GE - General Electric Dry Type Transformers Totally Enclosed Nonventilated Catalog Page

Dry Type Transformers
Totally Enclosed, Nonventilated
TENV
15-75kVA, Three-Phase, TP-1
Totally enclosed nonventilated (TENV) transformers are an excellent choice for applications where dry-type transformer benefits are desired but the standard enclosure openings are unacceptable because of adverse atmospheric conditions. TENV transformers are recommended where dust , dirt or lint may be present or where transformers are subject to sprays or controlled wash-down conditions. They are UL Listed through 75kVA for indoor or protected outdoor applications.
Advantages
Dry-type transformer is housed in an enclosed NEMA 3R
non-ventilated compartment
—Convenient wiring compartment is located beneath the
transformer and has removable front and rear covers
—Copper bus bars are located at the front of the wiring
compartment and are clearly labeled
—All electrical connections between the transformer and
bus bars are factory wired —Quiet performance – meets NEMA ST-20 —No-weld coil termination design – an industry first —Comprehensive factory testing assures quality
Section 10
TENV Transformer
Features
—Quiet design - unique core and coil design makes GE TENV
transformers among the quietest available —Core and coil assembly mounted on rubber isolation pads to
reduce noise —Bolted coil terminations are more reliable than welded
terminations, and they eliminate weld failures and problems
associated with welding and weld splatter —100% factory tested for shorts and coil integrity, current and
loss, voltage, impedance and noise —Qualified to the seismic requirements of IEEE-693-1997 and
IBC-2003 —Copper ground strap —Copper or aluminum windings available —Available in 150°C, 115°C, and 80°C rise models —Indoor or outdoor use
Applications
—Textile —Automotive —Foundry —Paper mills —Wash-down areas
TENV Transformer ( front panel removed)
10-36
BuyLog™Catalog
Rev. 11/13
Data subject to change without notice
Dry Type Transformers
Section 10
Totally Enclosed, Nonventilated
TENV
Three-Phase TP-1
Aluminum 150°C Rise
Input Output Net Voltage Voltage kVA Taps Weight (Lbs.) Frame Size Product Number
480 208Y/120 15 (+2,-4 2.5%) 370 XV372 9T85B3871 480 208Y/120 30 (+2,-4 2.5%) 450 XV373 9T85B3872 480 208Y/120 45 (+2,-4 2.5%) 670 XV374 9T85B3873 480 208Y/120 75 (+2,-4 2.5%) 815 XV375 9T85B3874
Aluminum 115°C Rise
Input Output Net Voltage Voltage kVA Taps Weight (Lbs.) Frame Size Product Number
480 208Y/120 15 (+2,-4 2.5%) 370 XV372 9T85B3871G15 480 208Y/120 30 (+2,-4 2.5%) 450 XV373 9T85B3872G15 480 208Y/120 45 (+2,-4 2.5%) 670 XV374 9T85B3873G15
Aluminum 80°C Rise
Input Output Net Voltage Voltage kVA Taps Weight (Lbs.) Frame Size Product Number
480 208Y/120 30 (+2,-4 2.5%) 670 XV374 9T85B3872G80 480 208Y/120 45 (+2,-4 2.5%) 670 XV374 9T85B3873G80
Copper 150°C Rise
Input Output Net Voltage Voltage kVA Taps Weight (Lbs.) Frame Size Product Number
480 208Y/120 15 (+2,-4 2.5%) 410 XV372 9T85C9871 480 208Y/120 30 (+2,-4 2.5%) 525 XV373 9T85C9872 480 208Y/120 45 (+2,-4 2.5%) 760 XV374 9T85C9873 480 208Y/120 75 (+2,-4 2.5%) 1000 XV375 9T85C9874
Copper 115°C Rise
Input Output Net Voltage Voltage kVA Taps Weight (Lbs.) Frame Size Product Number
480 208Y/120 15 (+2,-4 2.5%) 410 XV372 9T85C9871G15 480 208Y/120 30 (+2,-4 2.5%) 525 XV373 9T85C9872G15 480 208Y/120 45 (+2,-4 2.5%) 760 XV374 9T85C9873G15 480 208Y/120 75 (+2,-4 2.5%) 1000 XV375 9T85C9874G15
Copper 80°C Rise
Input Output Net Voltage Voltage kVA Taps Weight (Lbs.) Frame Size Product Number
480 208Y/120 15 (+2,-4 2.5%) 410 XV372 9T85C9871G80 480 208Y/120 30 (+2,-4 2.5%) 760 XV374 9T85C9872G80 480 208Y/120 45 (+2,-4 2.5%) 760 XV374 9T85C9873G80
Rev. 11/13
Data subject to change without notice
BuyLog™Catalog
10-37