GE - General Electric CR306, CR386 Catalog Page

NEMA Full Voltage Power Devices
NEMA Rated Full Voltage Starters - Magnetic
CR306, CR386 Magnetic Starters
Nonreversing, Non-combination NEMA Sizes 00-9 with Thermal Overload Relay 600 Volts Maximum 50/60 Hertz
Application
GE’s magnetic motor starters listed here may be used for starting full-voltage, nonreversing, single-speed ac motors up to 1600 horsepower, 600 Volts maximum, providing protection to the motor against running or stalled overloads.
Their compact size and ease of wiring make them especially suitable for motor control centers, custom-type control panels, and switchgear equipment. Refer to page 1-7 for features of basic starter.
Product Number Selection Instructions
1. Specify starter by complete Product Number.
Example: CR306C103 is a Size 1 starter with 230-240-Volt, 60-Hertz coil and in Type 1 general-purpose enclosure
2. The final letter of the Product Number denotes extra auxiliary contacts (sometimes referred to as auxiliary interlocks). Order the desired extra auxiliary contacts by replacing the final letter with one from first column of auxiliary interlock table (see page 1-134). Example: CR306C103AAB is Size 1 starter with one extra nor­mally open, auxiliary contact
3. Starter forms are available with coils of other ratings than those shown on pages 1-9 to 1-10. Refer to coil suffix table, page 1-8 for information. To order forms with other coil ratings, insert suffix from coil table in place of fifth and sixth numbers of listed starter Product Number shown on pages 1-9 to 1-10. (Contact your nearest GE Representative for other available starter coils not shown in table.) Example: A CR306C102 NEMA Size 1, three-pole starter in Type 1 enclosure with 24-Volt, 60-Hertz coil becomes a CR306C124 Product Number.
4. For continuous rated motors with a service factor of 1.15 to
1.25 select the heater with maximum motor Amperes equal to or immediately greater than the actual full-load current taken directly from the nameplate of motor. Order heaters by com­plete Product Number from appropriate heater tables on pages 1-153 to 1-159
5. Order special modifications or forms not listed by complete description using a listed Product Number as reference. Example: Similar to CR306C104 except with 480/120-Volt control transformer and red indicating light in cover. Total
6. Two-phase, four-wire forms are available. Contact nearest GE Representative for pricing and ordering information.
7. Standard Coil Ratings
Standard Voltages (60 Hertz): 24, 115-120, 200-208, 230-240, 265-277, 460-480 and 575-600 Standard Voltages (50 Hertz): 110, 220, 380, 440 and 550 For price adders on special voltage and/or frequency coils, refer to page 1-126.
8. 50-Hertz Starters
Pricing of starters for use on 50 Hertz at standard voltages is the same as shown in table for 60 Hertz. Refer to page 1-4 for three-phase horsepower ratings at 380 Volts, 50 Hertz.
Typical Schematic Di ag ra m for CR306 Start er (NEMA Si ze s 00-6)
9. Product Notes
Reference Publications
Instructions NEMA Size Publication Number
00, 0, 1 GEH-5190 2 GEH-4774 3 GEH-4806 4 GEH-4807 5 GEH-4839 6 GEH-5198 7-9 GEH-5108
CR306, CR386 Magnetic Starters – Contents
Basic Features (300-Line) and Technical Features
Non-combination, NEMA Sizes 00-9 with Thermal Overload
Non-combination, NEMA Sizes 00-9
Outlines and Dimensions (CR306, CR386)....................................1-13
Typical CR306 Si ze 4 ma gn et ic motor st ar ter
Motor full-load current should not exceed continuous ampere rating of starter.
(CR306, CR386)..........................................................................................1-7
Relays — Application Information and Selection Instructions
(CR306, CR386)..........................................................................................1-8
with Thermal Overload Relays (CR306, CR386).........................1-9
1-8
Other Coil Voltages: See page 1-6 Factory Installed Modifications: See pages 1-124
Field Installed Modifications: See pages 1-132 to 1-138 Extra Auxiliary Contacts: See pages 1-132 to 1-134 Heater Selection Tables: See pages 1-153 to 1-159
Rev. 4/16
Prices and data subject to change without notice
NEMA Full Voltage Power Devices
Section 1
NEMA Rated Full Voltage Starters - Magnetic
CR306, CR386 Magnetic Starters
Nonreversing, Non-combination, Open, NEMA Type 1, 3R, 12, 4/4X NEMA Sizes 00-9 with Thermal Overload Relay 600 Volts Maximum 50/60 Hertz
Three-Phase
List Price includes a holding interlock, pressure terminals for the line and load connections, plus a 3-leg block type overload relay (manual reset). All enclosures include external reset. One NO isolated contact on the overload relay is available as an option at $24.00, GO-10G. To order add suffix LAA to Product Numbers (Size 00-5) listed in table. Three heaters should be ordered as separate items. See pages 1-153 to 1-159 for selection. List price $9.00 each, GO-10H.
CR306, Three-Phase Magnetic Starters
Open Type NEMA Type 1 NEMA Type 3R NEMA Type 12 NEMA Type 4/4X
NEMA Continuous Number Number Number Price Number Number Size Ampere Rating
00 9 Separate Control—115-120 V A002 A102 Use NEMA Size 0 Use NEMA Size 0 Use NEMA Size 0 00 9 200-208 1 1/2 A023 A123 Use NEMA Size 0 Use NEMA Size 0 Use NEMA Size 0 00 9 230-240 1 1/2 A003 A103 Use NEMA Size 0 Use NEMA Size 0 Use NEMA Size 0 00 9 460-480 2 A004 A104 Use NEMA Size 0 Use NEMA Size 0 Use NEMA Size 0 00 9 575-600 2 A005 A105 Use NEMA Size 0 Use NEMA Size 0 Use NEMA Size 0 0 18 Separate Control—115-120 V B002 B102 B602 B202 B402 0 18 200-208 3 B023 B123 B623 B223 B423 0 18 230-240 3 B003 B103 B603 B203 B403 0 18 460-480 5 B004 B104 B604 B204 B404 0 18 575-600 5 B005 B105 B605 B205 B405 1 27 Separate Control—115-120 V C002 C102 C602 C202 C402 1 27 200-208 7 1/2 C023 C123 C623 C223 C423 1 27 230-240 7 1/2 C003 C103 1 27 460-480 10 C004 C104 C604 C204 C404 1 27 575-600 10 C005 C105 C605 C205 C405 2 45 Separate Control—115-120 V D002 D102 D602 D202 D402 2 45 200-208 10 D023 D123 D623 D223 D423 2 45 230-240 15 D003 D103 D603 D203 D403 2 45 460-480 25 D004 D104 D604 D204 D404 2 45 575-600 25 D005 D105 D605 D205 D405 3 90 Separate Control—115-120 V E002 E102 E602 E202 E402 3 90 200-208 25 E023 E123 E623 E223 E423 3 90 230-240 30 E003 E103 E603 E203 E403 3 90 460-480 50 E004 E104 E604 E204 E404 3 90 575-600 50 E005 E105 E605 E205 E405 4 135 Separate Control—115-120 V F002 F102 F602 F202 F402 4 135 200-208 40 F023 F123 F623 F223 F423 4 135 230-240 50 F003 F103 F603 F203 F403 4 135 460-480 100 F004 F104 F604 F204 F404 4 135 575-600 100 F005 F105 F605 F205 F405 5 270 Separate Control—115-120 V G002 G102 G602 G202 G402 5 270 200-208 75 G023 G123 G623 G223 G423 5 270 230-240 100 G003 G103 G603 G203 G403 5 270 460-480 200 G004 G104 G604 G204 G404 5 270 575-600 200 G005 G105 G605 G205 G405 6 540 Separate Control—115-120 V HH002 HH102 HH602 HH202 HH402 6 540 200-208 150 HH023 HH123 HH623 HH223 HH423 6 540 230-240 200 HH003 HH103 HH603 HH203 HH403 6 540 460-480 400 HH004 HH104 HH604 HH204 HH404 6 540 575-600 400 HH005 HH105 HH605 HH205 HH405
1
Voltage Horsepower CR306 CR306 CR306 GO-10G CR306 CR306
Product Product Product List Product Product
2
C603 C203 C403
CR386 Three-Phase Magnetic Starters
Continuous Control Product NEMA Ampere Circuit Number Size Rating
7 810 Separate Control J002AA1A
7 810 220-240 300 230 J003AA1A 7 810 440-480 600 460 J004AA1A 7 810 550-600 600 575 J005AA1A 8 1215 Separate Control K002AA1A
8 1215 220-240 450 230 K003AA1A 8 1215 440-480 900 460 K004AA1A 8 1215 550-600 900 575 K005AA1A 9 2250 Separate Control L002AA1A
9 2250 220-240 800 230 L003AA1A 9 2250 440-480 1600 460 L004AA1A 9 2250 550-600 1600 575 L005AA1A
1
Voltage Horsepower Voltage CR386
—115-120 V
—115-120 V
—115-120 V
Enclosure Descriptions: See Section 12
Rev. 4/16
Prices and data subject to change without notice
Open Type
1
Motor full load current should not exceed continuous ampere rating of the starter.
2
Units are individually boxed and “Poly-Packed” six per carton as standard.
1-9
Loading...
+ 1 hidden pages