GE - General Electric EP100 ULH Data Sheet

ElfaPlus with UL approvals
EP100 ULH (Branch circuit protection)
UL Listed 489 10kA CSA c22.2 No.5-02 EN/IEC 60947-2 15kA
120/240Vac
UL Listed 489 performances
UL FILE E256870 Ampere rating In (A) 0.5-63 0.5-63A Reference temperature °F/°C 77/25 Terminal capacity exible/rigid cable Max. Torque N.m/lbs.in 4.5/39.8
Rated voltage (V)
Poles V AC V DC
1 120 60
2,3 240 125
14-2 AWG
Line protection
Intro
A
B
C
D
X
Application
Standards
UL489, CSA c22.2 No.5-02 IEC 60947-2, IEC 60898-1
Approvals / Marking
(1)
Add-on devices
AC Interrupting ratings
Poles V kA
1 120 10
2,3 240 10
DC Interrupting ratings
Poles V DC kA
1 60 10 2 125 10
IEC performances
Thermal setting In 0.5-63A Rated voltage AC (V) 240/415V Weight/pole oz.(g) 4.6(130) Terminal capacity exible/rigid cable (mm
Short-circuit capacity according to IEC 60947-2
Poles V AC Icu (kA)
1 127 30
240 15 415 4
2 127 40
240 30 415 15
3 240 30
415 15 440 10
DC short-circuit capacity according to IEC 60497-2
Poles V Icu (kA)
1 60 25 2 125 30
2
) 0.75/1 - 25/35
A.14
Auxiliary contacts
Motor
operator
(1) Ask for availability. Under Type approval.
General performance
Minimum operating voltage 12 Tripping characteristics B-C-D Rated frequency (Hz) 50/60 Mechanical/electrical endurance 20000/10000 Humidity acc. to IEC 60068-2-28/2-30 95%RH at 131°F/55°C Poles 1, 2, 3
Instantaneous tripping ranges acc. to IEC 60898-1
B characteristic 3 to 5 times Ampere rating C characteristic 5 to 10 times Ampere rating D characteristic 10 to 20 times Ampere rating