Gefran W211 Data Sheet

PROFILE
Wattcor W211 line offers a wide range of solid state power controllers with “zero crossing” switching for resistive loads with current ratings up to 600A and 660Vac nominal voltages. The models of the W211 series accept Vdc and Vac logic controls. The conduction is activated by the control signal at the first zero crossing of the load power voltage. Switching off occurs by the first zero crossing of the load current after disabling the control signal. The control of three-phase loads can be by two or three W211 in series and fired in parallel. Each model is equipped with a logic input to disable the solid state relay/power controller and eventually break off power supply. Different options are available for the more critical applications, such as the “load control” (RPC option) which detects and indicates partial load failure interruption/cut-off, with a LED on the faceplate, and a relay alarm output. The DTC option allows the control of a possible SCR short-circuit or the complete current failure in the load. A further safety option is represented by the “electronic cut-off” circuit, (DE option), a device protecting the power element against a momentary excess
current higher than a selected value, corresponding to approx. 13 times the nominal current of the solid state power controller. The alarm condition disables the power supply, activates an alarm relay (in common with RPC option) and allows the instrument resetting through a front button. The WATTCOR W211 series are designed to guarantee nominal current and voltage values at 50°C ambient temperature, with a working temperature range from -5°C up to 60°C. 250A and 600A units are supplied with internal fuse and digital output for the fuse status. Signal connections are made via “plug-in” connectors to enable easy wiring. The instrument can be DIN rail or panel mounted (from 250 up to 600A current ratings, panel mounting only).
TECHNICAL DATA
General Features
Nominal working voltage
- 660Vac (max. range 20...725Vac) Nominal frequency: 50/60Hz
Current Ratings (50°C)
W211 (25-40-75-100-150-250-400-600A)
POWER CONTROLLERS, from 1KW to 400KW
Main Features
Conduction inhibition input
Overcurrent protection (DE option)
Detection of partial load failure
(RPC option)
SCR diagnosis circuit and complete load failure (DTC option)
Input control from Vdc and Vac logic signal
Zero crossing switching of mains voltage
High capacity anti-parallel SCR double thyristor
LED status indicators
MOV protections (varistor)
DIN rail or panel mounting
(depending on version)
Main Applications
Industrial heat-treatment furnaces
Industrial cooling plants
Painting plants
Driers for ceramics, paper
and textile products
Industrial heaters
Ovens and furnaces
Sterilizers
Repetitive Non repetitive
overcurrent overcurrent
(t=1s) (t=20ms) 25Arms 74A 600A 40Arms 100A 1500A 75Arms 180A 1700A 100Arms 300A 4800A 150Arms 300A 4800A 250Arms 450A 7800A 400Arms 2000A 15000A 600Arms 2000A 15000A
I2t for fusing Critical dv/dt
(t=1-10ms) with output
disactivated 25Arms 1800A2s 1000V/µs 40Arms 11200A2s 1000V/µs 75Arms 14450A2s 1000V/µs 100Arms 86200A2s 1000V/µs 150Arms 86200A2s 1000V/µs 250Arms 200000A2s 1000V/µs 400Arms 1125000A2s 500V/µs 600Arms 1125000A2s 500V/µs
Dissipated Power:
1.2 W per Amp of load
Control Input
• Two inputs available for Vdc and Vac logic signals
• Option for control via contact free from potential (option 4)
• Max. voltage-range:0...30Vdc, 0...32Vac
• Safety power-up voltage:< 3Vdc, <5Vac
• Safety power-off voltage: >5Vdc,≥15Vac
• Impedance: 1KW@5Vdc,
2.5KW@30Vdc,1.5KW for Vac
Inhibition Input
Max. voltage range: 0...30Vdc
Impedance: 15KW
Active inhibition: 5Vdc
Auxiliary Power Supply
- Required only if an option or a fan have
been selected
115 or 230Vac 50...60Hz - 5VA with
phase independent of the voltage on the load
- Fan power supply (for ratings ≥150A)
115 or 230Vac 50/60Hz - 35VA
Partial Load Failure Option (RPC)
Detects a decrease in the load current (in regard to a pre-selected value), distinguishing one caused by a mains voltage decrease. It is necessary to specify the voltage applied to the load (115 or 230 or 440Vac ± 10%)
Current limit point selectable from 30% up to 100% of nominal current (to be set via a front trimmer).
Min. working time to let the alarm start: 400ms
Alarm output: relay with NO 5A-250Vac working contact (shared by the DE option).
SCR (DTC) Control and Complete Load Failure Option
Detects current crossing in the load when there is no control signal (SCR short­circuit). Detects load current failure when a control signal is active (complete load or SCR failure/interruption, fuse break, load voltage failure). The alarm mode, with memory or not, is selectable via an internal switch.
Overcurrent Protection Option (DE)
Switching off with memory of the SCR if current exceeds the nominal value by 13 times
Option available for ratings from 25 up to 150A
Max. response time: 10ms@50Hz;
8.33ms@60Hz
Alarm output: 5A-250V no contact relay (shared by RPC option)
Reset of standard working through a front-face key
This option does not replace extra-fast fuses, which should be used in any installation.
Installation Comments
It is necessary to install the instrument correctly inside the panel to ensure best reliability:
Max. inclination as to the vertical axis: 10°
Vertical distance between two instruments: > 200mm
Horizontal distance between two instruments: > 20mm
POWER DISSIPATION CURVES
TYPE OF FUNCTIONING
Ratings from 25 up to 150A:
- DIN rapid rail mounting
- Panel mounting kit for ratings 75-150A (option 1886001)
MOUNTING
Ambient Temperature Ambient Temperature
Effective current A
Effective current A
Control signal
Load current
Ratings from 250 to 600A:
- Panel mounting only
Rating 600A
Rating 400A
Rating 250A
Rating 150A
Rating 100A
Rating 75A
Rating 40A
Rating 25A
140
120
100
80
60
40
20
0°C10°C20°C30°C40°C50°C60°C
700
600
500
400
300
200
100
0°C10°C20°C30°C40°C50°C60°C