Copyright, Limitation of Liability and Revision Rights5
2 Safety
Safety instructions7
General Warning7
Before commencing repair work8
Special conditions8
Avoid unintended start9
IT mains9
3 Electrical Installation
Electrical Installation11
Power Connections11
Mains connection23
Fuses24
Fuse tables24
Motor Insulation25
5
7
11
Motor Bearing Currents26
Control cable routing26
Electrical Installation, Control Terminals28
Connection Examples29
Start/Stop29
Pulse Start/Stop29
Electrical Installation - additional31
Electrical Installation, Control Cables31
Switches S201, S202, and S80133
Final Set-up and Test34
Additional Connections36
Motor Thermal Protection36
4 Introduction
5 Mechanical Installation
How to Get Started39
Pre-installation40
37
39
Planning the Installation Site40
Receiving the Frequency Converter40
Transportation and Unpacking40
Lifting42
Mechanical Dimensions44
1
AF-600 FP High Power Operating Instructions
Rated Power51
Mechanical Installation52
Terminal locations - Unit Size 4X54
Terminal Locations - Unit Size 5X55
Terminal Locations - Unit Sizes 6X57
Cooling and Airflow60
Field Installation of Options64
Installation of Duct Cooling Kit in Rittal Units64
Installation on pedestal67
Installation of Mains Shield for frequency converters69
Panel Options69
Unit Size 6X Panel Options69
6 How to operate the frequency converter
How to operate the keypad71
Tips and tricks78
7 How to Program
Quick Menu Mode83
Macros88
Parameter List119
K-## Keypad Set-up120
F-## Fundamental Parameters122
E-## Digital In/Outs123
C-## Frequency Control Functions125
P-## Motor Data126
H-## High Perf Parameters127
AN-## Analog In / Out129
SP-## Special Functions130
O-## Options/Comms131
AO-## Analog I/O Option132
71
81
DN-## DevicNet133
PB-## Profibus134
BN-## BACnet135
ID-## Drive Information136
DR-## Data Readouts138
LG-## Logs & I/O Opt. Status140
AP-## HVAC Appl. Param.141
FB-## Fire/Bypass Operation142
T-## Timed Functions143
CL-## PID Closed Loop144
XC-## Ext. PID Closed Loop145
2
AF-600 FP High Power Operating Instructions
PC-## Pump Controller146
LC-## Logic Controller147
B-## Braking Functions148
8 General Specifications
9 Warnings and Alarms
Fault messages164
Index
149
161
168
3
1
AF-600 FP High Power Operating Instructions
4
AF-600 FP High Power Operating Instructions
1 How to Read these Operating Instructions
1.1.1 Copyright, Limitation of Liability and Revision Rights
This publication contains information proprietary to GE. By accepting and using this manual the user agrees that the information contained herein will be used
solely for operating equipment from GE or equipment from other vendors provided that such equipment is intended for communication with GE equipment over
a serial communication link. This publication is protected under the Copyright laws of Denmark and most other countries.
GE does not warrant that a software program produced according to the guidelines provided in this manual will function properly in every physical, hardware or
software environment.
Although GE has tested and reviewed the documentation within this manual, GE makes no warranty or representation, neither expressed nor implied, with respect
to this documentation, including its quality, performance, or fitness for a particular purpose.
In no event shall GE be liable for direct, indirect, special, incidental, or consequential damages arising out of the use, or the inability to use information contained
in this manual, even if advised of the possibility of such damages. In particular, GE is not responsible for any costs, including but not limited to those incurred as
a result of lost profits or revenue, loss or damage of equipment, loss of computer programs, loss of data, the costs to substitute these, or any claims by third
parties.
GE reserves the right to revise this publication at any time and to make changes to its contents without prior notice or any obligation to notify former or present
users of such revisions or changes.
1
5
1.1.2 Symbols
Symbols used in this manual:
1
NB!
Indicates something to be noted by the reader.
AF-600 FP High Power Operating Instructions
Indicates a general warning.
Indicates a high-voltage warning.
✮
Indicates default setting
1.1.3 Available literature
-Operating Instructions provide the necessary information for getting the frequency converter up and running.
-Design Guide entails all technical information about the frequency converter and customer design and applications.
-Programming Guide provides information on how to program and includes complete parameter descriptions.
GE technical literature is available in print from your local GE Sales Office or online at: www.geelectrical.com/drives
- AF-600 FP Built-in network manuals are available separately.
6
2 Safety
2.1.1 High voltage warning
AF-600 FP High Power Operating Instructions
The voltage of the frequency converter is dangerous whenever it is connected to mains. Incorrect installation of the motor or frequency
converter may cause damage to the equipment, serious injury or death. Consequently, it is essential to comply with the instructions in this
manual as well as local and national rules and safety regulations.
2.1.2 Safety instructions
Prior to using functions directly or indirectly influencing personal safety (e.g. Fire Mode or other functions either forcing the motor to stop or
attempting to keep it functioning) a thorough risk analysis and system test must be carried through. The system tests must include testing
failure modes regarding the control signalling (analog and digital signals and serial communication.
•Make sure the frequency converter is properly connected to earth.
•Do not remove mains connections, motor connections or other power connections while the frequency converter is connected to power.
•Protect users against supply voltage.
•Protect the motor against overloading according to national and local regulations.
•The earth leakage current exceeds 3.5 mA.
•The [OFF] key is not a safety switch. It does not disconnect the frequency converter from mains.
2.1.3 General Warning
2
Warning:
Touching the electrical parts may be fatal - even after the equipment has been disconnected from mains.
Also make sure that other voltage inputs have been disconnected, (linkage of DC intermediate circuit), as well as the motor connection for
kinetic back-up.
Before touching any potentially live parts of the frequency converter, wait at least as follows:
380 - 480 V, 110 - 250 kW, wait at least 20 minutes.
380 - 480 V, 315- 1000 kW, wait at least 40 minutes.
525 - 600 V, 45 - 400 kW, wait at least 20 minutes.
525 - 600 V, 450 - 1000 kW, wait at least 30 minutes.
Shorter time is allowed only if indicated on the nameplate for the specific unit.
Leakage Current
The earth leakage current from the frequency converter exceeds 3.5 mA. According to IEC 61800-5-1 a reinforced Protective Earth connection
must be ensured by means of: a min. 10mm² Cu or 16mm² Al PE-wire or an addtional PE wire - with the same cable cross section as the Mains
wiring - must be terminated separately.
Residual Current Device
This product can cause a D.C. current in the protective conductor. Where a residual current device (RCD) is used for extra protection, only an
RCD of Type B (time delayed) shall be used on the supply side of this product.
Protective earthing of the frequency converter and the use of RCD's must always follow national and local regulations.
7
AF-600 FP High Power Operating Instructions
2.1.4 Before commencing repair work
1.Disconnect the frequency converter from mains
2.Disconnect DC bus terminals 88 and 89
3.Wait at least the time mentioned in section General Warning above
2
4.Remove motor cable
2.1.5 Special conditions
Electrical ratings:
The rating indicated on the nameplate of the frequency converter is based on a typical 3-phase mains power supply, within the specified voltage, current and
temperature range, which is expected to be used in most applications.
The frequency converters also support other special applications, which affect the electrical ratings of the frequency converter.
Special conditions which affect the electrical ratings might be:
•High temperature applications which require de-rating of the electrical ratings
•Marine applications with more severe environmental conditions.
Other applications might also affect the electrical ratings.
Consult the relevant sections in this manual and in the AF-600 FP Design Guide for information about the electrical ratings.
Installation requirements:
The overall electrical safety of the frequency converter requires special installation considerations regarding:
•Fuses and circuit breakers for over-current and short-circuit protection
•Selection of power cables (mains, motor, brake, loadsharing and relay)
•Grid configuration (IT,TN, grounded leg, etc.)
•Safety of low-voltage ports (PELV conditions).
Consult the relevant clauses in these instructions and in the AF-600 FP Design Guide for information about the installation requirements.
2.1.6 Caution
The frequency converter's DC link capacitors remain charged after power has been disconnected. To avoid an electrical shock hazard, dis-
connect the frequency converter from the mains before carrying out maintenance. Before doing service on the frequency converter, wait at
least the amount of time indicated below:
VoltagePower sizeMin. Waiting Time
380 - 480 V110 - 250 kW20 minutes
315 - 1000 kW40 minutes
525 - 600 V45 - 400 kW20 minutes
450- 1000 kW30 minutes
Be aware that there may be high voltage on the DC link even when the LEDs are turned off.
8
AF-600 FP High Power Operating Instructions
2.1.7 Installation at high altitudes (PELV)
Installation at high altitude:
380 - 480 V: At altitudes above 3 km, please contact GE regarding PELV.
525 - 600 V: At altitudes above 2 km, please contact GE regarding PELV.
2.1.8 Avoid unintended start
While the frequency converter is connected to mains, the motor can be started/stopped using digital commands, bus commands, references or via the
keypad.
•Disconnect the frequency converter from mains whenever personal safety considerations make it necessary to avoid unintended start.
•To avoid unintended start, always activate the [OFF] key before changing parameters.
•An electronic fault, temporary overload, a fault in the mains supply, or lost motor connection may cause a stopped motor to start.
2.1.9 IT mains
IT Mains
Do not connect frequency converters with option factory installed A1/B1 RFI filters to mains supplies with a voltage between phase and earth
of more than 440 V for 400 V.
For 400 V IT mains and delta earth (grounded leg), mains voltage may exceed 440 V between phase and earth.
2
par. SP-50 RFI Filter can be used to disconnect the internal RFI capacitiors from the RFI filter to ground.
2.1.10 Software version and approvals: AF-600 FP Fan & Pump Drive
AF-600 FP
This manual can be used with all AF-600 FP frequency converters with software version 2.9x.
The software version number can be seen from par. ID-43 Software Version.
Software version: 2.9.x
2.1.11 Disposal instruction
Equipment containing electrical components must not be disposed of together with domestic waste.
It must be separately collected with electrical and electronic waste according to local and currently valid legislation.
9
3
AF-600 FP High Power Operating Instructions
10
AF-600 FP High Power Operating Instructions
3 Electrical Installation
3.1 Electrical Installation
3.1.1 Power Connections
Cabling and Fusing
NB!
Cables General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper (75°C) conductors are recommended.
The power cable connections are situated as shown below. Dimensioning of cable cross section must be done in accordance with the current ratings and local
legislation. See the Specifications section for details.
For protection please see fuse in the tables of the fuse section. Always ensure that proper fusing is made according to local regulation.
3
NB!
Use a screened/armoured motor cable to comply with EMC emission specifications. For more information, see EMC specifications in the AF-600 FP/Design
Guide.
See section General Specifications for correct dimensioning of motor cable cross-section and length.
11
AF-600 FP High Power Operating Instructions
Screening of cables:
Avoid installation with twisted screen ends (pigtails). They spoil the screening effect at higher frequencies. If it is necessary to break the screen to install a motor
isolator or motor contactor, the screen must be continued at the lowest possible HF impedance.
Connect the motor cable screen to both the de-coupling plate of the frequency converter and to the metal housing of the motor.
Make the screen connections with the largest possible surface area (cable clamp). This is done by using the supplied installation devices within the frequency
converter.
Cable-length and cross-section:
The frequency converter has been EMC tested with a given length of cable. Keep the motor cable as short as possible to reduce the noise level and leakage
3
currents.
Switching frequency:
When frequency converters are used together with Sine-wave filters to reduce the acoustic noise from a motor, the switching frequency must be set according
to the instruction in par. F-26 Motor Noise (Carrier Freq).
Term. no.
U1V1W1
U1V1W1
1)
Protected Earth Connection
96979899
UVW
W2U2V26 wires out of motor
1)
Motor voltage 0-100% of mains voltage.
PE
1)
PE
1)
PE
3 wires out of motor
Delta-connected
Star-connected U2, V2, W2
U2, V2 and W2 to be interconnected separately.
12
Illustration 3.1: Compact IP 21 (NEMA 1) and IP 54 (NEMA 12), Unit Size 41
AF-600 FP High Power Operating Instructions
3
Illustration 3.2: Compact IP 21 (NEMA 1) and IP 54 (NEMA 12) Unit Size 42
1)AUX Relay5)Brake
010203 -R+R
040506 8182
2)Temp Switch6)SMPS Fuse (see fuse tables for part number)
1061041057)AUX Fan
3)Line 100101 102103
RSTL1L2L1 L2
9192938)Fan Fuse (see fuse tables for part number)
L1L2L39)Mains ground
4)Load sharing10)Motor
-DC+DC U VW
8889 969798
T1T2T3
13
3
AF-600 FP High Power Operating Instructions
Illustration 3.3: Compact IP 00 (Chassis), Unit Size 43
Illustration 3.5: Position of earth terminals IP00 (Chassis), 4X unit sizes
NB!
Unit sizes 42 and 44 are shown in above examples. Unit sizes 41 and 43 are equivalent.
14
Illustration 3.6: Position of earth terminals IP21 (NEMA type 1) and IP54
(NEMA type 12)Unit Size 42
Illustration 3.7: Compact IP 21 (NEMA 1) and IP 54 (NEMA 12) Unit Size 51
AF-600 FP High Power Operating Instructions
3
Illustration 3.9: Position of earth terminals IP00 (Chassis), Unit Size 52
15
3
AF-600 FP High Power Operating Instructions
Illustration 3.10: Rectifier Cabinet, unit sizes 61, 62, 63 and 64.
1)24 V DC, 5 A5)Loadsharing
T1 Output Taps-DC+DC
Temp Switch 8889
106104 1056)Control Transformer Fuses (2 or 4 pieces). See fuse tables for part numbers
2)Manual Motor Starters7)SMPS Fuse. See fuse tables for part numbers
3)30 A Fuse Protected Power Terminals8)Manual Motor Controller fuses (3 or 6 pieces). See fuse tables for part numbers
4)Line9)Line Fuses, F1 and F2 frame (3 pieces). See fuse tables for part numbers
RST10)30 Amp Fuse Protected Power fuses
L1L2 L3
16
AF-600 FP High Power Operating Instructions
3
Illustration 3.11: Inverter Cabinet, unit sizes 61 and 63.
1) External Temperature Monitoring6)Motor
2) AUX RelayUVW
010203 969798
040506 T1T2T3
3) NAMUR7)NAMUR Fuse. See fuse tables for part numbers
4) AUX Fan8)Fan Fuses. See fuse tables for part numbers
100 101 102 1039)SMPS Fuses. See fuse tables for part numbers
L1L2 L1L2
5) Brake
-R+R
8182
17
3
AF-600 FP High Power Operating Instructions
Illustration 3.12: Inverter Cabinet, unit sizes 62 and 64
1) External Temperature Monitoring6)Motor
2) AUX RelayUVW
010203 969798
040506 T1T2T3
3) NAMUR7)NAMUR Fuse. See fuse tables for part numbers
4) AUX Fan8)Fan Fuses. See fuse tables for part numbers
100 101 102 1039)SMPS Fuses. See fuse tables for part numbers
L1L2 L1L2
5) Brake
-R+R
8182
18
AF-600 FP High Power Operating Instructions
3
Illustration 3.13: Options Cabinet, unit sizes 63 and 64
1) Pilz Relay Terminal4)Safety Relay Coil Fuse with PILS Relay
2) RCD or IRM TerminalSee fuse tables for part numbers
3) Mains5)Line Fuses, F3 and F4 (3 pieces)
RST See fuse tables for part numbers
91 92 93 6)Contactor Relay Coil (230 VAC). N/C and N/O Aux Contacts
L1 L2 L3 7)Circuit Breaker Shunt Trip Control Terminals (230 VAC or 230 VDC)
Please consult GE for more information on these custom options.
19
AF-600 FP High Power Operating Instructions
3.1.2 Earthing
The following basic issues need to be considered when installing a frequency converter, so as to obtain electromagnetic compatibility (EMC).
•Safety earthing: Please note that the frequency converter has a high leakage current and must be earthed appropriately for safety reasons. Apply local
safety regulations.
•High-frequency earthing: Keep the earth wire connections as short as possible.
Connect the different earth systems at the lowest po ssible conductor impedance. The lowest possible conductor impedance is obtained by keeping the conductor
as short as possible and by using the greatest possible surface area.
3
The metal cabinets of the different devices are mounted on the cabinet rear plate using the lowest possible HF impedance. This avoids having different HF voltages
for the individual devices and avoids the risk of radio interference currents running in connection cables that may be used between the devices. The radio
interference will have been reduced.
In order to obtain a low HF impedance, use the fastening bolts of the devices as HF connection to the rear plate. It is necessary to remove insulating paint or
similar from the fastening points.
3.1.3 Extra Protection (RCD)
ELCB relays, multiple protective earthing or earthing can be used as extra protection, provided that local safety regulations are complied with.
In the case of an earth fault, a DC component may develop in the fault current.
If ELCB relays are used, local regulations must be observed. Relays must be suitable for protection of 3-phase equipment with a bridge rectifier and for a brief
discharge on power-up.
See also the section Special Conditions in the Design Guide.
3.1.4 Drives with factory installed A1/B1 RFI Filter option:
Mains supply isolated from earth
If the frequency converter is supplied from an isolated mains source ( IT mains, floating delta and grounded delta) or TT/TN-S mains with grounded leg, the RFI
switch is recommended to be turned off (OFF)
motors are connected or the motor cable length is above 25 m, it is recommended to set par. SP-50 RFI Filter to [ON].
1)
Not available for 525-600 V frequency converters.
In OFF, the internal RFI capacities (filter capacitors) between the chassis and the intermediate circuit are cut off to avoid damage to the intermediate circuit and
to reduce the earth capacity currents (according to IEC 61800-3).
It is important to use isolation monitors that are capable for use together with power electronics (IEC 61557-8).
1)
via par. SP-50 RFI Filter. For further reference, see IEC 364-3. In case optimum EMC performance is needed, parallel
3.1.5 Torque
When tightening all electrical con nections it is ver y important to tighten with
the correct torque. Too low or too high torque results in a bad electrical con-
nection. Use a torque wrench to ensure correct torque
20
Illustration 3.14: Always use a torque wrench to tighten the bolts.
AF-600 FP High Power Operating Instructions
Unit SizeTerminalTorqueBolt size
41, 42, 43 and 44Mains
Motor
Load sharing
Brake
51 and 52Mains
Motor
Load sharing
Brake9.5 (84 in-lbs)M8
61, 62, 63 and 64Mains
Motor
Load sharing
Brake
Regen
Table 3.1: Torque for terminals
3.1.6 Shielded Cables
It is important that shielded and armoured cables are connected in a proper way to ensure high EMC immunity and low emissions.
19 Nm (168 in-lbs)M10
9.5 (84 in-lbs)M8
19 NM (168 in-lbs)M10
19 Nm (168 in-lbs)M10
19 Nm (168 in-lbs)
9.5 Nm (84 in-lbs)
19 Nm (168 in-lbs)
M10
M8
M10
3
Connection can be made using either cable glands or clamps:
•EMC cable glands: Generally available cable glands can be used to ensure an optimum EMC connection.
•EMC cable clamp: Clamps allowing easy connection are supplied with the frequency converter.
3.1.7 Motor cable
The motor must be connected to terminals U/T1/96, V/T2/97, W/T3/98. Earth to terminal 99. All types of three-phase asynchronous standard motors can be used
with a frequency converter unit. The factory setting is for clockwise rotation with the frequency converter output connected as follows:
Terminal No.
96, 97, 98, 99Mains U/T1, V/T2, W/T3
• Terminal U/T1/96 connected to U-phase
• Terminal V/T2/97 connected to V-phase
• Terminal W/T3/98 connected to W-phase
Function
Earth
The direction of rotation can be changed by switching two phases in the motor cable or by changing the setting of par. H-08 Reverse Lock.
Motor rotation check can be performed using par. P-08 Motor Rotation Check and following the steps shown in the display.
21
AF-600 FP High Power Operating Instructions
Unit Size 6X Requirements
Unit Size 61/63 requirements: Motor phase cable quantities must be 2, 4, 6, or 8 (multiples of 2) to obtain equal amount of wires attached to both inverter module
terminals. The cables are required to be equal length within 10% between the inverter module terminals and the first common point of a phase. The recommended
common point is the motor terminals.
Unit Size 62 and 64 requirements: Motor phase cable quantities must be 3, 6, 9, or 12 (multiples of 3) to obtain equal amount of wires attached to each inverter
module terminal. The wires are required to be equal length within 10% between the inverter module terminals and the first common point of a phase. The
recommended common point is the motor terminals.
Output junction box requirements: The length, minimum 2.5 meters, and quantity of cables must be equal from each inverter module to the common terminal
in the junction box.
3
3.1.8 Load Sharing
Terminal No.Function
88, 89Loadsharing
The connection cable must be screened and the max. length from the frequency converter to the DC bar is limited to 25 metres (82 feet).
Load sharing enables linking of the DC intermediate circuits of several frequency converters.
Please note that voltages up to 1099 VDC may occur on the terminals.
Load Sharing calls for extra equipment and safety considerations. For further information, see load sharing Instructions MI.50.NX.YY.
Please note that mains disconnect may not isolate the frequency converter due to DC link connection
3.1.9 Shielding against Electrical Noise
Before mounting the mains power cable, mount the EMC metal cover to ensure best EMC performance.
NOTE: The EMC metal cover is only included in units with factory installed A1/B1 RFI Filter option..
Illustration 3.15: Mounting of EMC shield.
22
AF-600 FP High Power Operating Instructions
3.1.10 Mains connection
Mains must be connected to terminals 91, 92 and 93. Earth is connected to the terminal to the right of terminal 93.
Terminal No.
91, 92, 93
94
Check the name plate to ensure that the mains voltage of the frequency converter matches the power supply of your plant.
Ensure that the power supply can supply the necessary current to the frequency converter.
Function
Mains R/L1, S/L2, T/L3
Earth
3.1.11 External Fan Supply
In case the frequency converter is supplied by DC or if the fan must run independently of the power supply, an external power supply can be applied. The connection
is made on the power card.
Terminal No.
100, 101
102, 103
The connector located on the power card provides the connection of line voltage for the cooling fans. The fans are connected from factory to be supplied form
a common AC line (jumpers between 100-102 and 101-103). If external supply is needed, the jumpers are removed and the supply is connected to terminals 100
and 101. A 5 Amp fuse should be used for protection. In UL applications this should be LittleFuse KLK-5 or equivalent.
Function
Auxiliary supply S, T
Internal supply S, T
3
23
AF-600 FP High Power Operating Instructions
3.1.12 Fuses
Branch circuit protection:
In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and
over-current protected according to national/international regulations.
Short-circuit protection:
The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. GE recommends using the fuses mentioned below to protect
service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case of a short-circuit
on the motor output.
3
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. Fuses or circuit breakers can be used to provide the over-
current protection in the installation. Over-current protection must always be carried out according to national regulations.
3.1.13 Fuse tables
380-480 V, frame sizes 4X, 5X and 6X
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 480V/600V depending on the drive voltage rating. With the
proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
AF-600
150 HPFWH-
200 HPFWH-
250 HPFWH-
300 HPFWH-
350 HPFWH-
Table 3.3: For Unit Sizes 41, 42, 43, and 44,380-480 V
AF-600 FP
450 HP170M4017700 A, 700 V6.9URD31D08A070020 610 32.700
500 HP170M6013900 A, 700 V6.9URD33D08A090020 630 32.900
550 HP170M6013900 A, 700 V6.9URD33D08A090020 630 32.900
600 HP170M6013900 A, 700 V6.9URD33D08A090020 630 32.900
Table 3.4: For Unit Sizes 51 and 52, 380-480 V
AF-600 FP
650 HP170M70811600 A, 700 V20 695 32.1600170M7082
750 HP170M70811600 A, 700 V20 695 32.1600170M7082
900 HP170M70822000 A, 700 V20 695 32.2000170M7082
1000 HP170M70822000 A, 700 V20 695 32.2000170M7082
1200 HP170M70832500 A, 700 V20 695 32.2500170M7083
1350 HP170M70832500 A, 700 V20 695 32.2500170M7083
Bussmann
FP
E1958
JFHR2**
300
350
400
500
600
Bussmann
E4273
T/JDDZ**
JJS300
JJS350
JJS400
JJS500
JJS600
Bussmann PN*RatingFerrazSiba
Bussmann PN*RatingSibaInternal Bussmann Option
SIBA
E180276
RKI/JDDZ
2028220-
315
206xx32-
315
206xx32-
400
206xx32-
500
206xx32-
600
LittelFuse
E71611
JFHR2**
L50S-300A50-P300NOS-
L50S-350A50-P350NOS-
L50S-400A50-P400NOS-
L50S-500A50-P500NOS-
L50S-600A50-P600NOS-
Ferraz-
Shawmut
E60314
JFHR2**
Bussmann
E4274
H/JDDZ**
300
350
400
500
600
Bussmann
E125085
JFHR2*
170M3017170M3018
170M3018170M3018
170M4012170M4016
170M4014170M4016
170M4016170M4016
Bussmann
Internal
Option
Table 3.5: Unit Sizes 61, 62, 63, and 64, 380-480 V
AF-600 FP
650 HP170M86111100 A, 1000 V20 781 32.1000
750 HP170M86111100 A, 1000 V20 781 32.1000
900 HP170M64671400 A, 700 V20 681 32.1400
1000 HP170M64671400 A, 700 V20 681 32.1400
1200 HP170M86111100 A, 1000 V20 781 32.1000
1350 HP170M64671400 A, 700 V20 681 32.1400
Table 3.6: Unit Sizes 61, 62, 63, and 64, Inverter module DC Link Fuses, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use
**Any minimum 480 V UL listed fuse with associated current rating may be used to meet UL requirements.
Table 3.7: Unit Size 41, 42, 43, and 44, 525-600 V
AF-600 FP
450 HP170M4017700 A, 700 V6.9URD31D08A070020 610 32.700
500 HP170M4017700 A, 700 V6.9URD31D08A070020 610 32.700
600 HP170M6013900 A, 700 V6.9URD33D08A090020 630 32.900
650 HP170M6013900 A, 700 V6.9URD33D08A090020 630 32.900
Table 3.8: Unit Sizes 51 and 52, 525-600 V
AF-600 FP
750 HP170M70811600 A, 700 V20 695 32.1600170M7082
950 HP170M70811600 A, 700 V20 695 32.1600170M7082
1050 HP170M70811600 A, 700 V20 695 32.1600170M7082
1150 HP170M70811600 A, 700 V20 695 32.1600170M7082
1350 HP170M70822000 A, 700 V20 695 32.2000170M7082
Table 3.9: Unit Sizes 61, 62, 63, and 64, 525-600 V
AF-600 FP
750 HP170M86111100 A, 1000 V20 781 32. 1000
950 HP170M86111100 A, 1000 V20 781 32. 1000
1050 HP170M86111100 A, 1000 V20 781 32. 1000
1150 HP170M86111100 A, 1000 V20 781 32. 1000
1350 HP170M86111100 A, 1000 V20 781 32. 1000
Table 3.10: Unit Sizes 61, 62, 63, and 64, 525-600 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use.
Bussmann PN*RatingFerrazSiba
Bussmann PN*RatingSibaInternal Bussmann Option
Bussmann PN*RatingSiba
3.1.14 Motor Insulation
3
For motor cable lengths ≤ the maximum cable length listed in the General Specifications tables the following motor insulation ratings are recommended because
the peak voltage can be up to twice the DC link voltage, 2.8 times the mains voltage, due to transmission line effects in the motor cable. If a motor has lower
insulation rating it recommended to use a du/dt or sine wave filter.
Nominal Mains VoltageMotor Insulation
UN ≤ 420 V
420 V < U
500 V < UN ≤ 600 V
≤ 500 V
N
Standard ULL = 1300 V
Reinforced U
Reinforced ULL = 1800 V
= 1600 V
LL
25
AF-600 FP High Power Operating Instructions
3.1.15 Motor Bearing Currents
All motors installed with drives 90kW or higher power drives should have NDE (Non-Drive End) insulated bearings installed to eliminate circulating bearing currents.
To minimize DE (Drive End) bearing and shaft currents proper grounding of the drive, motor, driven machine, and motor to the driven machine is required.
Standard Mitigation Strategies:
1.Use an insulated bearing
2.Apply rigorous installation procedures
3
-Ensure the motor and load motor are aligned
-Strictly follow the EMC Installation guideline
-Reinforce the PE so the high frequency impedance is lower in the PE than the input power leads
-Provide a good high frequency connection between the motor and the frequency converter for instance by screened cable which has a 360°
connection in the motor and the frequency converter
-Make sure that the impedance from frequency converter to building ground is lower that the grounding impedance of the machine. This can
be difficult for pumps
-Make a direct earth connection between the motor and load motor
3.Lower the IGBT switching frequency
4.Modify the inverter waveform, 60° AVM vs. SFAVM
5.Install a shaft grounding system or use an isolating coupling
6.Apply conductive lubrication
7.Use minimum speed settings if possible
8.Try to ensure the line voltage is balanced to ground. This can be difficult for IT, TT, TN-CS or Grounded leg systems
9.Use a dU/dt or sinus filter
3.1.16 Control cable routing
Tie down all control wires to the designated control cable routing as shown
in the picture. Remember to connect the shields in a proper way to ensure
optimum electrical immunity.
Field Installed Network Module options connection
Connections are made to the network options on the control card. For details
see the relevant network instructions. The cable must be placed to the left
inside the frequency converter and tied down together with other control
wires (see picture).
Illustration 3.16: Wire path for control wiring.
26
In the IP 00 (Chassis) and IP 21 (NEMA 1) units it is also possible to connect the
network from the top of the unit as shown on the picture to the right. On the
IP 21 (NEMA 1) unit a cover plate must be removed.
Installation of field installed 24 Volt external DC Supply option module
(OPC24VPS)
Torque: 0.5 - 0.6 Nm (5 in-lbs)
Screw size: M3
AF-600 FP High Power Operating Instructions
3
Illustration 3.17: Top connection for fieldbus.
No.
35 (-), 36 (+)24 V external DC supply
24 VDC external supply can be used as low-voltage supply to the control card and any I/O or network option cards installed. This enables full operation of the
Keypad (including parameter setting) without connection to mains. Please note that a warning of low voltage will be given when 24 VDC has been connected;
however, there will be no tripping.
Use 24 VDC supply of type PELV to ensure correct galvanic isolation (type PELV) on the control terminals of the frequency converter.
Function
3.1.17 Access to Control Terminals
All terminals to the control cables are located beneath the Keypad. They are accessed by opening the door of the Nema 1 / Nema 12 or removing the covers of
the IP00 Open Chassis version.
27
3.1.18 Electrical Installation, Control Terminals
To connect the cable to the terminal:
1.Strip insulation by about 9-10 mm
1)
in the square hole.
1)
in the square hole.
3
2.
Insert a screwdriver
3.Insert the cable in the adjacent circular hole.
4.Remove the screwdriver. The cable is now mounted in the terminal.