GE - General Electric AF-650GP Wiring Diagrams

AF-650GP™General Purpose Drive
91 (L1) 92 (L2) 93 (L3)
PE
88 (-) 89 (+)
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24V OUT)
13 (+24V OUT)
18 (D IN)
20
(COM D IN)
10Vdc
15mA 130/200mA
+ -+-
(U) 96
(V) 97
(W) 98
(PE) 99
(COM A OUT) 39
(A OUT) 42
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
0V
5V
S801
0/4-20 mA
RS-485
03
0-10Vdc
+10Vdc
0-10Vdc 0/4-20 mA
240Vac, 2A
24Vdc
02
01
05
04
06
240Vac, 2A
24V (NPN) 0V (PNP)
0V (PNP)
24V (NPN)
19 (D IN)
24V (NPN) 0V (PNP)
27
24V
0V
(D IN/OUT)
0V (PNP)
24V (NPN)
(D IN/OUT)
0V
24V
29
24V (NPN) 0V (PNP)
0V (PNP)
24V (NPN)
33 (D IN)
32 (D IN)
1 2
ON
S201
ON
21
S202
ON=0-20mA OFF=0-10V
95
400Vac, 2A
21
ON
S801
ON = Terminated OFF = Open
Motor
Analog Output
(R+) 82
(R-) 81
37 (D IN)
(PNP) = Source (NPN) = Sink
3 Phase Input Power
DC Bus
Switch Mode Power Supply
Dynamic Brake resistor
relay 1
relay 2
RS-485 Interface
Start*
No Operation*
No Operation**
No Operation*
No Operation*
Safe Stop Alarm*
Jog*
Basic Wiring Diagrams
Section 15Drives
Rev. 8/15
Prices and data subject to change without notice
** Indicates default setting for version 1.10 drives or higher. Prior versions are set to Coast Inverse, indicating that terminal #27 must be Logic “High” to
15-22
* Indicates default setting; see Parameter Group E-## to re-program.
enable the drive to run. See Parameter E-03 Terminal 27 Digital Input to re-program.
These terminals are only available with optional factory installed brake chopper.
Control Catalog