The ME Performance Level ‘c’ series of Gefran are
pressure transmitters for using in high temperature environment.
The main characteristic of this series is the capability to
read temperature of the media up to 400°C.
The constructive principle is based on the hydraulic trasmission of the pressure.
The fluid-filled system assures the temperature stability.
The phisical measure is transformed in a electrical measure by means of the strain-gauge technology.
MAIN FEATURES
• Pressure ranges from:
0-17 to 0-2000 bar / 0-250 to 0-30000 psi
•1/2-20UNF, M18x1.5 standard threads; other types avai-
lable on request
• Autozero function on board / external option
• Standard diaphragm is 15-5 PH stainless steel with
GTP+ coating
• 17-7 PH corrugated diaphragm with GTP+ coating for
ranges below 100 bar-1500 psi
GTP+ (advanced protection)
Coating with high resistance against corrosion, abrasion
and high temperature
AUTOZERO FUNCTION
All signal variations in the absence of pressure can be eliminated by using the Autozero function.
This function is activated by closing a magnetic contact
located on the transmitter housing.
The procedure is permitted only with pressure at zero.
TECHNICAL SPECIFICATIONS
Accuracy (1)
Resolution16 bit
Measurement range
Maximum overpressure
(without degrading performances)
Measurement principleExtensimetric
Power supply13...30Vdc
Maximum current absorption
Output signal Full Scale FSO20mA
Zero balance
(tollerance ± 0.25% FSO)
Response time (10...90% FSO)8ms
Output noise (RMS 10-400Hz)< 0.025% FSO
Calibration signal80% FSO
Power supply polarity reverse
protection
Compensed temperature range
housing
Operating temperature range housing
Storage temperature range housing-40...+125°C
Thermal drift in compesated range:
Zero / Calibration / Sensibility
Diaphragm maximum temperature400°C / 750°F
Zero drift due to change in process
temperature (zero)
Standard material in contact
with process medium
Thermocouple (model ME2)STD : type “J” (isolated junction)
Protection degree
(with 6-pole female connector)
FSO = Full scale output : (1) BFSL method (Best Fit Straight Line): includes combined
effects of Non-Linearity, Hysteresis and Repeatability.
H <±0.25%FSO (100...2000 bar)
M <±0.5%FSO (35...2000 bar)
0..17 to 0..2000bar
0..250 to 0..30000psi
2 x FS
1.5 x FS above 1000bar/15000psi
23mA
(40mA with relay optional)
4mA
YES
0...+85°C
-30...+85°C
< 0.02% FSO/°C
< 0.02 bar/°C
Diaphragm:
• 15-5PH with GTP+ coating
• 17-7 PH corrugated diaphragm
with GTP+ coating for ranges
<100bar (1500psi)
Stem: • 17-4 PH
IP65
MECHANICAL DIMENSIONS
ME0
D1
D2
D3
D4
D5
A
B
C
Ch
[Hex]
D1
D2
ME2
1/2 - 20UNF
ø7.8 -0.05
[ ø0.31” -0.002 ]
ø10.5 -0.025
[ ø0.41” -0.001 ]
ø10.67
[ ø0.42” ]
ø12.7
[ ø0.5” ]
5.56 -0.26
[ 0.22” -0.01 ]
11.2
[ 0.44” ]
15.74
[ 0.62” ]
16
[ 5/8” ]
M18x1.5
ø10 -0.05
[ ø0.394” -0.002 ]
ME1
D3
D4
D5
A
B
C
Ch
[Hex]
ø16 -0.08
[ ø0.63” -0.003 ]
ø16 -0.4
[ ø0.63” -0.016 ]
ø18
[ ø0.71” ]
6 -0.26
[ 0.24” -0.01 ]
14.8 -0.4
[ 0.58” -0.016 ]
19
[ 0.75” ]
19
[ 3/4” ]
ME3
NOTE : dimensions refer to rigid stem length option “4” (153 mm – 6”)
WARNING : For installation use a maximum tightening torque of 56 Nm (500 in-lb)
Below the conditions detected by the sensor self-diagnostics:
· Cut cable / device non connected / broken power supply, output <3.6mA
· Pin detachment, output >21mA
· Pressure above 200% of the span, output >21mA
· Voltage monitor in case of overvoltage/undervoltage/voltage variation in the electronics, output <3.6mA
· Program sequence error, output <3.6mA
· Overtemperature on the electronics, output <3.6mA
· Error on the primary element output or on the first amplification stage, output <3.6mA
OPTIONAL RELAY OUTPUT FOR EXCESS PRESSURE PROTECTION
Safety relay characteristics:
· Activation threshold to be defined in the order code
· Rated carry current: 1A
· Rated voltage: 24Vdc ± 20%
· Switch accuracy: 2 x sensor accuracy
· Hysteresis: 2% FSO
SUPPLYOUTPUTRELAY STATUS
OFF-OPEN
ON< X%fsCLOSED
ON> X%fsOPEN
ONoutput < 3,6mAOPEN
ONoutput > 21mAOPEN
NAMUR COMPLIANCE
The sensors are tested according to Namur NE21 recommendations.
The same compatibility is valid for the NE43 Namur recommendation
with the following sensor behaviour in case of breakdown:
· Cut cable: breakdown information as the signal is <3,6mA
· Device not connected: breakdown information as the signal is <3,6mA
· Broken power-supply: breakdown information as the signal is <3,6mA
or in case of performance problems:
· most common failures on primary sensors: the signal goes to>21mA
Note: in all the remaining situations, the output signal is always included between 3,6 and 21mA.
Recommendation: the error level set by the customer
(e.g. maximum pressure value) has to be inside the
nominal range.
AUTOZERO FUNCTION
LOAD DIAGRAM
The diagram shows the optimum ratio between load and power supply
for transmitters with 4…20mA output.
For correct function, use a combination of load resistance and voltage
that falls within the two lines in the graph above.
The Autozero function is activated through a
magnetic contact (external magnet supplied
with the sensor).
See the manual for a complete Autozero function explanation.
ELECTRICAL CONNECTIONS
EXTERNAL AUTOZERO
EXTERNAL AUTOZERO
CURRENT OUTPUT
CONTROLLER
POWER SUPPLY
7-pin
F
The cable shield is tied to connector via cable clamp
RELAY OUTPUT
OUTPUT
POWER SUPPLY
AUTOZERO
C
B
D-G
A-E
The cable shield is tied to connector via cable clamp
pressure range, 0.5% accuracy, 153 mm (6”) rigid rod, 457 mm (18”) flexible rod; Performance
Level=’c’.
Sensors are manufactured in compliance with:
H
Standard
0000
X 000 X00
Output Relay Version
(activation threshold):
X=no relay B=80%fs
A=70%fs C=90%fs
000= Special executions
EExternal Autozero (*)
-Magnetic Autozero
(*) as an alternative to the CAL
function
PPerformance Level=’c’
FLEXIBLE ROD LENGTH
(mm/inches)
Standard (ME0)
0none
Standard (ME1,ME2)
457mm 18”
D
E610mm 24”
F760mm 30”
Standard (ME3)
711mm 28”
L
Available on request
76mm 3”
A
B152mm 6”
C300mm 12”
G914mm 36”
H1067mm 42”
I1220mm 48”
J1372mm 54”
K1520mm 60”
RIGID ROD LENGTH
(mm/inches)
Standard (ME0, ME1, ME2)
153mm 6”
4
5318mm 12.5”
Standard (ME3)
0none
Available on request
38mm 1.5”
1
250mm 2”
376mm 3”
6350mm 14”
7400mm 16”
8456mm 18”
- EMC directive
- machinery directive
Product designed and available in compliance with Directive 2011/65/EU (RoHS II) only for large-scale stationary installation or
industrial tools, or for B-to-B laboratory equipments for R&D purposes
Electrical installation requirements and Conformity certificate are available on our web site: www.gefran.com