GE - General Electric AF-60LP Specification Sheet

Drives
AF-60LP™Micro Drive
Standard Specifications
Section 15
Environmental Conditions
Enclosure IP20 (NEMA 1 with optional NEMA 1 kit) Installation Location Do not install in locations where product could be
Ambient Temperature -10° to +50°C Ambient Humidity 5 to 95% RH (non-condensing) Vibration 1.0g Storage Temperature -25° to 65°C
Standards
Approvals CE, UL, cUL , and C-Tick
Suitable for use on a circuit capable of delivering not more than 100,000 rms symmetrical amperes for 230V and 460V. WEEE and RoHS Compliant
Input Power Supply
Rated Input AC Voltage 200-240 Vac, 1-phase, 50-60 Hz, +/- 10% V
Maximum Voltage Imbalance 3% of rated supply voltage True Power Factor > 0.4 nominal at rated load Displacement Power Factor > 0.98 Switching on input power supply Maximum twice/minute Environment according to EN60664-1 Overvoltage category III/pollution degree 2
200-240 Vac, 3-phase, 50-60 Hz, +/- 10% V 380-480 Vac, 3-phase, 50-60 Hz, +/- 10% V
Output
Rated Output Voltage 0-100% of supply voltage Output Frequency 0-200 Hz (Adv. Vector Control Plus Mode),
Switching on output Unlimited Accel/Decel Times 0.05-3600 seconds Overload Current Rating 150% of drive rated current for 1 minute
0-400 Hz (Volts/Hertz Mode)
Control
Control Method Sinusoidal PWM Control (V/Hz with torque
Switching Frequency Select 2, 4, 8, 12, 16 kHz Operation Method Keypad operation: Hand, Off, Auto
Frequency Reference Setting Up or Down buttons on keypad or external reference Analog Input Built in Potentiometer
Preset Speeds 8 presets via digital inputs Link Operation Drive RS-485 or Modbus RTU Second Reference Setting Switch from speed reference 1 to reference 2
Trim Reference Setting Available for speed reference offset via potentiometer,
Acceleration/Deceleration Time 0.05-3600 seconds (two acceleration and deceleration
DC Injection Braking Starting frequency: 0.0-400 Hz
Frequency Limit 0-400 Hz Jump Frequency Control Two jump (or skip) frequencies via parameter
Jogging Operation Operation via On key or digital input (Fwd or Rev) Auto-Restart After Power Failure Restarts the drive without stopping after
Slip Compensation Maintains motor at constant speed with load fluctuations Energy Savings Controls output voltage to minimize motor loss during
Start Mode Function This functionality smoothly catches a spinning motor
vector control)
Digital Input: Programmable for Start/Stop,
Forward/Reverse, Jog Timer operation: Stop after predetermined time frame Link operation: RS-485 Modbus RTU
0-10 Vdc analog input 4-20ma analog input
via digital input
voltage input, or current input
rates are selectable via digital inputs. Acceleration and deceleration patterns can be selected from linear or S-curve
Braking time: 0.0-60.0 seconds Braking level: 0-150% of rated current
set to avoid mechanical vibration
instantaneous power failure
constant speed operation
Logic Controller (LC)
Logic Controller Events Over 23 types of Programmable Events Comparators Array of 4 Comparators Timers Array of 3 Timers, adjustable from 0.0 to 3600 sec Logic Rules Array of 4 Boolean Logic Rules Logic Controller States Array of 20 Logic Controller Action States
Process Controller (PI)
Process CL Feedback Select No function, analog input 1, analog input 2,
Process PI Control Normal or Inverse Process PI Anti Windup Disabled or enabled Process PI Start Speed 0.0-200 Hz Process PI Proportional Gain 0.00-10.00 Process PI Integral Gain 0.10-9999 seconds Process PI Feed Forward Factor 0-400% On Reference Bandwidth 0-200%
pulse input, local bus reference
Indication
LEDs Green - drive is on
Monitor Units Available Frequency, current, voltage, power, horsepower,
Yellow - indicates a warning Red - indicates an alarm
% load, speed, or time
Trip Codes
2 Live Zero Error 4 Line Phase Loss 7 DC Overvoltage 8 DC Undervoltage 9 Drive Overload 10 Motor Overtemperature 11 Motor Thermistor Overtemperature 12 Torque Limit 13 Overcurrent 14 Ground Fault 16 Short Circuit 17 Control Word Timeout 25 Brake Resistor Short-Circuited 27 Brake Chopper Short-Circuited 28 Brake Check 29 Power Board Overtemperature 30 Missing U Phase 31 Missing V Phase 32 Missing W Phase 38 Internal Fault 47 Control Voltage Fault 51 Auto Tune Check - Wrong Motor Parameters 52 Auto Tune Low Inom - Motor current is too low 59 Current Limit 63 Mechanical Brake Low 80 Drive restored to factory settings
Monitoring Parameters Available
Power kW Power HP Motor Voltage V Frequency Hz Motor Current A Frequency % Motor Thermal % DC Link Voltage V Drive Current A Drive Max Current A Logic Controller State On/Off
15-6
Control Catalog
Rev. 8/15
Prices and data subject to change without notice