5LE
1
Do not exceed contactor current rating when selecting and adjusting overload relays.
2
Can be mounted to contactor with Overload Jumpers (listed on page 5-47).
3
Maximum fuse rating of 1000 amps/maximum circuit breaker rating of 600 amps when used with CK10CE or CK11CE contactors. Use CK10BE or CK11BE with higher rated
1
2
Amps (min-max) Reset Type Trip Class Rating Amps Rating Amps Product Number
3 3 3 3
3 3 3 3
protective devices indicated. CK12BE suitable for all ratings listed.
Product Number Selection Instructions: See page 5-37
5-56
Control Catalog
IEC Power Devices
IEC Contactors Thermal Overload Relays Accessories
C-2000
Remote Electrical Reset
Remote electrical resets are used in applications where the motor starter is inaccessible or in automated control systems where it is required to reset the overload relay remotely after the fault has been cleared. Electrical reset coils are rated for intermittent duty and for use with momentary contacts. Minimum time .2 sec. on for reliable operation. Maximum time 1 sec. on/30 sec. off, 5 sec. on/90 sec. off, 10 sec. on/180 sec. off. Power consumption is 100VA/100 watts.
RTXRR_ _Remote Electrical Reset
For Use With Voltage 50/60 Hz AC or DC Product Number
All RT overload relays 12 RTXRRB All RT overload relays 24 RTXRRD All RT overload relays 48 RTXRRG All RT overload relays 110-120 RTXRRJ All RT overload relays 220-240 RTXRRN All RT overload relays 380-415 RTXRRU All RT overload relays 440-480 RTXRRX
Overload Base Adapter
Permits mounting of RT1 or RT2 overload on panel or DIN rail.
Section 5
For Use With Product Number
RT1 RTXP RT2 RT2XP
Transparent Cover for Range Adjustment Dial
Deters tampering with dial.
For Use With Product Number
All Overload Relays RTX3 1
Product number represents a quantity of 10 pieces.
1
Locking Plug for Manual/Auto Selector
Prevents changing reset mode after installation.
For Use With Product Number
All Overload Relays RTXL 1
Product number represents a quantity of 10 pieces.
1
Flexible Cable Reset Button
Allows manual reset of overload when overload is mounted in a special or inaccessible position. Fits standard 22.5 mm panel hole.
For Use With Cable Length Product Number
All Overloads .5 meter RTXR All Overloads 1.0 meter RTXRL
RT_ _ _Overload Base Adapter
RTX3 Transparent Cover
RTXL Locking Plug
RTXR Flexible Cable Reset Button
Control Catalog
5-57
IEC Power Devices
IEC Contactors Thermal Overload Relays Technical Characteristics
C-2000
Section 5
Class 10 RT1
Class 10 RT2
Class 20 RT12
Class 20 RT22
5-58
Class 10 RT3
Product Number Selection Instructions: See page 5-37
Control Catalog
Class 20 RT32
IEC Power Devices
IEC Contactors Thermal Overload Relays Technical Characteristics
C-2000
Section 5
RT4 RT4L
RT5 RT5L
Control Catalog
5-59