2) F
INE-AUTOZERO
FUNCTION
Application mode Limits Result
The Fine-Autozero function is activated by :
1) positioning the magnet near the
Autozero label on the shell of the
sensor.
2) The magnet has to be maintained
on the Autozero position for a time
within 10 to 30 sec.
After removing the magnet the
signal will start changing the value
step by step.
Stop adjustment:
Touch the Autozero area with the
magnet to stop the signal scrolling.
The whole Zero unbalancement in
addition to the zero done by the
manufacturer, has to be within
± 10%FS
The output signal will change within a
± 100mV value (± 0.16mA for 4 to
20mA output) in steps of 6mV ( 12µA
for 4 to 20mA output).
Eg:
0..-6..-12..//-100..+100..+94..+88..0
When the desired zero value is rea-
ched stop the adjustment cycle by
touching the Autozero area with the
magnet.
The Fine-Autozero function doesn’t
work outside the defined limits.
NOTE:
- The step duration time is 5 sec
- During the Autozero phase, the output for current transmitter series, will increase to around 7mA.
Furthermore between the step variations it will be possible to have short overcurrent up to 7mA.
- That’s an immediate variation only visible during the Autozero phase; it won’t have any effects on the final result.
- The new zero value setted with the “Fine-Autozero” function, will be the zero reference for future “Autozero” procedures.
3) C
ALIBRATION
Application mode Limits Result
Start calibration
The Calibration function is
activated by short-circuiting the
CAL pin for a minimum time of
1 sec
Stop calibration
Release the CAL pin short-circuit
The whole Zero unbalancement in
addition to the zero done by the
manufacturer, has to be within
± 20%FS.
During the Calibration phase the
signal will be unbalanced at 80% FS.
The calibration effect is visible 2 sec
after short-circuiting CAL pin.
The Calibration function doesn’t work
outside the defined limits.
NOTE:
- Switching off the supply while the calibration function is activated, could be cause of calibration problems; the
transmitter can be restored to the initial value by activating the “partial reset function”.
- To locate the CAL pin contacts, please refer to item “CAL pin” at the beginning of this manual.
2