NEMA Full Voltage Power Devices
50 Hertz
115 V 200-208 V 230-240 V 277 V 460-600 V 380 V
M-0
———
——
——
1
2
22
32
52
55
33
M-1
—
M-1P 3
—
M- 0
——
M- 1
—
7-1/2 7-1/2 10 10
—
Phase
Single
Three
Maximum Horsepower Ratings
Coil Motor Voltage and Frequency
60 Hertz
NEMA Size
NEMA Rated Full Voltage Starters - Manual
CR1062
Single-Phase and Polyphase
10 HP Maximum
600 Volts
25 to 60 Hertz
Application
Designed for controlling small ac motors. Standard CR1062R
and S starter forms provide overload protection but cannot be
used where undervoltage protection is required or for remote or
automatic
Features
—Front-connected; clamp-type terminals for easy wiring.
—Trip-free overload mechanism; can’t be held closed.
—Knockout in enclosure cover permits installation
of indicating light kit .
Schematic Diagrams
operation.
Section 1
Typical 3-Phase Typical Single-Phase Typical Single-Phase Typical Connections
Connections CR 10 62 R & S Connections CR 10 62 R & S Connections CR 10 62 T for DC Starte rs
Horsepower Ratings
Reference Publications
Instructions GEH-4737
1-168
Product Number Selection Instructions: See page 1-168
Control Catalog
Rev. 8/15
Prices and data subject to
change without notice
NEMA Full Voltage Power Devices
Type of Operator Enclosure Class Product No. Digit
Open P1
Type 1 P2
Type 3/12/13
—
Type 4/4X
—
Flush Mounted P5
Open T1
Type 1 T2
Type 3/12/13 T3
Type 4/4X T4
Flush Mounted T5
No hubs installed on Types 1, 3, 12, and 13 enclosures. 3/4-inch hubs
standard on Type 4X enclosures.
Toggle Lever
Push Button
Description
Product
Number
Type 1 Enclosure for Toggle Operated 2- to 4-Pole Starters
CR1062X9
Type 1 Enclosure for Push ButtonOperated 2- to 4-Pole Starters
CR1062X10
Type 3/12/13 Enclosure (no hubs)
Toggle Devices Only
CR1062X28
Type 4X Enclosure (with hubs)
Toggle Devices Only
CR1062X23
Type 1 Flush-Mounted Enclosure for
Toggle-Operated Starters
CR1062X30
Type 1 Flush-Mounted Enclosure for
Push Button-Operated Starters
CR1062X31
Indicating Light Color Product No. Digit
No Indicating Light Ø
Red Light
Green Light G
R
Type 1
Enclosure
Type 3/12/13
and 4/4X
Enclosures
No Indicating Light 00 00
120 V/60 Hz 100 V/50 Hz 02 02
240 V/60 Hz 220 V/50 Hz 03 03
480 V/60 Hz 440 V/50 Hz 04 04
600 V/60 Hz 05 05
Product No. Digit
Product No.
Digit
Product No.
Digit
Product No.
Digit
None A A A
1 NO B B B
2 NO C C
—
Cannot have 2 auxiliary contacts with size 1-P device.
Auxiliary
Contacts
Size 0 Size 1 Size 1-P
Product No.
Digit
Product No.
Digit
Standard Overload A A
Omit Overload B B
Protection
Single-Phase Three-Phase
Order heaters as a separate item from Heater Selection Tables, page 1-172.
NEMA Size Number of Poles Product No. Digits
Single-Phase DC (in series) R1
Single-Phase (AC) R2
3-Pole Three-Phase R3
Single-Phase DC (in series) S1
Single-Phase (AC) S2
3-Pole Three-Phase S3
Single-Phase DC (in series)
—
Single-Phase AC in Parallel T2
3-Pole Three-Phase
—
M-0
M-1
M-1P
NEMA Rated Full Voltage Starters - Manual
CR1062
Single-Phase and Polyphase
10 HP Maximum
600 Volts
25 to 60 Hertz
Section 1
1
Select NEMA Size and Number of Poles
2
Select Protection
3
Select Auxiliary Contacts
4
Select Type of Operator and Enclosure Type
5
Select Indicating Light Option
2601RC
Rev. 8/15
Prices and data subject to
change without notice
➋➌
6
Select Indicating Light Color
Enclosure Kits
Control Catalog
1-169