GE - General Electric Double-Throw Switches Catalog Page

Safety Switches
Double-Throw Switches
Spec-Setter™Safety Switches Type TC, Type TDT 240, 480, 600 Volts AC 250 Volts DC
Type TC Non-Fused (NEMA 1) and Outdoor (NEMA 3R) Double-Throw Switches
—Designed for application where safety, high performance, and
continuity of service are required.
—UL Listed. Products in this section have been tested by UL and
shown to meet the construction and performance requirements of UL Standard Number 98, Enclosed and Dead Front Switches. Suitable for use in accordance with Article 702 of the National Electrical Code.
—Meet Federal Specification W-S-865C for enclosed switches;
30-200 amps, Type HD; 400-600 amps, Type LD.
—Meet or exceed NEMA Enclosed Switch Standard KS1 except
paragraph 1-4.24 (withstand and short circuit) for Type HD
30-200 amps, Type GD 400-600 amps. —Seismic Certified (non-fused). —60°C and 75°C conductor ratings. —Quick-make, quick-break mechanisms 30-200 amps; quick
break mechanisms 400-600 amps. —UL Service Entrance rated (NEMA 1 and NEMA 3R).
TC35322, Type TC Indoor Double-throw Switch
TC35321, Type TC Outdoor Double-throw Switch
Type TC Outdoor Emergency Power Transfer Switches
—Designed for residential or light commercial applications where
duty is not severe. —UL Listed. Products in this section have been tested by UL and
shown to meet the construction and performance requirements
of UL Standard Number 98, Enclosed and Dead Front Switches. —Meet or exceed NEMA Enclosed Switch Standard KS1 for
Type GD. —Suitable for use as service entrance equipment when installed in
accordance with National Electrical Code. —60°C and 75°C conductor ratings. —Not quick-make, quick-break
Type TDT Fusible Double-Throw Safety Switches
—TDT safety switches are suitable for use as service entrance
equipment when either neutral kit DT200NK or ground lug kit
DS200GK is installed. UL listed (no CSA or cUL).
TC10323R, Type TC Outdoor
Emergency Power Transfer Switch
Three-pole, 240 Volts AC, 250 Volts DC, No Fuse
Three-pole, 600 Volts AC, 250 Volts DC, No Fuse
Three-wire SN, 120/240 Volts AC, No Fuse
Rev. 11/13
Data subject to change without notice
Four-wire SN, 240 Volts AC, No Fuse
BuyLog™Catalog
4-17
Safety Switches Section 4
Double-Throw Switches
Spec-Setter™Safety Switches Type TC, Type TDT 240, 480, 600 Volts AC 250 Volts DC
Three-pole, 240 Volts AC, 250 Volts DC, No Fuse
Ampere Enclosure HP, 240 Vac, HP, 480 Vac, HP, 600 Vac, Lug Wire Size, Product Rating Type NEC Std, 3-ph NEC Std, 3-ph NEC Std, 3-ph AWG/kcmil, Cu Only Number
30A NEMA Type 1 2––14-8 TC35321 60A NEMA Type 1 3––14-4 TC35322 100A NEMA Type 1 7 1/2 ––14-1/0 TC35323 200A NEMA Type 1 15 ––6-250 TC35324 400A NEMA Type 1 30 ––(2)1/0-250 or #2-600 TC35325 600A NEMA Type 1 50 ––(2)3/0-350 or #2-600 TC35326
Three-pole, 240 Volts AC, 250 Volts DC, No Fuse
Ampere Enclosure HP, 240 Vac, HP, 480 Vac, HP, 600 Vac, Lug Wire Size, Product Rating Type NEC Std, 3-ph NEC Std, 3-ph NEC Std, 3-ph AWG/kcmil, Cu Only Number
30A NEMA Type 3R 2--14-8 TC35321R 60A NEMA Type 3R 3--14-4 TC35322R 100A NEMA Type 3R 7.5 --14-1/0 TC35323R 200A NEMA Type 3R 15 --6-250 TC35324R 400A NEMA Type 3R 30 --(2) 1/0-250 or #2-600 TC35325R
Three-pole, 600 Volts AC, 250 Volts DC, No Fuse
Ampere Enclosure HP, 240 Vac, HP, 480 Vac, HP, 600 Vac, Lug Wire Size, Product Rating Type NEC Std, 3-ph NEC Std, 3-ph NEC Std, 3-ph AWG/kcmil, Cu Only Number
30A NEMA Type 1 10 10 10 14-4 Use 60A 60A NEMA Type 1 10 10 10 14-4 TC35362 100A NEMA Type 1 15 15 15 14-1/0 TC35363 200A NEMA Type 1 30 30 30 6-250 TC35364 400A NEMA Type 1 –––(2)1/0-250 or #2-600 TC35365 600A NEMA Type 1 –––(2)3/0-350 or #2-600 TC35366
Three-pole, 600 Volts AC, 250 Volts DC, No Fuse
Ampere Enclosure HP, 240 Vac, HP, 480 Vac, HP, 600 Vac, Lug Wire Size, Product Rating Type NEC Std, 3-ph NEC Std, 3-ph NEC Std, 3-ph AWG/kcmil, Cu Only Number
30A NEMA Type 3R 10 10 10 14.4 Use 60A 60A NEMA Type 3R 10 10 10 14-4 TC35362R 100A NEMA Type 3R 15 15 15 14-1/0 TC35363R 200A NEMA Type 3R 30 30 30 6-250 TC35364R
240 Volts AC, Fusible
Ampere Enclosure Time Delay, Time Delay, Time Delay, Time Delay, Time Delay, Time Delay, HP, DC Product Rating Type 1-ph 1-ph 1-ph 3-ph 3-ph 3-ph @ 250V Number
30A NEMA Type 1 3––7 1/2 ––5TDT3321 60A NEMA Type 1 10 ––15 ––10 TDT3322 100A NEMA Type 1 15 ––30 ––20 TDT3323 200A NEMA Type 1 15 ––60 ––40 TDT3324 400A NEMA Type 1 –––125 ––50 TDT3325 600A NEMA Type 1 –––50 ––50 TDT3326 30A NEMA Type 3R 3 7 1/2 10 7 1/2 15 20 5 TDT3321R 60A NEMA Type 3R 10 20 25 15 30 50 10 TDT3322R 100A NEMA Type 3R 15 30 40 30 60 75 20 TDT3323R 200A NEMA Type 3R 15 50 50 60 125 150 40 TDT3324R
HP, 240 Vac, HP, 480 Vac, HP, 600 Vac, HP, 240 Vac, HP, 480 Vac, HP, 600 Vac,
600 Volts AC, Fusible
Ampere Enclosure Time Delay, Time Delay, Time Delay, Time Delay, Time Delay, Time Delay, HP, DC Product Rating Type 1-ph 1-ph 1-ph 3-ph 3-ph 3-ph @ 250V Number
30A NEMA Type 1 3 7 1/2 10 7 1/2 15 20 TDT3361 60A NEMA Type 1 10 20 25 15 30 50 TDT3362 100A NEMA Type 1 15 30 40 30 60 75 TDT3363 200A NEMA Type 1 15 50 50 60 125 150 40 TDT3364 400A NEMA Type 1 –––125 250 350 50 TDT3365 100A NEMA Type 3R 15 30 40 30 60 75 20 TDT3363R 200A NEMA Type 3R 15 50 50 60 125 150 40 TDT3364R
1
Not UL Listed.
2
Not suitable for use as service equipment per NEC Article 702.
3
200 Amp switches move load base for Class J fuses.
4
600 Amp switch available with Class T fuse provision only.
5
No provision for auxiliary contact kit.
HP, 240 Vac, HP, 480 Vac, HP, 600 Vac, HP, 240 Vac, HP, 480 Vac, HP, 600 Vac,
2
1,2,5 1,2
3
4
3
3
3
4-18
BuyLog™Catalog
Rev. 11/13
Data subject to change without notice
Loading...