The “IMPACT” series of Gefran, are pressure transmitters,
without transmission fluid, for using in High temperature
environment (350°C).
Medium pressure is transferred directly to the sensitive
silicon element via a thick diaphragm.
Strain is transduced by a micro-worked silicon structure
(MEMS).
The operating principle is piezoresistive.
“IMPACT” is Gefran’s exclusive series of high-temperature
pressure sensors that use the piezoresistive principle.
The main characteristic of “IMPACT” sensors is that they
do not contain any transmission fluid.
The sensitive element, directly positioned behind the contact membrane, is realised in silicon through microprocessing techniques.
The micro structure includes the measurement membrane
and piezoresistors.
The minimum deflection required by the sensitive element
makes it possible to use very robust mechanics.
The process contact membrane can be up to 15 times thicker than the membrane used in traditional Melt sensors.
ADVANTAGES
- Total compatibility with the European RoHS Directive
- High strength
- Long life
- Working temperature: up to 350°C
- Excellent read stability over time
- Fast response time
MAIN FEATURES
• Pressure ranges:
0-100 to 0-1000 bar / 0-1500 to 0-15000 psi
• Accuracy: < ±0.25% FSO (H); < ±0.5% FSO (M)
• Standard threading 1/2-20UNF, M18x1.5
• Other types of diaphragms are available on request
• Autozero function on board / external option
• 15-5 PH stainless steel diaphragm GTP+ coated
AUTOZERO FUNCTION
All signal variations in the absence of pressure can be eliminated by using the Autozero function.
This function is activated by closing a magnetic contact
located on the transmitter electronics or by an external
contact.
The procedure is allowed only at zero pressure.
The Autozero function should be activated ONLY when the
sensor is completely installed on the system.
TECHNICAL SPECIFICATIONS
Accuracy (1)
Resolution16 Bit
Measurement range
Maximum overpressure
(without degrading performances)
Measurement principlePiezoresistive
Power supply13...30Vdc
Maximum current absorption
Output signal Full Scale FSO20mA
Zero balance
(tollerance ± 0.25% FSO)
Zero signals adjustment
(tollerance ± 0.25% FSO)
Response time (10...90% FSO) 8ms
Output noise (RMS 10-400Hz)< 0.025% FSO
Calibration signal80% FSO
Supply reverse polarity protectionYes
Compensed temperature range housing0...+85°C
Operating temperature range housing-30...+85°C
Storage temperature range housing-40...+125°C
Maximum diaphragm temperature350°C / 660°F
Zero signal variation due to process temperature variation in range (20-350°C)
Span signal variation due to process temperature variation in range (20-350°C)
Std contact diaphragm with process15-5 PH GTP+
Thermocouple (model IE2)
Protection degree
(with 6-pole female connector)
Electrical connection
FSO = Full scale output (1) BFSL method (Best Fit Straight Line):
includes combined effects of Non-Linearity, Hysteresis and Repeatability.
NOTE : dimensions refer to rigid stem length option “4” (153 mm – 6”)
WARNING : For installation use a maximum tightening torque of40 Nm (355 in-lb)
MECHANICAL DIMENSIONS
Max Temp.
220° C (428° F)
Max Temp.
220° C (428° F)
Max Temp.
220° C (428° F)
Max Temp.
220° C (428° F)
10.9
+0
-0.05
[0.43
+0
-0.002
]
IE1M
NOTE : dimensions refer to rigid stem length option “4” (153 mm – 6”)
WARNING : For installation use a maximum tightening torque of40 Nm (355 in-lb)
MECHANICAL DIMENSIONS
Max Temp.
220° C (428° F)
Max Temp.
220° C (428° F)
Max Temp.
220° C (428° F)
10.9
+0
-0.05
[0.43
+0
-0.002
]
IE1S
NOTE : dimensions refer to rigid stem length option “4” (153 mm – 6”)
WARNING : For installation use a maximum tightening torque of40 Nm (355 in-lb)
MECHANICAL DIMENSIONS
IE2
Max Temp.
220° C (428° F)
Max Temp.
230° C (446° F)
Max Temp.
230° C (446° F)
+0
+0
-0.05
-0.002
[0.43
]
10.9
NOTE : dimensions refer to rigid stem length option “4” (153 mm – 6”)
WARNING : For installation use a maximum tightening torque of40 Nm (355 in-lb)
SELF DIAGNOSTICS
(ohm
Below the conditions detected by the sensor self-diagnostics:
· Cut cable / device non connected / broken power supply, output <3.6mA
· Broken primary element / pin detachment, output >21mA
· Pressure above 200% of the span, output <3.6mA
· Pressure below the -30% of the span related to the zero value, output <3.6mA
· Voltage monitor in case of overvoltage/undervoltage/voltage variation in the electronics, output <3.6mA
· Program sequence error, output <3.6mA
· Overtemperature on the electronics, output <3.6mA
· Error on the primary element output or on the first amplification stage, output <3.6mA
OPTIONAL RELAY OUTPUT FOR EXCESS PRESSURE PROTECTION
Safety relay characteristics:
· Activation threshold to be defined in the order code
· Rated carry current: 1A
· Rated voltage: 24Vdc ± 20%
· Switch accuracy: 2 x sensor accuracy
· Hysteresis: 2% FSO
SUPPLYOUTPUTRELAY STATUS
OFF-OPEN
ON< X%fsCLOSED
ON> X%fsOPEN
ONoutput < 3,6mAOPEN
ONoutput > 21mAOPEN
NAMUR COMPLIANCE
The sensors are tested according to Namur NE21 recommendations.
The same compatibility is valid for the NE43 Namur recommendation with the following sensor behaviour in case of
breakdown:
· Cut cable: breakdown information as the signal is <3,6mA
· Device not connected: breakdown information as the signal is <3,6mA
· Broken power-supply: breakdown information as the signal is <3,6mA
or in case of performance problems:
· most common failures on primary sensors: the signal goes to>21mA
Note: in all the remaining situations, the output signal is always included between 3,6 and 21mA.
Recommendation: the error level set by the customer (e.g. maximum pressure value) has to be inside
the nominal range
The diagram shows the optimum ratio between load and power supply
for transmitters with 4…20mA output.
For correct function, use a combination of load resistance and voltage
that falls within the two lines in the graph above.
AUTOZERO FUNCTIONLOAD DIAGRAM
The Autozero function is
activated through a magnetic contact (external magnet
supplied with the sensor).
For the external Autozero
version short-circuit the correct pin.
See the manual for a complete Autozero function
explanation.
ELECTRICAL CONNECTIONS
CURRENT OUTPUT
RELAY OUTPUT (6-8 PIN CONNECTOR)
The cable shield is tied to connector via cable clamp
The cable shield is tied to connector via cable clamp