4) A
UTOSPAN
Application mode Limits Result
The Autospan function is activated in
three steps as explained in the
following.
Phase 1) pressure = 0 bar
:
1° Autozero
Activate the Autozero function
Phase 2) pressure = FS ***
:
Short-circuit CAL pin.
Maintain the short-circuit,
after a minimum time of 1 sec.,
start the “Autozero function”; the
magnet has to be maintained in
contact for a period of 1 - 10sec.
Than release the short-circuit,
after a minimum time of 1 sec.
Phase 3) pressure = 0 bar
:
2° Autozero
Activate the Autozero function
The whole Zero unbalancement in
addition to the zero done by the
manufacturer, has to be within
± 10%FS
The whole span unbalancement
which can be obtained must be within
± 5% of the FS of the transmitter
The transmitter will be calibrated at
the new Zero and Span values, within
the accuracy class of the sensor.**
The Autozero function doesn’t work
outside the defined limits.
NOTE:
**
: It is possible improve the calibration precision by doing several calibration runs (Autospan function).
***
: The FS has to be a pressure value within ± 5 %FS
- To locate the CAL pin contacts, please refer to item “CAL pin” at the beginning of this manual.
5) PARTIAL RESET OF THE CALIBRATION VALUES
Application mode Limits Result
The partial reset function is activated
by positioning the magnet near the
Autozero label on the shell of the
sensor.
The magnet has to be maintained on
the Autozero position for a time within
30 to 60 sec.
The Zero of the transmitter will be
restored to the factory settings; furthermore an Autozero will be done
automatically.
The Span calibration will not be affected.
NOTE:
- During the partial reset phase, the output for current transmitter series, will increase around 7mA
6) TOTAL RESET OF THE CALIBRATION VALUES
Application mode Limits Result
The total reset function is activated by
positioning the magnet near the
Autozero label on the shell of the
sensor.
The magnet has to be maintained on
the Autozero position for a time over
60 sec
The Zero and Span of the transmitter
will be restored to the factory
settings.
NOTE:
- During the total reset phase, the output for current transmitter series, will increase around 7mA
3