gefran GFW ADV, GFX4-IR Configuration Manual

Page 1
180963B_MSW_GFW_11-2012_ENG
ATTENTION!
This manual is an integral part of the product,
and must always be available to operators.
This manual must always accompany the pro-
duct, including if it is transferred to another user.
Installation and/or maintenance workers MUST read this manual and scrupulously follow all of the in­structions in it and in its attachments. GEFRAN will not be liable for damage to persons and/or property, or to the product itself, if the following terms and conditions are disregarded.
The Customer is obligated to respect trade secrets. Therefore, this manual and its attachments may not be tampered with, changed, reproduced, or transferred to third parties without GEFRAN’s authorization.
CONFIGURATION AND PROGRAMMING MANUAL
Software version: 2.0x
code: 80963B - 11-2012 - ENG
GFW adv
ADVANCED MODULAR POWER CONTROLLER
This document is the property of GEFRAN and may not be reproduced or transferred to third parties without authorization.
This document supplements the following manuals:
- Instructions and warnings for GFW
Page 2
2 80963B_MSW_GFW_11-2012_ENG
Page 3
380963B_MSW_GFW_11-2012_ENG
TABLE OF CONTENTS AND SUMMARIES
TABLE OF CONTENTS AND SUMMARIES .....................3
INTRODUCTION .................................................................4
FIELD OF USE ..............................................................4
CHARACTERISTICS OF PERSONNEL ........................4
STRUCTURE OF THIS MANUAL ...................................5
INSTRUMENT ARCHITECTURE ........................................6
SERIAL COMMUNICATION (MODBUS) ........................7
CONNECTION ................................................................8
INPUTS ..............................................................................9
ANALOG INPUT .............................................................9
MAIN INPUT ................................................................10
CURRENT VALUE ON LOAD ......................................14
VOLTAGE VALUE ON LOAD ........................................17
LINE VOLTAGE VALUE ................................................17
POWER ON LOAD ......................................................21
AUXILIARY ANALOG INPUTS (LIN/TC).......................23
DIGITAL INPUTS ..........................................................26
USING A FUNCTION ASSOCIATED WITH DIGITAL
INPUT AND VIA SERIAL ...............................................27
USING A FUNCTION OF DIGITAL INPUT 1
TO ENABLE AT SOFTWARE ON .................................28
ALARMS ...........................................................................29
GENERIC ALARMS AL1, AL2, AL3 e AL4 .................... 29
LBA ALARM (Loop Break Alarm) .................................34
HB ALARM (Heater Break Alarm) ................................35
SBR - ERR ALARMS
(probe in short or connection error) ..............................39
Power Fault ALARMS (SSR_SHORT, NO_VOLTAGE and NO_CURRENT) ...40
Overheat Alarm .............................................................41
SHORT CIRCUIT CURRENT ALARM ..........................41
FUSE OPEN ALARM .................................................... 41
OUTPUTS .........................................................................42
ALLOCATION OF REFERENCE SIGNALS .............42
ALLOCATION OF PHYSICAL OUTPUTS ................44
SETTINGS .........................................................................46
SETTING THE SETPOINT ...........................................46
SETPOINT CONTROL ..................................................47
CONTROLS ......................................................................49
PID HEAT/COOL CONTROL ........................................49
AUTOMATIC / MANUAL CONTROL .............................53
HOLD FUNCTION ........................................................53
MANUAL POWER CORRECTION ...............................53
MANUAL TUNING ........................................................54
AUTOTUNING ..............................................................54
SELFTUNING ...............................................................56
SOFTSTART .................................................................57
START MODE ...............................................................57
SOFTWARE SHUTDOWN ............................................58
OTHER FUNCTIONS ........................................................59
FAULT ACTION POWER ..............................................59
POWER ALARM ...........................................................59
SOFTSTART FOR PREHEATING ................................61
HEATING OUTPUT (Fast cycle) ...................................61
POWER CONTROL ..........................................................62
SSR CONTROL MODES ..............................................62
FEEDBACK MODALITY ...............................................64
HEURISTIC POWER CONTROL ..................................66
HETEROGENEOUS POWER CONTROL ....................67
VIRTUAL INSTRUMENT CONTROL ................................68
HW/SW INFORMATION ....................................................69
INSTRUMENT CONFIGURATION SHEET .......................73
KEYPAD USE ...................................................................92
Page 4
4 80963B_MSW_GFW_11-2012_ENG
INTRODUCTION
The modular power controller described in this manual and shown on the cover is a separate unit for the independent
control of a maximum of 3 zones. It offers high applicative exibility thanks to the extended congurability and programmability
of its parameters.
Instrument conguration and programming must be performed with a GFW-OP or a PC connected in USB/RS232/ RS485, with specic GF_eXpress application software.
Since it is impossible to foresee all of the installations and environments in which the instrument may be applied, adequate technical preparation and complete knowledge of the instrument’s potentials are necessary.
GEFRAN declines all liability if rules for correct
installation, conguration, and/or programming are disregarded, as well as all liability for systems upline and/or downline of the instrument.
FIELD OF USE
The modular power controller is the ideal solution for applications in heat treatment furnaces, in thermoformers, in
packaging and packing machines and, in general, in standard temperature control applications. Nevertheless, because it is highly programmable, the controller can also be used for other applications provided they are compatible with the instrument’s technical data.
Although the instrument’s exibility allows it to be used in a variety of applications, the eld of use must always conform to the limits specied in the technical data supplied.
GEFRAN declines all liability for damage of any type deriving from installations, congurations, or programmings that are inappropriate, imprudent, or not conforming to the technical data supplied.
Prohibited use
It is absolutely prohibited:
- to utilize the instrument or parts of it (including software) for any use not conforming to that specied in the technical docu­mentation supplied;
- to modify working parameters inaccessible to the operator, decrypt or transfer all or part of the software;
- to utilize the instrument in explosive atmospheres;
- to repair or convert the instrument using non-original replacement parts;
- to utilize the instrument or parts of it without having read and correctly understood the technical documentation supplied;
- to scrap or dispose of the instrument in normal dumps; components that are potentially harmful to the environment must be disposed of in conformity to the regulations of the country of installation.
CHARACTERISTICS OF PERSONNEL
All personnel operating, installing, or doing maintenance on the instrument must be expert, trained, aware and mature,
able to reliably and correctly interpret this manual. This manual CANNOT make up for cultural or intellectual insufciencies. Therefore, all personnel interacting with the instru­ment must:
- have adequate education, training, and skills;
- be completely aware of what he/she is doing;
- NOT act in an intentionally self-destructive manner. All personnel must always use proper methods, instruments, and protective devices to work under safe conditions.
It is forbidden to employ untrained personnel, per-
sons with disabilities, legally disqualied persons,
persons who are not sober, or persons who take
drugs.
Page 5
580963B_MSW_GFW_11-2012_ENG
STRUCTURE OF THIS MANUAL
This manual was originally written in ITALIAN. Therefore, in case of inconsistencies or doubts, request the original manual or explanations from GEFRAN.
The instructions in this manual do not replace the safety instructions and the technical data for installation, conguration and
programming applied directly to the product or the rules of common sense and safety regulations in effect in the country of installation.
For easier understanding of the controller’s basic functions and its full potentials, the conguration and programming parameters
are grouped according to function and are described in separate chapters. Each chapter has from 1 to 3 sections:
- the rst section presents a general description of the parameters described in detail in the following zones;
- the second section presents the parameters needed for the controller’s basic applications, which users and/or
installers can access clearly and easily, immediately nding the parameters necessary for quick use of the controller;
- the third section (ADVANCED SETTINGS ) presents parameters for advanced use of the controller: this section is addressed to users and/or installers who want to use the controller in special applications or in applications requiring the high performance offered by the instrument. Some sections may contain a functional diagram showing interaction among the parameters described;
- terms used on other pages of the manual (related or supplemental topics) are shown in underlined italics and listed in the index (linked to IT support). In each section, the programming parameters are shown as follows:
400*
21 - 29 - 143
tYP.
R/W
Type of probe, signal, enable, custom
linearization and main scale input
-999 ...999
Scale points
1000
Unless indicated otherwise, these parameters are in decimal format and represent 16 bit words.
Main Modbus address and additional addresses (if any). Any second / third Modbus addresses are alternatives to the main address. The presence of the asterisk near the main address indicates that the parameter is available for every zone; the lack indicates that the parameter is total to the device.
Mnemonic code (if any)
R read only (read) and/or W (write) attribute
Description
Supplemental data and/or information on the parameter
Setting limits
Default value
Supplemental data and/or information
Supplemental data and/or information
dP_S Format 0 xxxx 1 xxx.x 2 xx.xx (*)
Supplemental data and/or
information
68
bit
STAT E
DIGITAL INPUT 1
OFF = Digital input 1 off OFF = Digital input 1 on
Function
R/W
These parameters are represented in 1 bit format.
Page 6
6 80963B_MSW_GFW_11-2012_ENG
INSTRUMENT ARCHITECTURE
The modular power controller’s exibility permits replacement of previous-version such as GEFLEX (GFX), GFX4
and GFX4-IR instruments without changing the control software in use. Based on the chosen work mode (see MODBUS SERIAL COMMUNICATION), you can use the instrument in 2 different modes:
- GFX compatible mode: as if there were at most 3 separate instruments (recommended for retrotting projects and/ or replacement of damaged instruments);
- GFX4/GFW mode: as a single instrument with the same functions as at most 3 separate instruments, but with
possibility of interaction among the various parameters, inputs and outputs (recommended for new projects).
New shared parameters, are accessible for both modes and permit more advanced functions such as:
604
FLt.2
R/W
Digital filter for auxiliary input
0.0 ... 20.0 sec
0.1
In addition to having a CUSTOM group of parameters for dynamic addressing, GFX4/GFW mode lets you use a single communication network node instead of 3 nodes as in GFX compatible mode.
When programming, keep in mind that some of the
addresses (parameters) described in this manual
exist at most 3 times, specied by address node
(ID).
Inputs
ID01...
...ID03
Allocation of
outputs
Out1
Out2
Out3
Out5
Out6
Out7
Out8
Out9
Out10
GFX Compatible HARDWARE
SOFTWARE
Outputs
Inputs
Inputs
Inputs
Shared
parameters
ID03 Parameters
(**)
ID02 Parameters
(*)
ID01
Parameters
Inputs
ID01
Allocation
of outputs
Out1
Out2
Out3
Out5
Out6
Out7
Out8
Out9
Out10
HARDWARE GFX4/GFW
SOFTWARE
Outputs
Inputs
ID01
Allocation
of inputs
ID01
Parameters
------------------------
Custom parameters
Shared parameters
Serial line
Serial line
(*) if GFW_E1 module is present
(**) if GFW_E2 module is present
Page 7
780963B_MSW_GFW_11-2012_ENG
SERIAL COMMUNICATION (MODBUS)
There are two Modbus addressing modes for variables and conguration parameters:
- GFX compatible
- GFX4/GFW The modes are selected with dip-switch-7.
GFX-compatible mode (dip-switch-7 =ON)
This lets you uses supervision programs created for Geex modules.
Memory is organized in at most 3 groups:
- Zone 1 for the variables of the module GFW-M
- Zone 2 for the variables of the module GFW-E1
- Zone 3 for the variables of the module GFW-E2
In each zone, the variables and parameters have the same address as a Geex instrument; the value (Cod) set on
the rotary switches corresponds to that of Zone 1; the values in the other zones, if expansions are present, are sequential.
Examples: if the rotary switches have value 14, node 14 addresses Zone 1 (GFW-M), node 15 Zone 2 (GFW-E1), node 16 Zone 3 (GFW-E2). The power Ou.P for Zone 1 has address Cod 2, the Ou.P for Zone 2 has address Cod+1, 2, etc...
Parameter out.5, which denes the function of output OUT 5 on the GFW, has address Cod 611.
GFX4/GFW mode (dip-switch-7=OFF)
This lets you optimize the efciency of serial communication by integrating at most 3 zones in the GFW. Memory is organized in 4 groups: 3 already in GFX-compatible mode, plus one group dened as custom:
- Custom (additional memory map for dynamic addresses)
- Zone 1 for the variables of the module GFW-M
- Zone 2 for the variables of the module GFW-E1
- Zone 3 for the variables of the module GFW-E2
The custom group contains variables and parameters for a maximum of 120 words. The meaning of these words can be changed. There is a single value (Cod) set on the rotary switches; i.e., one for each GFX4/GFW instrument. To access the data in each zone, simply add an offset to the address (+1024 for Zone 1, +2048 for Zone 2, +4096 for Zone 3).
Words in the custom group have addresses 0,...,119. The variables and parameters are dened by default. At ad­dresses 200,...,319 we have words containing the value of the address of the corresponding variables or parameters. These addresses can be changed by the user, offering the ability to read/write data with multi-word messages structured according to various supervision requirements.
Protection of Maps 1-2 You have to write the value 99 on addresses 600
and 601 to enable change of the custom group
(addresses 200... 319). This value is reset at each switch-on.
Examples: you can access the Ou.P variable in Zone 1 with address Cod, 1+1024 or address Cod, 11 custom variable 12 (address Cod, 211 has value 2+1024); you can access the Ou.P variable in Zone 2 with address Cod, 2+ 2048 or address Cod, 40 custom variable 41 (address Cod, 240 has value 2+2048);
if you want to read the 3 powers in sequence at the rst 3 addresses, set Cod, 200 = 1026, Cod.201 = 2050, Cod,202 = 4098.
Page 8
8 80963B_MSW_GFW_11-2012_ENG
CONNECTION
Each GFW has an optically isolated serial port RS485 (PORT 1) with standard Modbus protocol via connectors J8 and J9 (type RJ10).
You can insert a serial interface (PORT 2). There are various models based on the eld bus required: Modbus, Pro­bus DP, CANopen, DeviceNet and Ethernet.
This communication port (PORT 2) has the same Cod address as PORT 1. The parameters for PORT 2 are bAu.2 (select baud-rate) and Par.2 (select parity). The Cod parameter (read only) shows the value of the node address, settable from 00 to 99 with the 2 rotary switches; the hexadecimal settings are reserved. A parameter can be read or written from both communication ports (PORT 1 and PORT 2).
Changing the
bAu (select baud-rate) and/or PAr (select
parity) parameters may cause communication failure.
To set the bAu and PAr parameters, you have to run the Autobaud procedure described in the “Instruction and warnings” manual.
Installation of the “MODBUS” serial network
A network typically has a Master that “manages” communication by means of “commands” and Slaves that interpret these commands. GFW are considered Slaves to the network master, which is usually a supervision terminal or a PLC.
They are positively identied by means of a node address (ID) set on the rotary switches (tens + ones).
GFW have a ModBus serial (Serial 1) and optional Fieldbus (Serial 2) serial (see order code) with one of the following
protocols: ModBus, Probus, CANopen, DeviceNet, Ethernet, EtherCAT and EthernetIP.
The following procedures are indispensable for the Modbus protocol. For the remaining protocols, see the specific Geflex Profibus, Geflex CANopen, Geflex DeviceNet, Geflex Ethernet, GFX4-EtherCAT and GFX4-ETH1 manuals. GFW modules have the following default settings:
- node address = 0 (0 + 0)
- speed Serial 1 = 19200 bit/s
- parity Serial 1 = none
- speed Serial 2 = 19200 bit/s
- parity Serial 2 = none You can install a maximum of 99 GFW modules in a serial network, with node address selectable from “01” to “99” in standard
mode, or create a mixed GFW / GFX4 network in GFX compatible mode in which each GFW identies 3 zones with sequential
node address starting from the code set on the rotary switches. In short, the valid rotary switch settings (tens + ones) are:
- (0 +0) = Autobaud Serial 1
- (B +0) = Autobaud Serial 2
46
(od
R
Device identification code
1 ... 99
45
baV
R/W
Select Baudrate - Serial 1
4
0 1200 bit/s 1 2400 bit/s 2 4800 bit/s 3 9600 bit/s 4 19200 bit/s 5 38400 bit/s 6 57600 bit/s 7 115200 bit/s
Baudrate table
47
par
R/W
Select parity - Serial 1
0
0 No parity 1 Odd 2 Even
Parity table
626
bav.2
R/W
Select Baudrate - Serial 2
4
627
par.2
R/W
Select parity - Serial 2
0
Page 9
980963B_MSW_GFW_11-2012_ENG
INPUTS
ANALOG INPUT
The modular power controller has a analog input with the functionality power retransmission.
FUNCTIONAL DIAGRAM
Probe type
tP.A
Scale limits HS.A, LS.A
Low pass lter
FLt.A
see Control
analog input value
(In.A)
Input signal
Probe type
Scale limits
Offset adjustment
Input lter
Read state
573
tP.A
R/W
analog input
1
Table of analog input
0 Disable 1 0 ... 10V 2 0 ... 5V/Potentiometer 3 0 ... 20mA 4 4 ... 20mA
574
LS.A
R/W
Minimum scale limit
analog input
-100,0...200,0
0,0
577
oFS.A
R/W
Offset correction for analog input -99,9...99,9
0,0
576
Flt.A
R/W
Low pass digital filter
analog input
0,0...20,0 sec
0,1
572
In.A
R
Value of the ingegneristico reading
analog input
575
kS.A
R/W
Maximum scale limit
analog input
LS.A...200,0
100,0
ADVANCED SETTINGS
Page 10
10 80963B_MSW_GFW_11-2012_ENG
MAIN INPUT PID
The modular power controller has one main input (IN1) to control, to which you can connect temperature sensors (thermocouples and RTD), linear sensors or custom sensors to acquire process variable (PV) values. These type of input is optional.
To congure, you always have to dene the type of probe or sensor (tYP), the maximum and minimum scale limit
(Hi.S – Lo.S) for the process variable value, and the position of the decimal point (dP.S).
If the sensor is a thermocouple or resistance thermometer, the minimum and maximum limits can be dened on the specic scale of the sensor. These limits dene the width of the proportional control band and the range of values settable for the
setpoint and alarm setpoints.
There is a parameter to correct the offset of the input signal (oF.S): the set value is algebraically added to the read of the process variable.
You can read the state of the main input (Err) in which an input error is reported: when the process variable goes beyond the upper or lower scale limit, it assumes the value of the limit and the corresponding state reports the error condition: Lo = process variable < minimum scale limit Hi = process variable > maximum scale limit Err = Pt100 in short circuit and input value below minimum limit,
4...20mA transmitter interrupted or not powered Sbr = Tc probe interrupted or input value above maximum limit
If noise on the main input causes instability of the acquired value, you can reduce its effect by setting a low pass
digital lter (Flt). The default setting of 0.1sec is usually sufcient.
You can also use a digital lter (Fld) to increase the apparent stability of the process variable PV; the lter introduces a hysteresis on its value: if the input variation remains within the set value, the DPV value is considered unchanged.
Page 11
1180963B_MSW_GFW_11-2012_ENG
Maximum error of non linearity for thermocouples (Tc), resistance thermometer (PT100)
Type Type of probe Scale Without dec. point With dec. point 0 TC J °C 0/1000 0.0/999.9 1 TC J °F 32/1832 32.0/999.9 2 TC K °C 0/1300 0.0/999.9 3 TC K °F 32/2372 32.0/999.9 4 TC R °C 0/1750 0.0/999.9 5 TC R °F 32/3182 32.0/999.9 6 TC S °C 0/1750 0.0/999.9 7 TC S °F 32/3182 32.0/999.9 8 TC T °C -200/400 -199.9/400.0 9 TC T °F -328/752 -199.9/752.0 28 TC custom custom custom 29 TC custom custom custom
Tc type: J, K error < 0.2% f.s. S, R range 0...1750°C: error < 0.2% f.s. (t > 300°C) For other ranges: error < 0.5% f.s. T error < 0.2% f.s. (t > -150°C)
And inserting a custom linearization E, N, L error <0.2% f.s. B range 44...1800°C; error < 0.5% f.s. (t > 300°C) range 44.0...999.9; error f.s.(t>300°C) U range -200...400; error < 0.2% f.s. (for t > -100°C) For other ranges; error <0.5% f.s. G error < 0.2% f.s. (t > 300°C) D error < 0.2% f.s. (t > 200°C) C range 0...2300; error < 0.2% f.s. For other ranges; error < 0.5% f.s.
JPT100 and PT100 error < 0.2% f.s.
The error is calculated as deviation from theoretical value with % reference to the full-scale value expressed in degrees Celsius (°C).
TC SENSOR
Type Type of probe Scale Without dec. point With dec. point 30 PT100 °C -200/850 -199.9/850.0 31 PT100 °F -328/1562 -199.9/999.9 32 JPT100 °C -200/600 -199.9/600.0 33 JPT100 °F -328/1112 -199.9/999.9
SENSOR: RTD 3-wires
Type Type of probe Scale Without dec. point With dec. point 34 0...60 mV Linear -1999/9999 -199.9/999.9 35 0...60 mV Linear Custom linearization Custom linearization 36 12...60 mV Linear -1999/9999 -199.9/999.9 37 12...60 mV Linear Custom linearization Custom linearization
SENSOR: 60mV voltage
Type Type of probe Scale Without dec. point With dec. point 38 0...20 mA Linear -1999/9999 -199.9/999.9 39 0...20 mA Linear Custom linearization Custom linearization 40 4...20 mA Linear -1999/9999 -199.9/999.9 41 4...20 mA Linear Custom linearization Custom linearization
SENSOR: 20mA current
Type Type of probe Scale Without dec. point With dec. point 42 0...1 V linear -1999/9999 -199.9/999.9 43 0...1 V linear Custom linearization Custom linearization 44 200 mv..1 V linear -1999/9999 -199.9/999.9 45 200 mv..1 V linear Custom linearization Custom linearization
SENSOR: 1V voltage
Type Type of probe Scale Without dec. point With dec. point 46 Cust. 20mA - -1999/9999 -199.9/999.9 47 Cust. 20mA - Custom linearization Custom linearization 48 Cust. 60mV - -1999/9999 -199.9/999.9 49 Cust. 60mV - Custom linearization Custom linearization 50 PT100-JPT - custom custom
SENSOR: Custom
400
tYP.
R/W
Probe type, signal, enable, custom
linearization and main input scale
0
Probes and sensors
Table of probes and sensors
99 Input off
403
dP.S
R/W Decimal point position for input scale
0
Format 0 xxxx 1 xxx.x 2 xx.xx (*) 3 x.xxx (*) (*) Not available for TC, RTD probes
Species the number of decimal gures used to represent the input signal value: for
example, 875.4 (°C) with dP.S = 1.
Decimal point table
Scale limits
401
Lo.S
R/W Minimum scale limit of main input
0
min...max scale
of input selected
in tyP
Engineering value associated to minimum level of the signal generated by the sensor connected to the input: for example 0 (°C) with type K thermocouple.
402
xi.S
R/W Maximum scale limit of main input
1000
min...max scale
of input selected
in tyP
Engineering value associated to maximum level of the signal generated by the sensor connected to the input: for example 1300 (°C) with type K thermocouple.
Setting the offset
519
23
ofs.
R/W Offset correction for main input
-999...999
scale points
0
Lets you set a value in scale points that is algebraically added to the value measured by the input sensor.
Page 12
12 80963B_MSW_GFW_11-2012_ENG
0
470
P. V.
R
Read of engineering value of
process variable (PV)
Input lters
24
flt
R/W
Low pass digital filter
on input signal
0.0 .... 20.0 sec
0,1
Sets a low pass digital lter on the main input, running the average value read in the
specied time interval. If = 0 exclude the average lter on the sampled values.
179
fld
R/W
Digital filter on oscillations
of input signal
0 ... 9.9
scale points
0,5
Introduces a hysteresis zone on the input signal value within which the signal is considered unchanged, thereby increasing its apparent stability.
85
Err
R
Self-diagnostic error code
of main input
0 No Error 1 Lo (process variable value is < Lo.S) 2 Hi (process variable value is > di Hi.S) 3 ERR [third wire interrupted for PT100 or input values below minimum limits (ex.: for CT with connection error)] 4 SBR (probe interrupted or input values beyond maximum limits)
Error code table
ADVANCED SETTINGS
Linearization of input signal
The modular power controller lets you set a custom linearization of the signal acquired by the main input for signals coming from sensors and for signals coming from custom thermocouples. Linearization is performed with 33 values (S00 ... S32: 32 segments). S33, S34, S35 are an additional 3 values to be inserted in case of linearization with custom CT.
- Signals from sensors
For signals coming from sensors, linearization is done by dividing the input scale into 32 zones of equal dV amplitude, whe­re:
dV = (full-scale value – start of scale value) / 32
Point 0 (origin) corresponds to the engineering value attributed to the minimum value of the input signal. Subsequent points correspond to the engineering values attributed to input values equal to:
Input value (k) = Minimum input value + k * dV
where k is the order number of the linearization point
For custom linearization (tYP = 28 or 29):
- LO is signaled with input values below Lo.S or at minimum calibration value.
- HI is signaled with input values above Lo.S or at maximum calibration value.
Read state
Scale of the visualized
engineering value
Example of linearization:
S.32
S.24
S.12
S.00
...
...
S.05
...
0 9.375mV = 5 * (f.s./32) 22.5 mV 45 mV f.s. = 60 mV
Ex.: Input 0...60mV
349
DPV
R
Read of engineering value of
process variable (PV) filtered by FLd
Page 13
1380963B_MSW_GFW_11-2012_ENG
- Signals coming from custom thermocouples
An alternate linearization is available only for sensors consisting of custom thermocouples, created by dening engineering
values at three measurement scale points settable with the following parameters:
295
S.35
R/W
Engineering value attributed to input
signal corresponding to 50°C.
mV at 50° C
(- 1,999 ... 9,999)
294
S.34
R/W
Engineering value attributed to maxi-
mum value of the input scale.
mV full scale
((S.33+1) ... 99,99)
293
S.33
R/W
Engineering value attributed to minimum
value of the input scale.
mV start of scale
(- 19,99 ... 99,99)
86
S.00
R/W
Engineering value attributed to Point 0
(minimum value of input scale)
(- 1999 ... 9999)
118
S.32
R/W
Engineering value attributed to
Point 32
(maximum value of input scale)
(- 1999 ... 9999)
87
S.01
R/W
Engineering value attributed to
Point 1
(- 1999 ... 9999)
. . . . .
intermediate values
For correct signaling of error state (Lo, Hi), the value set in S.00 must coincide with limit Lo.S and the value set in S.32 with limit Hi.S.
The engineering values calculated in this way by the user can be set by means of the following parameters.
FUNCTIONAL DIAGRAM
N.B. The decimal point does not change the
contents of the PV, but only permits its correct interpretation.
Ex.: if dP.S = 1 and PV = 300, the engineering value
in °C is 30.0.
Input signal
Probe type (tYP).
Linearization of signal
(S00...S35)
Scale limits and
decimal point (Hi.S,
Lo.S, dP.S). Offset
(OfS)
Low pass
lter
(FIt)
Process variable (PV)
Select PV
for zone
See control
Digital lter
(FId)
Variable DPV
Page 14
14 80963B_MSW_GFW_11-2012_ENG
CURRENT VALUE IN LOAD
The RMS current value is read in variable Ld.A of each zone.
If zone 1 has a 3-phase load, variable Ld.At contains the average value of the three RMS currents. The Ld.A of the rst three
zones contain the RMS current value on lines L1, L2 and L3, respectively.. Accuracy is better than 1% in start modes ZC, BF and HSC. Accuracy is better than 3% in PA mode with conduction angle >90°, and better than 10% for lower conduction angles. The circulating current in the load is acquired with a 0.25ms sampling time.
In addition, there are the following parameters for a zone with single-phase load: I.tA1 instantaneous ammeter value
I.AF1 ltered ammeter value (see Ft.tA)
I1on current with active control o.tA1 ammeter input offset correction
Ft.tA ammeter input digital lter
There are also the following parameters if zone 1 has a three-phase load: I.tA1, I.tA2 and I.tA3 instantaneous ammeter value on line L1, L2 and L3
I.AF1, I.AF2 and I.AF3 ltered ammeter value (see Ft.tA) on line L1, L2 and L3
I1on, I2on and I3on current with active control o.tA1, o.tA2 and o.tA3 ammeter input offset correction on line L1, L2 and L3
Ft.tA ammeter input digital lter
If diagnostics detects a fault condition on the load, the red ER LED will ash in synch with yellow LED O1 or O2 or O3 for the
zone in question.
The condition POWER FAULT in OR with HB alarm can be assigned to an alarm or identied in the state of a bit in variables
STATUS, STATUS1, STATUS2 and STATUS3. In STATUS3 you can identify the condition that activated the POWER_FAULT alarm.
POWER_FAULT diagnostics is congurable with parameter hd.2, with which even just a part may be enabled
SSR SHORT SSR module in short circuit NO VOLTAGE power failure or interrupted fuse NO CURRENT due to SSR module open or fuse or load interrupted
For alarm HB (load partially interrupted), refer to the specic section of this manual.
The default value of the maximum limit or ammeter full-scale depends on the model:
MODEL H.tA
40A 80,0
60A 120,0 100A 200,0 150A 300,0 200A 400,0 250A 500,0
Page 15
1580963B_MSW_GFW_11-2012_ENG
Setting the offset
Read state
220
o.tA1
R/W
Offset correction CT input
(phase 1)
-99.9 ...99.9 scale points
415
o.tA2
R/W
Offset correction CT input
(phase 2)
-99.9 ...99.9 scale points
With 3-phase load
416
o.tA3
R/W
Offset correction CT input
(phase 3)
-99.9 ...99.9 scale points
With 3-phase load
Input lter
ADVANCED SETTINGS
219*
FT.TA
R/W
CT input digital filter
0.0 ... 20.0 sec
Sets a low pass lter on the CT auxiliary input, running the average of values read in the specied time interval. If = 0 , excludes the average lter on sampled values.
491
495
I.ta3
R
Instantaneous CT ammeter input value
(phase 3)
With 3-phase load
490
494
I.ta2
R
Instantaneous CT ammeter input value
(phase 2)
With 3-phase load
With 3-phase load
With 3-phase load
227*
473 - 139 - 756
I.ta1
R
Instantaneous CT ammeter input value
(phase 1)
499
I.3oN
R
CT filtered ammeter input value with
output activated (phase 3)
498
I.2oN
R
CT filtered ammeter input value with
output activated (phase 2)
468*
I.1oN
R
CT filtered ammeter input value with
output activated (phase 1)
754
ld.a.t
R
Current RMS on 3-phase load
753*
ld.a
R
Current RMS on load
716*
cos.f
R
Power factor in hundredths
709*
I.taP
R
Peak ammeter input during phase
softstart ramp
Scale limits
748
L.ta3
R
Minimum limit of CT ammeter
input scale (phase 3)
With 3-phase load
414
k.ta3
R
Maximum limit of CT ammeter
input scale (phase 3)
With 3-phase load
747
L.ta2
R
Minimum limit of CT ammeter
input scale (phase 2)
With 3-phase load
413
k.ta2
R
Maximum limit of CT ammeter
input scale (phase 2)
With 3-phase load
746*
L.ta1
R
Minimum limit of CT ammeter
input scale (phase1)
405*
k.ta1
R
Maximum limit of CT ammeter
input scale (phase 1)
0,0
zone 1
0,0
zone 2
0,0
zone 3
0,1
zone 1
0,1
zone 2
0,1
zone 3
Page 16
16 80963B_MSW_GFW_11-2012_ENG
FUNCTIONAL DIAGRAM
Monophase load
FUNCTIONAL DIAGRAM
Threephase load
zone 1
zone 2
zone 3
media
Variable
Ld.A.t (*)
(Instantaneous current)
Variable
I.tA1
Variable
I.tAP
(Peak current)
CT1
auxiliary input
Offset scale
limits
(o.tA1)
I.tA1
value
SCR ON
Low pass
lter
(Ft.tA)
(ON current)
Variable
I.1ON
Function
(Ou.P)
(Load RMS current)
Variable
Ld.A
(Instantaneous current)
Variable
I.tA1
Variable
I.tAP
(Peak current)
CT2
auxiliary input
Offset scale
limits
(o.tA1)
I.tA1
value
SCR ON
Low pass
lter
(Ft.tA)
(ON current)
Variable
I.1ON
Function
(Ou.P)
(Load RMS current)
Variable
Ld.A
(Instantaneous current)
Variable
I.tA1
Variable
I.tAP
(Peak current)
CT3
auxiliary input
Offset scale
limits
(o.tA1)
I.tA1
value
SCR ON
Low pass
lter
(Ft.tA)
(ON current)
Variable
I.1ON
Function
(Ou.P)
(Load RMS current)
Variable
Ld.A
(Instantaneous current)
Variable
I.tA1
Variable
I.tAP
(Peak current)
CT1
auxiliary input
Offset scale
limits
(o.tA1)
I.tA1
value
SCR ON
Low pass
lter
(Ft.tA)
(ON current)
Variable
I.1ON
Function
(Ou.P)
(Load RMS current)
Variable
Ld.A
Management:
- HB Alarm
- No Current Alarm
- Feedback I
- Irms limitation
(*) with BI-PHASE command the Ld.A value of zone 3 is gained like average of the Ld.A values of zones 1 and 2
Page 17
1780963B_MSW_GFW_11-2012_ENG
VOLTAGE VALUE ON LOAD
RMS voltage is read in variable Ld.V of each zone. If zone 1 has a 3-phase load, variable Ld.V.t in the rst zone
contains the average RMS value of voltages on three load L1, L2 and L3. Voltage on the load is acquired with sampling on each cycle, 20ms at 50Hz (16.6ms at 60Hz). Accuracy is better than 1%. If the option VLOAD is not present, the Load RMS voltage value is calculated from the line voltage and from the output power values.
752
Ld.U.t
R
Voltage on 3-phase load (*)
751*
Ld.U
R
Voltage on load
if the option VLOAD is present there are available the following parameters:
Read state
Scale limit
Setting the offset
444*
o.t L
R/W
Offset correction for
TV_LOAD input
-99.9 ...99.9 scale points
443*
k.t L
R
Maximum limit of TV_LOAD voltmeter
input scale
439*
L.t L
R
Minimum limit of TV_LOAD voltmeter
input scale
0,0
zone 3
0,0
zona 2
0,0
zona 1
ADVANCED SETTINGS
Input lter
442*
Ft.t L
R/W
Digital filter for voltmeter transformer
TV_LOAD input
0,0 ..20,0 sec
0,1
zone 3
0,1
zona 2
0,1
zona 1
FUNCTIONAL DIAGRAM
Single-Phase Load without VLOAD option
RMS
Variabe Ld.V
Voltmeter input
phase 1
I.VF1
Control value
output
Ou.P
Single-Phase Load with VLOAD option
Offset
scale limits
(o.tVL)
Filter
low pass
(Ft.tVL)
Variable Ld.V
Voltmeter input
on the load
phase
Page 18
18 80963B_MSW_GFW_11-2012_ENG
FUNCTIONAL DIAGRAM
Three-Phase Load without VLOAD option
RMS
Variable Ld.V fase 1
Voltmeter input
phase 1
I.VF1
control value
output Ov.P
RMS
Voltmeter input
phase 2
I.VF2
Variable Ld.V fase 2
RMS
Voltmeter input
phase 3
I.VF3
Variable Ld.V fase 3
media
Variable Ld.Vt (*)
Three-Phase Load with VLOAD option
Scale limits,
Offset
(o.tVL zone 1)
Variable Ld.V fase 1
Voltmeter input
on the load
phase 1
Voltmeter input
on the load
phase 2
Variable Ld.V fase 2
Voltmeter input
on the load
phase 3
Variable Ld.V fase 3
Scale limits,
Offset
(o.tVL zone 2)
Scale limits,
Offset
(o.tVL zone 3)
Filter
low pass
(Ft.tVL zone 1)
Filter
low pass
(Ft.tVL zone 2)
Filter
low pass
(Ft.tVL zone 3)
(*) with Dual-Phase command the zone 3 Ld.V value is calculated
as an average of the zone 1 and zone 2 Ld.V values
media
Variable Ld.Vt (*)
LINE VOLTAGE VALUE
There are the following parameters if zone 1 has a single-phase load: I.tV1 instantaneous voltmeter value of line
I.VF1 ltered voltmeter value
o.tV1 voltmeter input offset correction
Ft.tV voltmeter input digital lter
There are the following parameters if zone 1 has a 3-phase load: I.tV1, I.tV2 and I.tV3, the instantaneous voltmeter value on line L1, L2 and L3, respectively. RMS voltage values refer to voltage between 1/L1 and 3/L2 terminals.
I.VF1, I.VF2 and I.VF3 ltered voltmeter value on line L1, L2 and L3
o.tV1, o.tV2 and o.tV3 voltmeter input offset correction on line L1, L2 and L3. Each phase has a voltage presence check that shuts off the module in case of incorrect values. 3-phase loads have an imbalance diagnostic, with consequent shut-down of the load and signal via LEDs.
A “voltage status” parameter contains information on the status of line voltage, including mains frequency identied 50/60Hz.
3-phase loads have diagnostics for correct phase connection, lack of a voltage, or imbalance of the three line voltages.
Page 19
1980963B_MSW_GFW_11-2012_ENG
420
o.tU3
R/W
Offset correction for TV input
(phase 3)
-99.9 ...99.9 Scale points
0,0
zone 3
With 3-phase load
419
o.tU2
R/W
Offset correction for TV input
(phase 2)
-99.9 ...99.9 Scale points
0,0
zone 2
With 3-phase load
Setting the offset
493
1.tU3
R
Value of voltmeter input (phase 3)
With 3-phase load
492
1.tU2
R
Value of voltmeter input (phase 2)
With 3-phase load
232*
485
1.tU1
R
Value of voltmeter input (phase 1)
411*
o.tU1
R/W
Offset correction for TV input
(phase 1)
-99.9 ...99.9 Scale points
0,0
zone 1
Read state
322*
1.UF1
R
Value filtered of voltmeter input
(phase 1)
496
1.UF2
R
Value filtered of voltmeter input
(phase 2)
With 3-phase load
497
1.UF3
R
Value filtered of voltmeter input
(phase 3)
With 3-phase load
315*
FREq
R
Voltage frequency in tenths of Hz
702
R
Voltage Stutus
bit 0 frequency_warning 1 10% umbalanced_line_warning 2 20% umbalanced_line_warning 3 30% umbalanced_line_warning 4 rotation 123_error 5 triphase_missing_line_error 6 60Hz
Table Voltage Status
Scale limits
455
L.t 3
R
Minimum limit of TV voltmeter
input scale (phase 3)
With 3-phase load
418
k.t 3
R
Maximum limit of TV voltmeter
input scale (phase 3)
With 3-phase load
454
L.t 2
R
Minimum limit of TV voltmeter
input scale (phase 2)
With 3-phase load
417
k.t 2
R
Maximum limit of TV voltmeter
input scale (phase 2)
With 3-phase load
453*
L.t 1
R
Minimum limit of TV voltmeter
input scale (phase1)
410*
k.t 1
R
Maximum limit of TV voltmeter
input scale (phase 1)
0,0
0,0
Page 20
20 80963B_MSW_GFW_11-2012_ENG
Input lter
ADVANCED SETTINGS
412*
FT.TU
R/W
Digital filter for voltmeter transformer
TV input
0.0 ... 20.0 sec.
Sets a low pass lter on the auxiliary TV input, running the average of values read in the specied time interval. If = 0 , excludes the average lter on sampled values.
FUNCTIONAL DIAGRAM
Single-phase load
Scale limits,
Offset
(o.tV1)
Filter
low pass
(Ft.tV)
Variable I.VF1
see generic
alarms
Voltmeter
input
phase1
FUNCTIONAL DIAGRAM
3-phase load
Scale limits,
Offset
(o.tV1)
Filter
low pass
(Ft.tV)
Variable I.VF1
Voltmeter
input
phase1
Variable I.tV1
Scale limits,
Offset
(o.tV2)
Filter
low pass
(Ft.tV)
Variable I.VF 2
Voltmeter
input
phase2
Variable I.tV2
Scale limits,
Offset
(o.tV3)
Filter
low pass
(Ft.tV)
Variable I.VF 3
Voltmeter
input
phase3
Variable I.tV3
Variable I.tV1
2,0
zone 3
2,0
zone 2
2,0
zone 1
Page 21
2180963B_MSW_GFW_11-2012_ENG
POWER ON LOAD
Power on the load in each zone is read in variable Ld.P and the corresponding energy value in variables Ld.E1 and Ld.E2.
These energy values show the value accumulated since the rst power on or since the last reset (commands at bits 114 and
115); non-volatile memory is updated at power off. Load impedance in each zone is read in variable Ld.I. If zone 1 has a 3-phase load, variable Ld.P.t shows power and Ld.I.t total impedance, the corresponding energy value in va­riables Ld.E1.t and Ld.E2.t.
Note that for loads such as IR lamps, impedance can vary greatly based on the power transferred to the load.
FUNCTIONAL DIAGRAM
Single-phase load
X CoS.F
Variable Ld.P
RMS voltage
value
on load (Ld.V)
active power [kW]
RMS current
value
on load (Ld.A)
X
Ld.V/Ld.A
Variable Ld.I
impedance [ohm]
by time
Variables Ld.E1 and Ld.E2
energy [kwh
719*
Ld.P
R
Power on load
749*
Ld.I
R
Impedance on load
720
Ld.P.t
R
Power on load 3-phase
750
Ld.I.t
R
Impedance onload 3-phase
531*
Ld.E1
R
Energy on load Data in DWORD (32 bit) format
541
Ld.E1.t
R
Energy on 3-phase load Data in DWORD (32 bit) format
510*
Ld.E2
R
Energy on load Data in DWORD (32 bit) format
541
Ld.E2.t
R
Energy on 3-phase load Data in DWORD (32 bit) format
114*
bit
Azzeramento
Ld.E1
R/W
OFF = ­ON = Reset Ld.E1
115*
bit
Azzeramento
Ld.E2
R/W
OFF = ­ON = Reset Ld.E2
Page 22
22 80963B_MSW_GFW_11-2012_ENG
FUNCTIONAL DIAGRAM
3-phase load
Ld.V phase 1
Ld.V phfase 2
Ld.V phase 3
media
Ld.A phase 1
Ld.A phase 2
Ld.A phase 3
media
Ld.V.t
Ld.A.t
Ld.V.t/Ld.A.t
Ld.I.t
impedance [ohm]
(*) with BI-PHASE command the Ld.A value of zone 3 is gained like average of the Ld.A values of zones 1 and 2
Variable Ld.P phase 1
phase1
phase2
phase3
active power [kW]
Variable Ld.P phase 2 active power [kW]
Variable Ld.P phase 3 active power [kW]
+
Ld.P.t (*)
for time
Variable Ld.E1 and Ld.E2 phase 1
energy [kWh]
for time
Variable Ld.E1 and Ld.E2 phase 2
energy [kWh]
for time
Variable Ld.E1 and Ld.E2 phase 3
energy [kWh]
+
Ld.E1.t
e
Ld.E2.t
Page 23
2380963B_MSW_GFW_11-2012_ENG
AUXILIARY ANALOG INPUTS (LIN/TC)
The GFW has 4 inputs defined as auxiliary (IN2 for zone 1, IN3 for zone 2, IN4 for zone 3, IN5 for zone 4) to which TC or linear temperature sensors can be connected. The presence of these inputs is optional
Input values are available in variables In.2/In.3/In.4/In.5 and can be read or used to activate assigned alarm signals.
When an auxiliary input is present, you have to dene the following parameters:
- sensor type (AI.2, AI.3, AI.4, AI.5);
- its function (tP.2); (only for IN2 input)
- decimal point position (dP.2, HS.3 – LS.3, HS.4 – LS.4, HS.5 – LS.5);
- scale limits (HS.2 – LS.2);
- offset correction value (oFS.2, oFS.3, oFS.4, oFS.5).
If the sensor is a thermocouple, the minimum and maximum limits can be dened in the specic scale of the sensor
used. The range of values settable for alarm setpoints depends on these limits.
There is also a digital lter (Flt.2, Flt.3, Flt.4, Flt.5,) that can be used to reduce noise on the input signal.
194
AI.2
R/W
Select type of auxiliary sensor input 2
0
Type Type of probe Without dec. point With dec. point or sensor
0 TC J °C 0/1000 0.0/999.9 1 TC J °F 32/1832 32.0/999.9 2 TC K °C 0/1300 0.0/999.9 3 TC K °F 32/2372 32.0/999.9 4 TC R °C 0/1750 0.0/999.9 5 TC R °F 32/3182 32.0/999.9 6 TC S °C 0/1750 0.0/999.9 7 TC S ° F 32/3182 32.0/999.9 8 TC T °C -200/400 -199.9/400.0 9 TC T °F -328/752 -199.9/752.0 34 0...60 mV -1999/9999 -199.9/999.9 35 0...60 mV Custom linearization Custom linearization 36 12...60 mV -1999/9999 -199.9/999.9 37 12...60 mV Custom linearization Custom linearization 99 Input off
Auxiliary inputs sensors table
181
tp.2
R/W
Definition of auxiliary analog input
function
tP.2 Auxiliary LIMITS FOR SETTING the LS.2 and HS.2 input function min max
0 None -1999 9999 1 Remote setpoint Absolute Lo.S, Absolute Hi.S, deviation -999 deviation +999 2 Manual analog remote -100.0% +100.0% 3 Reset analog power -100.0% +100.0% 8 analogic remote manual from main input 16 remote manual from analogic input 32 remote manual from PWM input
0
Table of auxiliary input functions
(*)
(*)
(**)
(*) see: Settings – Control Setpoint (**) see: Controls –PID Parameters
677
dP.2
R/W
Decimal point position for the auxiliary
input scale 2
Format 0 xxxx 1 xxx.x 2 xx.xx (*) 3 x.xxx (*) (*) not available for TC probes
Decimal point table
0
Species the number of decimal gures used to represent the input signal value: for
example, 875.4 (°C) with dP.S: = 1
553
AI.3
R/W
Select type of auxiliary sensor input 3
554
AI.4
R/W
Select type of auxiliary sensor input 4
555
AI.5
R/W
Select type of auxiliary sensor input 5
0
0
0
568
dP.3
R/W
Decimal point position for the auxiliary
input scale 3
569
dP.4
R/W
Decimal point position for the auxiliary
input scale 4
570
dP.5
R/W
Decimal point position for the auxiliary
input scale 5
0
0
0
(*)
(*)
(*)
Page 24
24 80963B_MSW_GFW_11-2012_ENG
602
In.2
R
Value of auxiliary input 2
606
Er.2
R
Error code for self-diagnosis
of auxiliary input 2
0 No error 1 Lo (value of process variable is < LS.x) 2 Hi (value of process variable is > HS.x) 3 ERR [third wire interrupted for PT100 or input values below minimum limits (ex.: for TC with connection error)] 4 SBR (probe interrupted or input values beyond maximum limits)
Error code table
Read state
603
XS.2
R/W
Maximum limit of auxiliary input scale 2
Min...max input scale selected in AI.2 and tP.2
1000
404
LS.2
R/W
Minimum limit of auxiliary input scale 2
Min...max input scale selected in AI.2 and tP.2
0
605
oFS.2
R/W
Offset for auxiliary input correction 2
-999 ...999
Scale points
0
Scale limits
Setting the offset
Min...max input scale selected in AI.3
1000
Min...max input scale selected in AI.4
1000
Min...max input scale selected in AI.3
0
Min...max input scale selected in AI.4
0
556
LS.3
R/W
Minimum limit of auxiliary input scale 3
557
LS.4
R/W
Minimum limit of auxiliary input scale 4
558
LS.5
R/W
Minimum limit of auxiliary input scale 5
Min...max input scale selected in AI.5
0
559
XS.3
R/W
Maximum limit of auxiliary input scale 3
560
XS.4
R/W
Maximum limit of auxiliary input scale 4
561
XS.5
R/W
Maximum limit of auxiliary input scale 5
Min...max input scale selected in AI.5
1000
-999 ...999 punti scala
0
-999 ...999 punti scala
0
565
oFS.3
R/W
Offset for auxiliary input correction 3
566
oFS.4
R/W
Offset for auxiliary input correction 4
567
oFS.5
R/W
Offset for auxiliary input correction 5
-999 ...999 punti scala
0
547
In.3
R
Value of auxiliary input 3
548
In.4
R
Value of auxiliary input 4
549
In.5
R
Value of auxiliary input 5
550
Er.3
R
Error code for self-diagnosis
of auxiliary input 3
551
Er.4
R
Error code for self-diagnosis
of auxiliary input 4
552
Er.5
R
Error code for self-diagnosis
of auxiliary input 5
Page 25
2580963B_MSW_GFW_11-2012_ENG
ADVANCED SETTINGS
Input lter
FUNCTIONAL DIAGRAM
604
FLt.2
R/W
Digital filter for auxiliary input 2
0.0 ... 20.0 sec
0.1
Sets a low pass lter on the auxiliary input, running the average of values read in the specied time interval. If = 0 , excludes the average lter on sampled values.
Auxiliary
input IN2
Select sensor
(AI.2)
Scale limits, decimal
point, Offset (H.S2, L.S2, dP.2, OFS.2)
Low pass f
ilter
(Flt.2)
variable In.2
See generic
alarms and
Control
Auxiliary
input IN3
Select sensor
(AI.3)
Scale limits, decimal
point, Offset (H.S3, L.S3, dP.3, OFS.3)
Low pass f
ilter
(Flt.3)
variable In.3
See generic
alarms and
Control
Auxiliary
input IN4
Select sensor
(AI.4)
Scale limits, decimal
point, Offset (H.S4, L.S4, dP.4, OFS.4)
Low pass f
ilter
(Flt.4)
variable In.4
See generic
alarms and
Control
Auxiliary
input IN5
Select sensor
(AI.5)
Scale limits, decimal
point, Offset (H.S5, L.S5, dP.5, OFS.5)
Low pass f
ilter
(Flt.5)
variable In.5
See generic
alarms and
Control
0.0 ... 20.0 sec
0.1
0.0 ... 20.0 sec
0.1
562
FLt.3
R/W Digital filter for auxiliary input 3
563
FLt.4
R/W
Digital filter for auxiliary input 4
564
FLt.5
R/W Digital filter for auxiliary input 5 0.0 ... 20.0 sec
0.1
Page 26
26 80963B_MSW_GFW_11-2012_ENG
DIGITAL INPUTS
There are always three inputs. Each input can perform various functions based on the setting of the following parameters:
Read state
618
diG.2
R/W
140
diG.
R/W
Digital input function
0
0 No functions (input off) 1 MAN/AUTO controller 2 LOC / REM 3 HOLD 4 AL1, ..., AL4 alarms memory reset 5 SP1 / SP2 selection 6 Software on/off 7 None 8 START / STOP Selftuning 9 START / STOP Autotuning 10 Power_Fault alarms memory reset 11 LBA alarm reset 12 AL1 .. AL4 and Power_Fault alarms reset memory 13 Enable at software ON (*) 14 Reference calibration of retroaction selected by Hd.6 15 Calibration threshold alarm HB
Digital input 2 function
0
Digital input functions table
68
bit
STATE of DIGITAL
INPUT 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
STATE of DIGITAL
INPUT 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
Functions related to digital inputs
- MAN / AUTO controller see AUTO/MAN CONTROL
- LOC / REM see SETTING THE SETPOINT
- HOLD see HOLD FUNCTION
- Reset memory latch see GENERIC ALARMS AL1 .. AL4
- Select SP1 / SP2 see SETTINGS - Multiset
- Software OFF / ON see SOFTWARE SHUTDOWN
- START / STOP Selftuning see SELFTUNING
- START / STOP Autotuning see AUTOTUNING
- Calibration of feedback reference see FEEDBACK
- Calibration of HB alarm setpoint see HB ALARM
317
R
State of (INPUT_DIG) digital inputs
bit.0 = state INDIG1 bit.1 = state INDIG2 bit.2 = state INDIG3
(*) For diG. only (**) IN diG. alternative to serial
On leading edge On leading edge On state On state On leading edge On leading edge
On leading edge (**) On leading edge (**) On state On state
On state
Activation
694
diG.3
R/W
Digital input 3 function
0
Digital input 3 functions table
0 No functions (input off) 1 PWM input
67
bit
STATE of DIGITAL
INPUT 3
OFF = Digital input 3 off
ON = Digital input 3 on
R
+ 16 for inverse logic input + 32 to force logic state 0 (OFF) + 48 to force logic state 1 (ON)
+ 16 for inverse logic input
518
In.PWM R
PWM input value
0,0...100,0%
Page 27
2780963B_MSW_GFW_11-2012_ENG
USING A FUNCTION ASSOCIATED WITH DIGITAL
INPUT AND VIA SERIAL
At power-on or on the leading edge of digital input 1 or 2, all zones assume the state set by the digital input. For each zone, this state can be changed by writing via serial. The setting via serial is saved in eeprom (STATUS_W_EEP, address 698).
State A/B Setting Address for writing via serial
dIG. or dIG.2 Access at 16 bits Access at 1 bit
AUTO/MAN controller 1 word 305 bit 4 bit 1
LOC/REM setpoint 2 word 305 bit 6 bit 10
SP1/SP2 setpoint 5 word 305 bit 1 bit 75
ON/OFF software 6 word 305 bit 3 bit 11
STOP/START selftuning 8 word 305 bit 2 bit 3
STOP/START autotuning(*) (**) 9 word 305 bit 5 bit 29
(*) continuous or one-shot (**) only for zone 1 (GFW-M)
A
B
STATE OF DIGITAL
INPUT
A B
STATE OF A/B
SERIAL zone 1
A B
STATE OF A/B
SERIAL zone 2
A B
STATE OF A/B
SERIAL zone 3
STATE OF A/B
zone 1
STATE OF A/B
zone 2
STATE OF A/B
zone 3
SERIAL WRITING STATE A/B zone 3
SERIAL WRITING STATE A/B zone 2
SERIAL WRITING STATE A/B zone 1
LEADING EDGE OF DIGITAL INPUT
or at POWER-ON
Page 28
28 80963B_MSW_GFW_11-2012_ENG
USING A FUNCTION OF DIGITAL INPUT 1 TO ENABLE
AT SOFTWARE ON
Software ON can be configured either by enabling a digital input or by writing via serial. Enabling by digital input 1
(diG) is common to all zones, whereas enabling via serial is specific for each individual zone.
The ON/OFF setting via serial is saved in eeprom (STATUS_W_EEP, address 698 bit 3) for resetting of the condition at the next hardware power-on; use parameter P.On.t. to force software always ON or software always OFF at next power-on.
Setting Address for writing via serial
dIG Access at 16 bits Access at 1 bit
ON/OFF software 13 word 305 bit 3 bit 11
ON
OFF
STATE DIGITAL INPUT 1
SERIAL WRITING
ON/OFF zone 1
ON
OFF
ON
OFF
ON
OFF
SERIAL WRITING
ON/OFF zone 2
SERIAL WRITING
ON/OFF zone 3
STAT E
ON/OFF zone 1
AND logic
STAT E
ON/OFF zone 2
AND logic
STAT E
ON/OFF zone 3
AND logic
Page 29
2980963B_MSW_GFW_11-2012_ENG
ALARMS
GENERIC ALARMS AL1, AL2, AL3 and AL4
Four generic alarms are always available and can perform various functions. Typically, alarm AL.1 is defined as minimum and AL.2 as maximum. These alarms are set as follows:
- select the reference variable to be used to monitor the value (parameters A1.r, A2.r, A3.r and A4.r): the origin of the variable can be chosen from the process variable PV (generally linked to the main input), the ammeter input, the voltmeter input, the auxiliary analog input, or the active setpoint.
- set the value of the alarm setpoint (parameters AL.1, AL.2, AL.3 and AL.4). This value is used for comparison with the reference variable value: it can be absolute or indicate a shift from the variable in case of deviation alarm.
- set the hysteresis value for the alarm (parameters Hy.1, Hy.2, Hy.3 and Hy.4): the hysteresis value defines a band for safe re-entry of the alarm condition: without this band, the alarm would be deactivated as soon as the reference variable re-entered the setpoint limits, with the possibility of generating another alarm signal in the presence of oscillations of the reference signal around the setpoint value.
- select alarm type:
- absolute/deviation: if the alarm refers to an absolute value or to another variable (for example, to the setpoint).
- direct/reverse: if the reference variable exceeds the alarm setpoint in the “same direction” as the control action or not. For example, the alarm is direct if the reference variable exceeds the upper setpoint value during heating or assumes values below the lower setpoint during cooling. In the same manner, the alarm is reverse if the reference variable assumes values below the lower setpoint during heating or exceeds the setpoint during cooling.
- normal/symmetrical: if band value is subtracted or added, respectively, to/from the upper and lower limit of the alarm setpoints or indicates a higher and lower band compared to the alarm setpoint.
- with/without disabling at switch-on: if you want to check the reference variable value at system switch-on or wait until the variable enters the control window.
- with/without memory: if the alarm signal persists even when the cause has been eliminated or stops when the variable returns to normal values.
The above concepts are better explained in the following figures:
time
AL1 + Hyst1
AL2 + Hyst2
AL2
AL1
allarm 1
allarm 2
(*)
For AL1 reverse absolute alarm (low) with positive Hyst1, AL1 t = 1 (*) = OFF if disabled at switch on For AL2 direct absolute alarm (high) with negative Hyst2, AL2 t = 0
Normal absolute alarm
For AL1 = symmetrical inverse absolute alarm with Hyst1, AL1 t = 5 For AL1 = symmetrical direct absolute alarm with Hyst1, AL1 t = 4 Minimum hysteresis = 2 scale points
Inverse
Direct
AL1
AL1 + [ Hyst1 ]
AL1 - [ Hyst1 ]
time
Symmetrical absolute alarm
For AL1 = normal inverse deviation alarm with negative Hyst 1, AL1 t = 3 For AL1 = normal direct deviation alarm with negative Hyst 1, AL1 t = 2
SP+AL1
SP
Inverse
Direct
time
Hyst1
Deviation alarm
For AL1 = Symmetrical inverse deviation alarm with Hyst 1, AL1 t = 7 For AL1 = Symmetrical direct deviation alarm with Hyst 1, AL1 t = 6
time
SP+AL1
SP
Inverse
Direct
SP-AL1
Symmetrical deviation alarm
Page 30
30 80963B_MSW_GFW_11-2012_ENG
Alarms hysteresis
27
187
XY.1
R/W
Hysteresis for alarm 1
± 999
Scale points
- 1
0...999 sec. If +32 in A1.t
0...999 min. If +64 in A1.t
59
XY.4
R/W
Hysteresis for alarm 4
± 999
Scale points
- 1
0...999 sec. If +32 in A1.t
0...999 min. If +64 in A1.t
53
189
XY.3
R/W
Hysteresis for alarm 3
± 999
Scale points
- 1
0...999 sec. If +32 in A1.t
0...999 min. If +64 in A1.t
30
188
XY.2
R/W
Hysteresis for alarm 2
± 999
Scale points
- 1
0...999 sec. If +32 in A1.t
0...999 min. If +64 in A1.t
Reference variables
215
a1.r
R/W
Select reference variable alarm 1
0
216
A2.r
R/W
Select reference variable alarm 2
217
A3.r
R/W
Select reference variable alarm 3
218
A4.r
R/W
Select reference variable alarm 4
Variable to be compared Reference setpoint 0 PV (process variable) AL 1 in.tA1 AL (In.tA1 OR In.tA2 OR In.tA3 WITH 3-PHASE LOAD) 2 In.tV1 AL (In.tV1 OR In.tV2 OR In.tV3 WITH 3-PHASE LOAD) 3 SPA (active setpoint) AL (absolute only) 4 PV (process variable) AL [deviation only and referred to SP1 (with multiset function) 5 In.2 auxiliary input AL 6 In.3 auxiliary input AL 7 In.4 auxiliary input AL 8 In.5 auxiliary input AL 9 In.A analg input AL 10 In.Pwm PWM input AL
N.B. for codes 1, 2, 5, 6, 7, 8, 9 and 10 the reference to the alarm is in scale points and not to the decimal point (dP.x)
0
0
0
Table of alarm reference setpoints
Alarm setpoints
12
475 - 177
AL.1
R/W
Alarm setpoint 1 (scale points)
13
476 - 178
AL.2
R/W
Alarm setpoint 2 (scale points)
14
52 - 479
AL.3
R/W
Alarm setpoint 3 (scale points)
58
480
AL.4
R/W
Alarm setpoint 4 (scale points)
500
100
700
800
-1999...9999 Scale points
-999...999 if alarm symetrical
0...999 if alarm relative and symetrical
-1999...9999 Scale points
-999...999 if alarm symetrical
0...999 if alarm relative and symetrical
-1999...9999 Scale points
-999...999 if alarm symetrical
0...999 if alarm relative and symetrical
-1999...9999 Scale points
-999...999 if alarm symetrical
0...999 if alarm relative and symetrical
Page 31
3180963B_MSW_GFW_11-2012_ENG
46
bit
AL1 direct/inverse R/W
47
bit
AL1 absolute/relative R/W
48
bit
AL1 normal/symmetrical R/W
49
bit
AL1 disabled at switch-on R/W
50
bit
AL1 with memory R/W
54
bit
AL2 direct/inverse R/W
55
bit
AL2 absolute/relative R/W
56
bit
AL2 normal/symmetrical R/W
57
bit
AL2 disabled at switch-on R/W
58
bit
AL2 with memory R/W
Alarm type
406
a1.t
R/W
Alarm type 1
0
407
A2.t
R/W
Alarm type 2
408
54
A3.t
R/W
Alarm type 3
409
A4.t
R/W
Alarm type 4
0
0
0
Direct (high limit) Absolute Normal Inverse (low limit) Relative Symmetrical to activfe setpoint (window) 0 direct absolute normal 1 inverse absolute normal 2 direct relative normal 3 inverse relative normal 4 direct absolute symmetrical 5 inverse absolute symmetrical 6 direct relative symmetrical 7 inverse relative symmetrical
Table of alarm behaviour
36
bit
AL3 direct/inverse R/W
37
bit
AL3 absolute/relative R/W
38
bit
AL3 normal/symmetrical R/W
39
bit
AL3 disabled at switch-on R/W
40
bit
AL3 with memory R/W
70
bit
AL4 direct/inverse R/W
71
bit
AL4 absolute/relative R/W
72
bit
AL4 normal/symmetrical R/W
73
bit
AL4 disabled at switch-on R/W
74
bit
AL4 with memory R/W
+ 8 to disable at switch-on until first setpoint + 16 to enable memory latch + 32 Hys becomes delay time for activation of alarm (0...999 sec.) (excluding absolute symmetrical) + 64 Hys becomes delay time for activation of alarm (0...999 min.) (excluding absolute symmetrical) + 136 to disable at switch-on or at change of setpoint until first setpoint + 256 only for alarms with memory and delay time: the delay time becomes a timed hysteresis (with time stopped in case of SBR condition: when SBR condition disappears the delay time starts counting from zero)
Page 32
32 80963B_MSW_GFW_11-2012_ENG
Enable alarms
195*
AL.n
R/W
Select number of enabled alarms
+ 16 to enable HB alarm
+ 32 to enable LBA alarm
Alarm 1 Alarm 2 Alarm 3 Alarm 4 0 disabled disabled disabled disabled 1 enabled disabled disabled disabled 2 disabled enabled disabled disabled 3 enabled enabled disabled disabled 4 disabled disabled enabled disabled 5 enabled disabled enabled disabled 6 disabled enabled enabled disabled 7 enabled enabled enabled disabled 8 disabled disabled disabled enabled 9 enabled disabled disabled enabled 10 disabled enabled disabled enabled 11 enabled enabled disabled enabled 12 disabled disabled enabled enabled 13 enabled disabled enabled enabled 14 disabled enabled enabled enabled 15 enabled enabled enabled enabled
Table of enabled alarms
Reset memory latch
4
bit
STATE of ALARM 1
OFF = Alarm off
ON = Alarm on
R
5
bit
STATE of
ALARM 2
OFF = Alarm off
ON = Alarm on
R
62
bit
STATE of
ALARM 3
OFF = Alarm off
ON = Alarm on
R
69
bit
STATE of
ALARM 4
OFF = Alarm off
ON = Alarm on
R
Read state
618
diG.2
R/W
140
diG.
R/W
Digital input function
0
0 No function (input off) 1 MAN /AUTO controller 2 LOC / REM 3 HOLD 4 AL1, ..., AL4 latch alarm reset 5 SP1 / SP2 selection 6 Software on/off 7 None 8 START / STOP Selftuning 9 START / STOP Autotuning 10 Power_Fault latch alarm reset 11 LBA alarm reset 12 AL1 .. AL4 and Power_Fault latch alarm reset 13 Enable at software ON (*) 14 Reference calibration of retroaction selected by Hd.6
15 Calibration threshold alarm HB
Digital input function 2
0
Digital input functions table
318*
R
State of alarms ALSTATE IRQ
bit 0 State AL.1 1 State AL.2 2 State AL.3 3 State AL.4 4 State AL.HB (if 3-phase or phase 1/2/3) or Power Fault 5 State AL.HB PHASE 1 (if 3-phase) 6 State AL.HB PHASE 2 (if 3-phase) 7 State AL.HB PHASE 3 (if 3-phase)
States of alarm table
79
bit
Reset memory latch R/W
(*) For diG. only
(*) For zone 2 (GFW-E1) and zona 3 (GFW-E2), AL.n denes enabling of only the HB alarm in mono-phase conguration.
+ 16 for inverse logic input + 32 to force logic state 0 (OFF) + 48 to force logic state 1 (ON)
3
zone1
0
zone20zone3
Page 33
3380963B_MSW_GFW_11-2012_ENG
FUNCTIONAL DIAGRAM
Alarm setpoint
AL1
State of alarm AL1
Select
reference
variable
(A1.r, A2.r,
A3.r, A4.r)
See outputs
PV
I.tV1 or I.tV2 or
I.tV3
I.tA1 or I.tA2 or
I.tA3
In.2
In.3
In.4
In.5
SPA
Type of alarm and
hysteresis
(A1.t, HY.1)
Type of alarm and
hysteresis
(A2.t, HY.2)
Type of alarm and
hysteresis
(A3.t, HY.3)
Type of alarm and
hysteresis
(A4.t, HY.4)
State of alarm AL2
State of alarm AL3
State of alarm AL4
Alarm setpoint
AL2
Alarm setpoint
AL3
Alarm setpoint
AL4
PV: process variable SPA: active setpoint In.2/In.3/In.4/In.2: auxiliary analog input I.tAx: ammeter input I.tVx: voltmeter input In.A: analog input In.Pwm: PWM input
In.A
In.Pwm
Page 34
34 80963B_MSW_GFW_11-2012_ENG
LBA ALARM (Loop Break Alarm)
This alarm identifies incorrect functioning of the control loop due to a possible load break or to a short circuited or reversed probe.
With the alarm enabled (parameter AL.n), the instrument checks that in condition of maximum power delivered for a settable time (Lb.t) greater than zero, the value of the process variable increases in heating or decreases in cooling: if this does not happen, the LBA alarm trips. In these conditions, power is limited to value (Lb.P).
The alarm condition resets if the temperature increases in heating or decreases in cooling.
Enable alarm
195*
AL.n
R/W
Select number of enabled alarms
119
Lb.p
R/W
Limitation of power delivered in
presence of LBA alarm
-100,0 ..100,0 %
8
bit
STATE of LBA
ALARM
OFF = LBA alarm off
ON = LBA alarm on
R
Read state
44
Lb.t
R/W
Delay time for tripping of LBA alarm
0,0 ... 500,0 min
FUNCTIONAL DIAGRAM
Enable alarm
(AL.n)
Delay time for tripping
(Lb.t)
State of LBA variable
Break in control
loop
See outputs
Limitation of power Lb.P
See Alarms
SBR-Err
81
bit
Reset LBA alarm R/W
see: Table of enabled alarms
25,0
30,0
If Lb.t = 0, the LBA alarm is disabled
3
zone1
0
zone20zone3
Page 35
3580963B_MSW_GFW_11-2012_ENG
HB ALARM (Heater Break Alarm)
This type of alarm identifies load break or interruption by measure the current delivered by means of a current transformer. The following three fault situations may occur:
- delivered current is lower than nominal current: this is the most common situation, and indicates that a load element is breaking.
- delivered current is higher than nominal current: this situation occurs, for example, due to partial short circuits of load elements.
- delivered current remains significant even during periods in which it should be zero: this situation occurs in the presence of pilot circuits for the short-circuited load or due to relay contacts soldered together. In these cases, prompt action is very important to prevent greater damage to the load and/or to the pilot circuits. In standard configuration, output SSR is associated to heating control in zone 1, obtained by modulating electrical power with the ON/OFF control based on the set cycle time. The current read performed during the ON phase identifies an anomalous shift from the rated value due to a load break (first two fault situations described above), while the current read performed during the OFF phase identifies a break in the control relay, with consequent output always active (third fault situation). The alarm is enabled by means of parameter AL.n; select the type of function you want by means of parameter Hb.F:
Hb.F=0: alarm activates if the current load value is below the setpoint value set in A.Hbx while the SSR control output is ON. Hb.F=1: alarm activates if the current load value is above the setpoint value set in A.Hbx while the SSR control output is OFF. Hb.F=2: alarm activates by combining functions 0 and 1, considering the setpoint of function 1 as 12% of the ammeter full
scale defined in H.tAx. Hb.F=3 or Hb.F=7 (continuous alarm): alarm activates due to a load current value below the setpoint value set in A.Hbx; this alarm does not refer to the cycle time and is disabled if the heating (cooling) output value is below 3%. Setting A.Hbx = 0 disables both types of HB alarm by forcing deactivation of the alarm state. The alarm resets automatically if its cause is eliminated. An additional configuration parameter for each zone, related to the HB alarm is: Hb.t = delay time for activation of HB alarm, understood as the sum of times for which the alarm is considered active. For example, with:
- Hb.F = 0 (alarm active with current below setpoint value),
- Hb.t = 60 sec and cycle time of control output = 10 sec,
- power delivered al 60%, the alarm will activate after 100 sec (output ON for 6 sec each cycle); if power is delivered at 100%, the alarm will activate after 60 sec. If the alarm deactivates during this interval, the time sum is reset. The delay time set in Hb.t must exceed the cycle time of the SSR output. If zone 1 has a 3-phase load, you can set three different setpoints for the HB alarm: A.Hb1= alarm setpoint for line L1 A.Hb2= alarm setpoint for line L2 A.Hb3= alarm setpoint for line L3
FUNCTION: HB ALARM SETPOINT SELF-LEARNING
This function permits self-learning of the alarm setpoint. To use this function, you first have to set parameter Hb.P, which defines the percentage of current compared to rated load below which the alarm trips. The function can be activated via control from serial line, digital input (see parameter dIG or dIG.2) or by key. When the Teach-in function is activated in modes ZC, BF and HSC, the RMS current value in conduction ON multiplied by parameter Hb.P determines the HB alarm setpoint. When the Teach-in function is activated in mode PA, the existing RMS current value is shown at 100% of power, which, mul­tiplied by parameter Hb.P, determines the HB alarm setpoint.
For IR lamps (see parameter Hd.5 option +128), the function activates automatic reading of the power/current curve useful for determining the HB alarm setpoint. Automatic reading of the power/current curve takes place with the following sequence:
- softstart at maximum power (default 100%), 5 sec. delay
- reduction of power to 50%, 30%, 20%, 15%, 10%, 5%, 3%, 2%, 1%, between every value 5 sec. delay
- return to normal operation. Maximum conduction value in this phase can be limited by means of the PS.Hi parameter. If requested, MUST be activated only with Hd.6=0 (the required Hd.6 value can be set only after calibration).
Page 36
36 80963B_MSW_GFW_11-2012_ENG
Alarm setpoints
0,0 ... 100,0%
737*
xb.P
R/W
Percentage HB alarm setpoint of
current read in HB calibration
10,0
With 3-phase load
503
A.xb3
R/W
HB alarm setpoint (scale points amme-
ter input - Phase 3)
10,0
With 3-phase load
502
A.xb2
R/W
HB alarm setpoint (scale points amme-
ter input - Phase 2)
55*
A.xb1
R/W
HB alarm setpoint (scale points amme-
ter input - Phase 1)
112* bit
Calibration HB
alarm setpoint for
zone
R/W
OFF = Calibration not enabled
ON = Calibration enabled
NB: In case of 3-phase load, you can set a different value for parameter A.Hb1,
A.Hb2, A.Hb3 for each zone (ex.: to control an unbalanced 3-phase load).
759*
Ir.tA.1
R/W
HB Calibration with IR lamp: current at
50% conduction
758*
Ir.tA.0
R/W
HB Calibration with IR lamp: current at
100% conduction
743*
xb.Pw
R/W
Ou.P power in calibration
742*
xb.tA
R/W
CT read in HB calibration
760*
Ir.tA.2
R/W
HB Calibration with IR lamp: current at
30% conduction
761*
Ir.tA.3
R/W
HB Calibration with IR lamp: current at
20% conduction
Enable alarm
57*
Xb.f
R/W
HB alarm functions
Val. Description of functions 0 Relay, logic output: alarm active at a load current value below set point for control output ON time. 1 Relay, logic output: alarm active at a load current value above set point for control output OFF time. 2 Alarm active if one of functions 0 and 1 is active (OR logic between functions 0 and 1) (*) 3 Continuous heating alarm 7 Continuous cooling alarm
(*) minimum setpoint is set at 12% of ammeter full scale
Default: SINGLE-PHASE LOAD: each A.HbX refers to its respective phase. 2-PHASE LOAD: single reference setpoint A.Hb1 and OR between phases 1, 2 and phases 3, 4. 3-PHASE LOAD: single reference setpoint A.Hb1 and OR among phases 1, 2 and 3.
+ 8 HB reverse alarm + 16 relates to single setpoints and singled phases WITH 3-PHASE LOAD
Table of HB alarm functions
195*
AL.n
R/W
Select number of enabled alarms
See: Table of enable alarms
56*
XB.T
R/W
Delay time for activation of HB alarm
The value must exceed the cycle
time of the output to which the HB
alarm is associated.
0 ... 999 sec
452*
xb.t
R/W TV read in HB calibration
767*
Ir.tA.4
R/W
HB Calibration with IR lamp
current at 15% conduction
768*
Ir.tA.5
R/W
HB Calibration with IR lamp
current at 10% conduction
769*
Ir.tA.6
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 5% conduction
3
zone1
0
zone20zone3
0
zone1
0
zone20zone3
5
zone1
5
zone25zone3
10,0
zone1
10,0
zone2
10,0
zone3
80,0
zone1
80,0
zone2
80,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
382*
Ir.tA.7
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 3% conduction
0,0
zone1
0,0
zone2
0,0
zone3
383*
Ir.tA.8
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 2% conduction
0,0
zone1
0,0
zone2
0,0
zone3
384*
Ir.tA.9
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 1% conduction
0,0
zone1
0,0
zone2
0,0
zone3
Page 37
3780963B_MSW_GFW_11-2012_ENG
Read state
26*
bit
HB ALARM STATE OR
POWER_FAULT
OFF = Alarm off
ON = Alarm on
R
504
R
HB alarm states ALSTATE_HB
(for 3-phase loads)
bit 0 HB TA2 time ON 1 HB TA2 time OFF 2 HB alarm TA2 3 HB TA3 time ON 4 HB TA3 time OFF 5 HB alarm TA3
Table of HB alarm states
512*
R
States of alarm ALSTATE
(for single-phase loads)
bit 4 HB alarm time ON 5 HB alarm time OFF 6 HB alarm
Table of alarm states ALSTATE
76*
bit
State of HB alarm
phase 1TA
OFF = Alarm off
ON = Alarm on
R
77
bit
State of HB alarm
phase 2TA
OFF = Alarm off
ON = Alarm on
R
78
bit
State of HB alarm
phase 3TA
OFF = Alarm off
ON = Alarm on
R
744*
xb.tr
R
HB alarm setpoint as function
of power on load
445*
Ir.t .0
R/W
HB Calibration with IR lamp: voltage at 100% conduction
446*
Ir.t .1
R/W
HB Calibration with IR lamp:
voltage at 50% conduction
447*
Ir.t .2
R/W
HB Calibration with IR lamp:
voltage at 30% conduction
448*
Ir.t .3
R/W
HB Calibration with IR lamp:
voltage at 20% conduction
451*
Ir.t .6
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 5% conduction
450*
Ir.t .5
R/W
HB Calibration with IR lamp:
voltage at 10% conduction
449*
Ir.t .4
R/W
HB Calibration with IR lamp:
voltage at 15% conduction
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
390*
Ir.t .7
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 3% conduction
0,0
zone1
0,0
zone2
0,0
zone3
391*
Ir.t .8
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 2% conduction
0,0
zone1
0,0
zone2
0,0
zone3
392*
Ir.t .9
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 1% conduction
0,0
zone1
0,0
zone2
0,0
zone3
318*
R
State of alarms ALSTATE IRQ
bit 0 State AL.1 1 State AL.2 2 State AL.3 3 State AL.4 4 State AL.HB (if 3-phase or phase 1/2/3) or Power Fault 5 State AL.HB PHASE 1 (if 3-phase) 6 State AL.HB PHASE 2 (if 3-phase) 7 State AL.HB PHASE 3 (if 3-phase)
States of alarm table
Page 38
38 80963B_MSW_GFW_11-2012_ENG
FUNCTIONAL DIAGRAM
Alarm setpoint
Hb.tr zone 1
State of alarm HB phase 1
I.1on
Function of
HB alarm
and time for
activation
of HB alarm
(Hb.F, Hb.t)
See outputs
State of alarm HB phase 2 (*)
Alarm setpoint
Hb.tr zone 2 (*)
Alarm setpoint
Hb.tr zone 3 (*)
(*) - Only for 3-phase applications
I.2on
I.3on
State of alarm HB phase 3 (*)
HB Alarm
HB Calibration in mode PA
NOTE: the value of setpoint Hb.tr for the HB alarm is calculated in two different ways, depending on the selected function mode:
if ZC, BF, HSC mode: ................................................... Hb.tr = A.Hb
if PA mode .................................................................... Hb.tr = A.Hb *
V(Ou.P)
HB Calibration in modes ZC - BF - HSC
Percent HB alarm
setpoint of current
read in HB calibration
Hb.P
HB alarm
setpoint
A.Hb
- Calibration ON Bit 112
- dIG/dIG.2 Function
- Key Function
Value of Ou.P
control outputs
Value of CT input
with output on (phase 1)
I.1ON
CT read in
HB calibration
Hb.TA
Ou.P power in
Hb.Pw
calibration
X
Ou.P power
in Hb.Pw
calibration
CT read in
HB calibration
Hb.TA
HB alarm
setpoint
A.Hb
(Load current referred to
100% of conduction)
X
X
Percent HB alarm
setpoint of current
read in HB calibration
Hb.P
Value of Ou.P
control outputs
Value of CT input
with output on (phase 1)
I.1ON
- Calibration ON Bit 112
- dIG/dIG.2 Function
- Key Function
Page 39
3980963B_MSW_GFW_11-2012_ENG
SBR - ERR ALARM (probe in short or connection error)
This alarm is always ON and cannot be deactivated. It controls correct functioning of the probe connected to the main input. In case of broken probe:
- the state of alarms AL1, AL2, AL3 and AL4 is set based on the value of parameter rEL;
- control power control is set to the value of parameter FAP. Identification of the type of break detected on the main input is contained in Err.
9
bit
STATE OF INPUT
IN SBR
OFF = -
ON = Input in SBR
R
Enable alarm
229
rEL
R/W
Fault action
(definition of state in case
of broken probe)
Sbr, Err
Only for main input
0
Alarm Alarm Alarm Alarm 1 2 3 4 0 OFF OFF OFF OFF 1 ON OFF OFF OFF 2 OFF ON OFF OFF 3 ON ON OFF OFF 4 OFF OFF ON OFF 5 ON OFF ON OFF 6 OFF ON ON OFF 7 ON ON ON OFF 8 OFF OFF OFF ON 9 ON OFF OFF ON 10 OFF ON OFF ON 11 ON ON OFF ON 12 OFF OFF ON ON 13 ON OFF ON ON 14 OFF ON ON ON 15 ON ON ON ON
Table of probe alarm settings
228
fa.p
R/W
Fault action power
(supplied in conditions of broken probe)
-100,0 ..100,0 %
0,0
see: OTHER FUNCTION
Read state
85
Err
R
Error code in self-diagnostics
of main input
See: Table of error codes
Page 40
40 80963B_MSW_GFW_11-2012_ENG
661
dg.t
R/W
Refresh rate SSR_SHORT
The alarm activates after 3 seconds.
662*
dg.f
R/W
Time lter for NO_VOLTAGE, SSR_
OPEN and NO_CURRENT alarms
Power Fault ALARMS (SSR_SHORT, NO_VOLTAGE, SSR_OPEN and NO_CURRENT)
660*
hd.2
R/W
Enable POWER_FAULT alarms
Table of Power Fault alarms
Read state
96*
bit
State of alarm
SSR_SHORT phase 1
R
97
bit
State of alarm
SSR_SHORT phase 2
R
98
bit
State of alarm
SSR_SHORT phase 3
R
99*
bit
State of alarm
NO_VOLTAGE phase 1
R
100
bit
State of alarm
NO_VOLTAGE phase 2
R
101
bit
State of alarm
NO_VOLTAGE phase 3
R
102*
bit
State of alarm
NO_CURRENT phase 1
R
103
bit
State of alarm
NO_CURRENT phase 2
R
104
bit
State of alarm
NO_CURRENT phase 3
R
105*
bit
Reset SSR_SHORT
/ NO_VOLTAGE /
NO_CURRENT alarms
R/W
0
zone1
0
zone20zone3
with 3-phase load
with 3-phase load
with 3-phase load
with 3-phase load
with 3-phase load
with 3-phase load
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
OFF = LBA alarm off
ON = LBA alarm on
10
Set a value not less than
cycle time
10
zone1
10
zone210zone3
SSR _SHORT NO_ VOLTAGE NO_CURRENT
0 1 X 2 X 3 X X 4 5 X 6 X 7 X X 8 X 9 X X 10 X X 11 X X X 12 X 13 X X 14 X X 15 X X X
1...999 sec
0...99 sec
+ 32 alarms with memory
+ 64 disables current polarity check (inductive loads only)
+ 136 enables partial load mode
(128+8) for three-phase delta configuration without neutral, with or without
transformer Y/Y or Δ /Δ)
+ 264 enables partial load mode
(256+8) for three-phase delta configuration without neutral, with or without
transformer Δ/Y or Y/Δ)
Page 41
4180963B_MSW_GFW_11-2012_ENG
Overheat alarm
Each power module has one temperature sensor for the internal heat sink and two additional temperature sensors connected to the LINE and LOAD terminals. Temperature levels are shown in variables INNTC_SSR, INNTC_LINE and INNTC_LOAD. The over_heat alarm trips when at least one of the temperatures exceeds a set threshold. This condition may be caused by obstructed ventilation slits or by a stopped cooling fan. With the over_heat alarm active, the control disables control outputs OUT1, OUT2 and OUT3. There is an additional maximum temperature protection that hardware disables the SSR controls.
655*
R
INNTC_SSR
Overheat alarm
534*
R
INNTC_LINE
Overheat alarm
535*
R
INNTC_LOAD
Overheat alarm
10,0 ....120,0 °C
10,0 ....120,0 °C
10,0 ....120,0 °C
FUSE_OPEN AND SHORT_CIRCUIT_CURRENT ALARMS
The FUSE_OPEN alarm trips when the (optional) internal high-speed fuse opens or when the (optional) electronic fuse switches off.
The SHORT_CIRCUIT_CURRENT alarm trips when peak current on the load exceeds the maximum limit (corre­sponding to twice the rating) during the softstart ramp or at first power-on (with softstart ramp disabled).
If configured (Fr.n other than zero), the device restarts automatically in softstart for a maximum of Fr.n attempts, beyond which it remains deactivated while awaiting manual reset with front panel key BUT or with the control via serial (bit 109).
456
fr.n
R/W
Number of restarts in case of
FUSE_OPEN / SHORT_CIRCUIT_CURRENT
0
109*
bit
RESET FUSE_OPEN /SHORT_
CIRCUIT_CURRENT ALARMS
R/W
OFF = ­ON = Reset FUSE_OPEN / SHORT_CIRCUIT_CURRENT alarms
The restart function is available on models:
- with Electronic Fuse option from V.2.00
- without Electronic Fuse option from V.2.02
Read state
634*
R State 4 (STATUS4) Table State 4
ELECTRONIC FUSE OPTION
The electronic fuse avoids the use of a high-speed fuse to protect the controller. In case of a short circuit on the load, the electronic fuse switches off immediately and the relative FUSE_OPEN alarm activates.
- The electronic fuse DOES NOT replace any of the safeties on the system (such as magnetothermic switches,
delay fuses, etc.).
- The electronic fuse protects the controller (and therefore also the load) by replacing the high-speed fuse needed to protect the control SCRs against faults (without creating any additional cost to replace the fuse and reducing
machine downtime).
- The electronic fuse has 2 function states:
- Normal (On-Off control of load power)
- Fuse-Open: GFW is open (a short occurred during normal operation).
Page 42
42 80963B_MSW_GFW_11-2012_ENG
OUTPUTS
The modular power controller has high flexibility in the assignment of functions to the physical outputs. As a result, the instrument can be used in sophisticated applications. A function is assigned to each physical output in two steps: first assign the function to one of internal reference signals rL.1 .. rL.6, and then attribute the reference signal to parameters out.1 .. out.10 (corresponding to physical outputs OUT1 .. OUT10). In standard configuration, physical outputs Out1, Out2, Out3 perform the heating control function (Heat) for zone 1, zone 2, and zone 3, respectively; value 0 (function HEAT) is assigned to reference signals rL.1 in each zone, and the following values to the output parameters: out.1=1 (output rL.1 zone 1), out.2=2 (output rL.1 zone 2), out.3=3 (output rL.1 zone 3). Physical outputs Out5, Out6, Out7, Out8 are optional, and the type (relay, logic, continuous or triac) is defined by the order code. In standard configuration, these outputs perform the cooling control function (Cool) for zone 1, zone 2, and zone 3, respectively. In this configuration, value 1 (function COOL) is assigned to reference signals rL.2 in each zone, and the following values to the output parameters: out.5=5 (output rL.2 zone 1), out.6=6 (output rL.2 zone 2), out.7=7 (output rL.2 zone 3). Relay outputs Out9 and Out10 are always present, programmable by means of parameters out.9 and out.10, to which available alarm signal functions are assigned by means of the four reference signals rL.3, rL.4, rL.5, rL.6 in each zone. Standard configuration has the following assignments:
- reference signals: rL.3=2 (function AL1), rL.4=3 (function AL2), rL.5=4 (function AL3) and rL.6=5 (function AL.HB or PO­WER_FAULT with HB alarm).
- output parameters: out.9 =17 and out.10 =18. In this way, the state of output physical Out9 is given by the logic OR of AL1, AL3 in each zone, and the state of output Out10 is given by the logic AND of AL2, AL.HB in each zone. Each output can always be disabled by setting parameter out.x = 0. The state of outputs Out1,...,Out10 can be acquired by serial communication by means of bit variables. The following additional configuration parameters are related to the outputs: Ct.1 = cycle time for output rL.1 for heating control (Heat) Ct.2 = cycle time for output rL.2 for cooling control (Cool) rEL = alarm states AL1, AL2, AL3, AL4 in case of broken probe, Err, Sbr
ALLOCATION OF REFERENCE SIGNALS
160*
rL.1
R/W
Allocation of reference signal
+ 32 for logic level denied in output + 128 to force output to zero NOTE: continuous COOL OUTPUTS can be assigned codes 0, 1, 64 and 65 only, with cycle time fixed at 100 ms
163*
rL.2
R/W
Allocation of reference signal
Function
0 HEAT (heating control output) / in case of
continuous output 0...20mA / 0...10V 1 COOL (cooling control output) / in case of continuous output 0...20mA / 0...10V 2 AL1 - alarm 1 (*) 3 AL2 - alarm 2 (*) 4 AL3 - alarm 3 (*) 5 AL.HB or POWER_FAULT with HB alarm (TA1 OR TA2 OR TA3) 6 LBA - LBA alarm (*) 7 IN1 – repetition of logic input DIG1 8 AL4 - alarm 4 (*) 9 AL1 or AL2 (*) 10 AL1 or AL2 or AL3 (*) 11 AL1 or AL2 or AL3 or AL4 (*) 12 AL1 and AL2 (*) 13 AL1 and AL2 and AL3 (*) 14 AL1 and AL2 and AL3 and AL4 (*) 15 AL1 or AL.HB or POWER_FAULT with HB alarm (TA1 OR TA2 OR TA3) (*) 16 AL1 or AL2 or (AL.HB or POWER_FAULT) with HB alarm (TA1 OR TA2 OR TA3) (*) 17 AL1 and (AL.HB or POWER_FAULT) with HB alarm (TA1 OR TA2 OR TA3) (*) 18 AL1 and AL2 and (AL.HB or POWER_FAULT) with HB alarm (TA1 OR TA2 OR TA3) (*) 19 AL.HB - HB alarm (TA2) 20 AL.HB - HB alarm (TA3) 21 Setpoint power alarm (*) 22 AL.HB - HB alarm (TA1) 23 POWER_FAULT 24 IN2 - repetition of logic input DIG2 64 HEAT (heating control output) with fast cycle time
0.1 ... 20.0sec. / in case of continuous output
4...20mA / 2...10V 65 COOL (cooling control output) with fast cycle time
0.1 ... 20.0sec. / in case of continuous output
4...20mA / 2...10V
Table of reference signals
NOTE: Parameters rL.1, ..., rL.6 for each zone
can be considered as internal states.
Ex.: To assign alarm AL1 to physical output OUT5, assign rL.1-Zone1=2 (AL1-alarm 1) and than assign parameter out.5=1 (rL.1-Zone1)
(see: SETTINGS)
(see: SETTINGS)
(see: GENERIC ALARMS)
(*) only for zone 1 (GFW-M)
0
zona1
0
zona20zona3
1
zona1
1
zona21zona3
Page 43
4380963B_MSW_GFW_11-2012_ENG
308*
319
R
State of rL.x (MASKOUT_RL)
bit 0 State rL.1 1 State rL.2 2 State rL.3 3 State rL.4 4 State rL.5 5 State rL.6
Table of signal reference states
12*
bit
STATE rL.1
OFF = Signal off
ON = Signal on
R
13*
bit
STATE rL.2
OFF = Signal off
ON = Signal on
R
14*
bit
STATE rL.3
OFF = Signal off
ON = Signal on
R
15*
bit
STATE rL.4
OFF = Signal off
ON = Signal on
R
16*
bit
STATE rL.5
OFF = Signal off
ON = Signal on
R
17*
bit
STATE rL.6
OFF = Signal off
ON = Signal on
R
Read state
166*
rL.3
R/W
Allocation of reference signal
Function
2 AL1 - alarm 1 (*) 3 AL2 - alarm 2 (*) 4 AL3 - alarm 3 (*) 5 AL.HB or POWER_FAULT with HB alarm (TA1 OR TA2 OR TA3) 6 LBA - LBA alarm (*) 7 IN1 - repetition of logic input INDIG1 8 AL4 - alarm 4 (*) 9 AL1 or AL2 (*) 10 AL1 or AL2 or AL3 (*) 11 AL1or AL2 or AL3 or AL4 (*) 12 AL1 and AL2 (*) 13 AL1 and AL2 and AL3 (*) 14 AL1 and AL2 and AL3 and AL4 (*) 15 AL1 or AL.HB or POWER_FAULT with HB alarm (TA1 OR TA2 OR TA3) (*) 16 AL1 or AL2 or (AL.HB or POWER_FAULT) with HB alarm (TA1 OR TA2 OR TA3) (*) 17 AL1 and (AL.HB or POWER_FAULT) with HB alarm (TA1 OR TA2 OR TA3) (*) 18 AL1 and AL2 and (AL.HB or POWERFAULT) with HB alarm (TA1 OR TA2 OR TA3) (*) 19 AL.HB - HB alarm (TA2) 20 AL.HB - HB alarm (TA3) 21 Setpoint power alarm (*) 22 AL.HB - HB alarm (TA1) 23 POWER_FAULT 24 IN2 - repetition of logic input INDIG2
+ 32 for denied logic level at output + 128 to force output to zero
170*
rL.4
R/W
Allocation of reference signal
171*
rL.5
R/W
Allocation of reference signal
172*
rL.6
R/W
Allocation of reference signal
(*) state definite in zone 1 (GFW-M)
152*
9
(t.1
R/W
OUT 1 (Heat) cycle time
1 ...200 sec
(0,1 ...20,0 sec)
Set 0 for BF/HSC function
See POWER CONTROL
159*
(t.2
R/W
OUT 2 (Cool) cycle time
1 ...200 sec
(0,1 ...20,0 sec)
2
zone1
2
zone22zone3
35
zone1
35
zone235zone3
4
zone1
4
zone24zone3
160
zone1
160
zone2
160
zone3
0
zone1
0
zone20zone3
20
zone1
20
zone220zone3
DIP 5 = OFF (Resistive load)
4
zone1
4
zone24zone3
DIP 5 = ON (Inductive load)
Page 44
44 80963B_MSW_GFW_11-2012_ENG
82
bit
83
bit
84
bit
86
bit
87
bit
88
bit
89
bit
90
bit
91
bit
State of output OUT10
OFF = Output off
ON = Output on
R
State of output OUT9
OFF = Output off
ON = Output on
R
State of output OUT8
OFF = Output off
ON = Output on
R
State of output OUT7
OFF = Output off
ON = Output on
R
State of output OUT6
OFF = Output off
ON = Output on
R
State of output OUT5
OFF = Output off
ON = Output on
R
State of output OUT3
OFF = Output off
ON = Output on
R
State of output OUT2
OFF = Output off
ON = Output on
R
State of output OUT1
OFF = Output off
ON = Output on
R
Read state
664
R
State of outputs (MASKOUT_OUT)
bit 0 OUT 1 1 OUT 2 2 OUT 3 4 OUT 5 5 OUT 6 6 OUT 7 7 OUT 8 8 OUT 9 9 OUT 10
607
ovt.1
R/W
Allocation of physical output OUT 1
1
0 Output disabled 1 Output rL.1 zone 1 2 Output rL.1 zone 2 3 Output rL.1 zone 3 5 Output rL.2 zone 1 6 Output rL.2 zone 2 7 Output rL.2 zone 3 9 Output rL.3 OR rL.5 zone 1 10 Output rL.3 OR rL.5 zone 2 11 Output rL.3 OR rL.5 zone 3 13 Output rL.4 AND rL.6 zone 1 14 Output rL.4 AND rL.6 zone 2 15 Output rL.4 AND rL.6 zone 3 17 Output (rL.3 OR rL.5) zone 1...zone 3 18 Output (rL.4 AND rL.6) zone 1...zone 3
Table of output allocations
NOTE: In 3-phase conguration, the state of physical output OUT1 is copied
to OUT2 and OUT3. In case of auxiliary continuous outputs, the same output functions can not be used on other outputs. Ex: If out.1 = 1 (out rL.1 zone 1) it is not possible to set out.5 with the same code, if out.5 is continuous
608
ovt.2
R/W
Allocation of physical output OUT 2 (*)
2
609
ovt.3
R/W
Allocation of physical output OUT 3(**)
3
17
611
ovt.5
R/W
Allocation of physical output OUT 5
612
ovt.6
R/W
Allocation of physical output OUT 6
613
ovt.7
R/W
Allocation of physical output OUT 7
614
ovt.8
R/W
Allocation of physical output OUT 8
615
ovt.9
R/W
Allocation of physical output OUT 9
616
ovt.10
R/W
Allocation of physical output OUT 10
18
5
6
7
9
ALLOCATION OF PHYSICAL OUTPUTS
+32 to reverse output status (only for Logic/Relay) output
Table of output state
(*) available only with GFW-E1 present
(**) available only with GFW-E2 present
Page 45
4580963B_MSW_GFW_11-2012_ENG
FUNCTIONAL DIAGRAM
(*) Only for 3-phase applications
Out1
Out2
Out3
Out5
Out6
Out7
Out8
Out9
Out10
Allocation
of physical
outputs
(out.1,
out.2,
...,
out.10)
Ou.P (Heat)
Allocation
of reference
signal
(rL.1, rL.2,
rL.3, rL.4,
rL.5, rL.6)
Ou.P (Cool)
State of AL1
State of AL2
State of AL3
State of AL4
State of Hb.1
State of Hb.2 (*)
State of LbA
rL.1 - Zone1
rL.2 - Zone1
rL.3 or rL.5 - Zone1
rL.4 or rL.6 - Zone1
Zone 1
Ou.P (Heat)
Allocation
of reference
signal
(rL.1, rL.2,
rL.3, rL.4,
rL.5, rL.6)
Ou.P (Cool)
State of Hb.1
rL.1 - Zone2
rL.2 - Zone2
rL.3 or rL.5 - Zone2
rL.4 or rL.6 - Zone2
Zone 2
Ou.P (Heat)
Allocation
of reference
signal
(rL.1, rL.2,
rL.3, rL.4,
rL.5, rL.6)
Ou.P (Cool)
State of Hb.1
rL.1 - Zone3
rL.2 - Zone3
rL.3 or rL.5 - Zone3
rL.4 or rL.6 - Zone3
Zone 3
State of Hb.3 (*)
Page 46
46 80963B_MSW_GFW_11-2012_ENG
SETTINGS
The controller has the following setpoint controls.
SETTING THE SETPOINT
Local setpoint
138
16 - 472
sp
R/W
Local setpoint
0
Remote setpoint
Read active setpoint
1
137 - 481
spa
R Active setpoint
25
20 - 28 - 142
Lo.L
R/W
Lower settable limit SP, SP remote
Lo.S ... Hi.S
0
26
21 - 29 - 143
xI.L
R/W
Upper settable limit SP, SP remote
Lo.S ... Hi.S
1000
181
tp.2
R/W
Auxiliary analog input function
0
See: AUXILIARY ANALOG INPUT (LIN/TC)
The remote setpoint can be set by means of the auxiliary analog input by enabling the function with parameter tP.2
Shared settings
The active (control) setpoint (SPA) can be set by means of the local setpoint (SP) or the remote setpoint (SP.rS). A remote setpoint can assume the value of an auxiliary input or one set via serial line (SP.r).
The remote setpoint can be dened in absolute value or relative to the local setpoint; in the latter case, the control
setpoint will be given by the algebraic sum of the set local and the remote setpoint.
10
bit
LOCAL/REMOTE
OFF = Enable local setpoint
ON = Enable remote setpoint
R/W
18
136 - 249
SP.r
R/W
Remote setpoint
(SET gradient for manual power
correction)
0
Type of remote set Absolute/Relative 0 Digital (from serial line) Absolute 1 Digital (from serial line ) Relative to local set (SP or SP1 or SP2) 2 Auxiliary input Absolute 3 Auxiliary input Relative to set (SP or SP1 or SP2) +4 set gradient in digit/sec. +8 manual power correction based on line voltage +16 disables saving of local setpoint SP +32 disables saving of local manual power (at switch-off, returns to last value saved)
Setpoint table
4
R
Deviation (SPA - PV)
250
SERIAL_SP R/W Remote setpoint from serial line
0
Lo.L ... HI.L
Lo.L ... HI.L
305*
R/W
State (STATUS_W)
bit 0 ­ 1 Select SP1/SP2 (*) 2 Start/Stop Selftuning (*) 3 Select ON/OFF 4 Select AUTO/MAN 5 Start/Stop Autotuning (*) 6 Select LOC/REM (*)
Table of state settings
(*) only for zone1 (GFW-M)
0
zone1
0
zone20zone3
Page 47
4780963B_MSW_GFW_11-2012_ENG
Set gradient
The “Set gradient” function sets a gradual variation of the setpoint, with programmed speed, between two defined
values. If this function is active (
g.sp other than 0), at switch-
on and at auto/man switching the initial setpoint is assumed equal to the PV, and the local or selected set is reached with set gradient. Every variation of set, including variations of the
local setpoint, is subject to the gradient.
The value of remote setpoint SP.rS is not saved in eeprom. The set gradient is inhibited at switch-on when sel­ftuning is enabled.
265
xot
R/W
Select special functions
0
Table of special functions
Fault action Enable power if PV is Enable not stabilized preheating softstart
0 FA.P 1 X Average power 2 FA.P 3 X FA.P 4 FA.P X 5 X Average power X 6 FA.P X 7 X FA.P X +8 enable GS.2
FA.P – see alarm for probe in short or connection error (SBR-ERR)
234
22
g.sp
R/W
Set gradient
0.0 ...999.9 digit / min ( digit / sec see SP.r )
0,0
259
g.s2
R/W
Set gradient relative to SP2
0.0 ...999.9 digit / min ( digit / sec see SP.r )
0,0
Multiset
The MULTISET function determines the local setpoint by selecting the value from Setpoint 1 (SP.1) or from Setpoint 2 (SP.2) based on the state of a digital input or by setting from a serial line. The variation between Setpoint 1 and Setpoint 2 can take place with gradient: parameter G.SP determines the speed for reaching Setpoint 1 and parameter G.S2 defines the speed for reaching Setpoint 2. The MULTISET function is enabled with parameter hd.1 and automatically enables the gradient function. Selection between Setpoint 1 and Setpoint 2 can be seen by means of LED.
191
hd.1
R/W
Enable multiset:
control instruments via serial
0
Multiset table
hd.1 Enable Enable Multiset virtual instrument
0 1 X 2 X 3 X X
SETPOINT CONTROL
AL
Referred to cur-
rent setpoint
Setpoint profile
Setpoint < AL
Delay (parameter HY.n)
Absolute alarm
Reverse alarm
Direct alarm
Time (min. or sec.)
SP1
SP2
SPrem
SP1
(*)
ON
ON
SP
IN1
LOC/REM
t
t
t
(*) if set gradient is set
230
482
SP.1
R/W
Setpoint 1
100
231
483
SP.2
R/W
Setpoint 2
200
Lo.L ... HI.L
Lo.L ... HI.L
Page 48
48 80963B_MSW_GFW_11-2012_ENG
140
diG.
R/W
Digital input function
0
See: Table of digital input functions
618
diG.2
R/W
Digital input function 2
0
See: Table of digital input functions
FUNCTIONAL DIAGRAM
Active setpoint
(SPA)
Local
setpoint
See Controls
SP
Enable
multiset
(Hd.1)
SERIAL_SP
Select
remote
setpoint
(SP.r)
Remote setpoint
(auxiliary analog input)
Select
remote
setpoint
(SP.r)
Remote absolute
setpoint
Remote setpoint relative
to local setpoint
Setpoint
gradients
(G.SP,
G.S2)
+
+
75
bit
SELECT
SP1 / SP2
OFF = Select SP1
ON = Select SP2
R/W
SP.2
SP.1
STATUS_W
dIG
dIG.2
Bit SP1/SP2
SP.1
SP.2
STATUS_W
dIG
dIG.2
Bit LOC/REM
LOC
REM
305*
R/W
State (STATUS_W)
bit 0 ­ 1 Select SP1/SP2 (*) 2 Start/Stop Selftuning (*) 3 Select ON/OFF 4 Select AUTO/MAN 5 Start/Stop Autotuning (*) 6 Select LOC/REM (*)
Table of state settings
(*) only for zone1 (GFW-M)
0
zone1
0
zone20zone3
Page 49
4980963B_MSW_GFW_11-2012_ENG
PID HEAT/COOL CONTROL
The controller can manage a heating output and a cooling output in a completely independent manner. Heating and cooling parameters are described below. Parameters for PID (proportional band, integral and derivative time) control are typically calculated by means of Autotuning and Selftuning functions.
Proportional action: action in which contribution to output is proportional to deviation at input (deviation = difference between controlled variable and setpoint Derivative action: action in which contribution to output is proportional to rate of variation input deviation. Integral action: action in which contribution to output is proportional to integral of time of input deviation.
Control actions
Increasing the proportional band reduces oscillation but increases deviation. Reducing the proportional band reduces deviation but causes oscillation of the controlled variable (excessively low proportional band values make the system unstable). An increase in Derivative Action corresponds to an increase in Derivative Time, reduces deviation, and prevents oscillation up to a critical Derivative Time value, beyond which deviation increases and there are prolonged oscillations. An increase in Integral Action corresponds to a decrease in Integral Time, tends to annul deviation between the controlled variable and the setpoint at rated operating speed. If the Integral Time value is too long (weak Integral Action), there may be persistent deviation between the controlled variable and the setpoint. For more information on control actions, contact GEFRAN.
Proportional, derivative, and integral action
CONTROLS
Control output with only proportional action in case of proportional heating band separate from cooling band.
Control output with only proportional action in case of proportional heating band superimposed on cooling band.
Output with separate band Output with superimposed band
Heat/cool control with separate or superimposed band
This control mode (enabled with parameter Ctr = 14) asks you to specify cooling type. The PID cooling parameters are then calculated based on heating parameters in the ratio specified (ex: C.ME = 1 (oil), H_Pb = 10, H_dt =1, H_It = 4 im­plies: C_Pb = 12.5, C_dt = 1 , C_It = 4) Apply the following values when setting cycle times: Air T Cool cycle = 10 sec. Oil T Cool cycle = 4 sec. Water T Cool cycle = 2 sec.
NB.: Cool parameters cannot be changed in this mode.
PV = process variable SP + cSP = cooling setpoint c_Pb = cooling proportional band
Time
PV
c_Pb
h_Pb
SP+cSP
SP
+100%
Control output
0%
-100%
Time
PV
c_Pb
h_Pb
SP+cSP
SP
+100%
Control output
0%
-100%
PV = process variable SP = heating setpoint h_Pb = heating proportional band
Heat/cool control with relative gain
Page 50
50 80963B_MSW_GFW_11-2012_ENG
180
(tr
R/W
Control type
134
Table of heat/cool controls
Select sample time for derivative action.
+0 sample 1 sec.
+16 sample 4 sec.
+32 sample 8 sec.
+64 sample 240 msec.
+128 No Reset of integral component at setpoint change
Note: the LBA alarm is not enabled in the ON/OFF control.
Val Control type 0 P heat 1 P cool 2 P heat / cool 3 PI heat 4 PI cool 5 PI heat / cool 6 PID heat 7 PID cool 8 PID heat / cool 9 ON-OFF heat 10 ON-OFF cool 11 ON-OFF heat / cool 12 PID heat + ON-OFF cool 13 ON-OFF heat + PID cool 14 PID heat + cool with relative gain (see parameter C.MEd)
PID Parameters
617*
spu
R/W
Reference power
Table of selections
- The reference power of a slave zone in automatic mode is the power of a master zone in automatic or manual mode.
- The reference power of a slave zone in manual mode is the zone manual power.
- Software shutdown remains independent for each zone.
0
zone1
0
zone20zone3
(**) function “slave” zone
SPU 0 Power from analog input (In.A) 1 Power from main input (PV) 2 Power from aux input (In.2) 3 Power from aux input (In.3) 4 Power from aux input (In.4) 5 Power from aux input (In.5) 6 Power from PID (PID_POWER) (**) 7 Power from digital input (In.Pwm) 9 Power from GFW-M (FW_POWER) (**) 10 Power from GFW-E1 (FW_POWER) (**) 11 Power from GFW-E2 (FW_POWER) (**)
513
R/W
Select cooling uid
0 ...2
0
Relative gain (rG)
0 Air 1 1 Oil 0,8 2 Water 0,4
77
c.dt
R/W
Derivative cooling time
0.00 ...99,99 min
1,00
Note: Parameters c.PB, c.It and c.dt are read-only if heat/cool control is enabled with relative gain (Ctr = 14).
6
c.pb
R/W
Proportional band for cooling or hyste-
resis ON/OFF
0 ...999,9% f.s.
1,0
76
c.1t
R/W
Integral cooling time
0.00 ...99,99 min
4,00
2*
132 - 471
0v.p
R
Value of control outputs
(+Heat / -Cool)
(W – only in manual mode at address 252)
Read state
5
148 - 149
h.pb
R/W
Proportional band for heating or hyste-
resis ON/OFF
0 ...999,9% f.s.
1,0
7
150
h.1t
R/W
Integral heating time
0.00 ...99,99 min
4,00
8
151
h.dt
R/W
Derivative heating time
0.00 ...99,99 min
1,00
(.Ae
Page 51
5180963B_MSW_GFW_11-2012_ENG
766*
P.oFS
R/W
Offset of output power
-100,0 ...100,0 %
765*
P..pEr
R/W
Percentage of output power
0.0 ...100,0 %
39
484
c.sp
R/W
Cooling setpoint
relative to heating setpoint
±25.0% f.s.
0,0
78
rst
R/W
Manual reset
(value added to PID input)
-999 ...999
scale points
0
516
p.rs
R/W
Reset power
(value added directly to PID output)
-100,00....
....100,0 %
0,0
79
a.rs
R/W
Antireset
(limits integral action of PID))
0 ...9999
scale points
0
80
ffd
R/W
Feedforward (value added to PID output
after processing)
-100,00....
....100,0 %
0,0
42
146
h.p.x
R/W
Maximum limit
heating power
0.0 ...100,0 %
100,0
254
h.p.L
R/W
Minimum limit heating power
(not available for double heat/cool
action)
0.0 ...100,0 %
0,0
43
c.p.x
R/W
Maximum limit
cooling power
0.0 ...100,0 %
100,0
255
c.p.L
R/W
Minimum limit cooling power (not availa-
ble for double heat/cool action)
0.0 ...100,0 %
0,0
ADVANCED SETTINGS
763*
G.oUt
R/W
Gradient for control output
0,0 ...200,0 %
sec
set to 0 to disable
764*
Lo.P
R/W
Minimum trigger output
0,0 ...50,0 %
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
100,0
zone1
100,0
zone2
100,0
zone3
Page 52
52 80963B_MSW_GFW_11-2012_ENG
FUNCTIONAL DIAGRAM
Process variable
(PV) (*)
Active setpoint
(SPA) (*)
PID
(h.Pb,
h.it, h.dt,
c.SP, c.Pb,
h.b,rSt,A.rS)
(*)
Output
power
limits
(*)
Power limit for Fault
Action (FA.P) (*)
Power limit for LBA
alarm (Lb.P) (*)
Average power for
power alarm (*)
+
-
PID_POWER
A
(*) only for zona 1 (GFW-M)
Power
reference
(SPU)
Analog input
(In.A)
Main input
(PV)
Auxiliary input
(In.2)
Auxiliary input
(In.3)
Auxiliary input
(In.4)
Auxiliary input
(In.5)
Digital input
(In.Pwm)
Power from GFW-M
(FW_POWER)
Power from GFW-E1
(FW_POWER)
Power from GFW-E2
(FW_POWER)
Manual power
MANUAL_POWER
Main input
(PV) (*)
Manual
from
analog
input
(TP.2)
(*)
Auxiliary input
(In.2) (*)
Status_W
diG
diG.2
Bit
ON/OFF
OFF
Ou.P
G.Out
Lo.P
ø
Correction
of output
power
x
+
P.PEr P.oFS
Feedback
Current limits
RMS
A
Status_W
diG
diG.2
Bit
A/M
AUTO
MAN
(*) only for zone 1 (GFW-M)
Analog input
(In.A) (*)
Digital input (In.Pwm) (*)
FW_POWER
Page 53
5380963B_MSW_GFW_11-2012_ENG
AUTOMATIC / MANUAL CONTROL
By means of the digital input function you can set the controller in MAN (manual) and set the control output to a constant value changeable by means of communication. When returning to AUTO (automatic), if the variable is within the proportional band, switching is bumpless.
With this function (available on models with CV diagnostics option), you can run a correction of power delivered in manual based on the reference line voltage (riF). The % value of the (Cor) is freely settable and acts in inverse proportion. The function is activated/deactivated by means of parameter SP.r.
Example: with the following settings: Cor = 10%; riF = 380; SP.r = value + 8; instrument in manual; line voltage 380 VAC, manual power set at 50%, following a 10% increase in line voltage, 380V + 10% (380V) = 418V, there is a decrease in set manual power equal to the same % of change: 50% - 10% (50%) = 45%. To use this function, the controller must have a CT (current transformer) and a VT (voltage transformer). N.B.: the % change in manual power is limited to the value set in parameter “Cor”. The maximum manual power correction is limited to ± 65%.
HOLD FUNCTION
The process variable value and the setpoints remain “frozen” for the time the digital input is active. By activating the digital input with the Hold function when the variable is at values below the setpoint, a setpoint memory reset de-energizes all energized relays and resets all memory latches.
MANUAL POWER CORRECTION
505*
rif
R/W
Line voltage
0.0 ...999,9
Compensation of the voltage transformer read to maintain output power at a constant level.
506*
(or
R/W
Correction of manual power based on
line voltage
0,0 ...100,0 %
1*
bit
AUTO/MAN
OFF = Automatic
ON =Manual
R/W
2*
132 - 471
0v.p
R
Value of control outputs
(+Heat / -Cool)
(W – only in manual mode at address 252)
140
diG.
R/W
Digital input function
0
See: Table of digital input functions
618
diG.2
R/W
Digital input function 2
0
140
diG.
R/W
Digital input function
0
See: Table of digital input functions
618
diG.2
R/W
Digital input function 2
0
64
bit
HOLD
OFF = Disable hold
ON = Enable hold
R/W
18
136 - 249
SP.r
R/W
Remote setpoint
(SET gradient for manual power
correction)
0
Type of remote set Absolute/Deviation 0 Digital (from serial line) Absolute 1 Digital (from serial line) Deviation local set (_SP o SP1 o SP2) 2 Auxiliary input Absolute 3 Auxiliary input Deviation set (_SP o SP1 o SP2) +4 set gradient in digit/sec. +8 correction of manual power based on line voltage +16 disable saving of local setpoint _SP +32 disable saving of local manual power (at switch-off returns to last value saved)
Setpoint table
305*
R/W
State (STATUS_W)
See: Table of state settings
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0
zone1
0
zone20zone3
252*
R/W
MANUAL_POWER
-100,0...100,0%
0,0
zone1
0,0
zone2
0,0
zone3
Page 54
54 80963B_MSW_GFW_11-2012_ENG
AUTOTUNING
Enabling the autotuning function blocks the settings of the PID parameters. Autotuning continues to measure the system oscillations, seeking as quickly as possible the PID parameter values that reduce the oscillation; it does not intervene if the oscillations drop to values below 1.0% of the proportional band. It is interrupted if the setpoint is changed, and resumes automatically with a constant setpoint. The calculated parameters are not saved; if the instrument is switched off the controller resumes with the parameters programmed before autotuning was enabled. Autotuning terminates the procedures with switching to manual.
Enabling the autotuning function blocks the settings of the PID parameters. It can be two types: continuous or one shot.
Continuous autotunìng is enabled with parameter Stu (values 1, 3, 5); it continues to measure the system oscillations, seeking as quickly as possible the PID parameter values that reduce the oscillation; it does not intervene if the oscillations drop to values below 1.0% of the proportional band. It is interrupted if the setpoint is changed, and resumes automatically with a constant setpoint. The calculated parameters are not saved if the instrument is switched off, in case of switching to manual or disabling the code in configuration, and controller resumes with the parameters programmed before autotuning was enabled. The calculated parameters are saved when the function is enabled via digital input or via A/M key (start /stop) at stop.
One-shot autotuning can be activated manually or automatically with parameter Stu (as can be seen on the table, the values to be set depend on enabling of Selftuning or Softstart). It is useful for calculating PID parameters when the system is in the vicinity of the setpoint; it produces a variation on the control output of a maximum of ± 100% of the current control power limited by h.PH - h.PL (heat), c.PH - c.PL (cool) and assesses the effects in overshoot over time. The calculated parameters are saved. Manual activation (code Stu = 8, 10, 12) by setting the parameter directly or via digital input or key. Automatic activation (code Stu = 24, 26, 28 with error range of 0.5%) when the PV-SP error exceeds the defined range (programmable at 0.5%, 1%, 2%, 4% of full scale).
Activation is inhibited if PV <5% or PV >95% of input scale.
NB: at switch-on after selftuning, after switching to MANUAL, after software shutdown or after a setpoint change, automatic activation is inhibited for an interval equal to five times the integral time, with a minimum of 5 minutes. An identical interval has to lapse after a one-shot run.
MANUAL TUNING
Process variable
Time
T
Peak
A) Enter the setpoint at its working value. B) Set the proportional band at 0.1% (with on-off type setting). C) Switch to automatic and observe the behavior of the varia­ble. It will be similar to that in the figure: D) The PID parameters are calculated as follows: Proportional band
Peak P.B.= ---------------------------------------- x 100 V max - V min
(V max - V min) is the scale range. Integral time It = 1,5 x T Derivative time dt = It/4 E) Switch the controller to manual, set the calculated parame­ters (activate the PID control by setting a cycle time for relay outputs, if any), switch to automatic. F) To assess parameter optimization, change the setpoint value if possible and check temporary behavior. If oscillation persists, increase the value of the proportional band; if respon­se is too slow, decrease the value.
See: CONTROL - PID Parameters
See: CONTROL - PID Parameters
Page 55
5580963B_MSW_GFW_11-2012_ENG
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
0
Autotuning Selftuning Softstart continuous
0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 5 YES NO YES 6 Autotuning One-shot 8* WAIT NO NO 9 GO NO NO 10* WAIT YES NO 11 GO YES NO 12* WAIT NO YES 13 GO NO YES
Selftuning, autotuning, softstart table
(*) +16 with automatic switching in GO if PV-SP > 0.5% f.s. +32 with automatic switching in GO if PV-SP > 1% f.s. +64 with automatic switching in GO if PV-SP > 2% f.s. +128 with automatic switching in GO if PV-SP > 4% f.s.
140
diG.
R/W
Digital input function
0
See: Table of digital input functions
618
diG.2
R/W
Digital input 2 function
0
29
bit
AUTOTUNING
OFF = Stop Autotuning
ON = Start Autotuning
R/W
28
bit
AUTOTUNING STATE
OFF = Autotuning in Stop
ON = Autotuning in Start
R
68
bit
DIGITAL INPUT 1
OFF = Digital input 1 off ON = Digital input 1 on
R
92
bit
DIGITAL INPUT 2
OFF = Digital input 2 off ON = Digital input 2 on
R
See: Table of digital input functions
Read state
296
R
Autotuning and selftuning
enable state (FLG_PID)
bit 3 Selftuning on 4 Softstart on 6 Autotuning on
305*
R/W
State (STATUS_W)
bit 0 ­ 1 Select SP1/SP2 (*) 2 Start/Stop Selftuning (*) 3 Select ON/OFF 4 Select AUTO/MAN 5 Start/Stop Autotuning (*) 6 Select LOC/REM (*)
Table of state settings
(*) only for zone1 (GFW-M)
0
zone1
0
zone20zone3
Page 56
56 80963B_MSW_GFW_11-2012_ENG
The procedure runs automatically until termination. At termination, the new PID parameters are saved: proportional band, integral and derivative times calculated for the current action (heat or cool). In case of double action (heat + cool), the parameters for the opposite action are calculated by maintaining the initial ratio between the parameters (example: Cpb = Hpb * K; where K = Cpb / Hpb when selftuning is started). At termination, the Stu code is automatically cancelled. Note: The procedure does not start if temperature exceeds the setpoint for heat control, or is below the setpoint for cool control. In this case, the Stu code is not cancelled. It is advisable to enable the LEDs to signal selftuning state. By setting parameter Ld.St = 4 on the Hrd menu, the appropriate LED will light up or flash when selftuning is active.
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
0
Selftuning, autotuning, softstart table
140
diG.
R/W
Function digital input
0
See: Table of digital input functions
618
diG.2
R/W
Digital input 2 function
0
68
bit
STATE OF DIGITAL
INPUT 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
STATE OF DIGITAL
INPUT 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
See: Table of digital input functions
Read state
0
bit
SELFTUNING STATE
OFF = Selftuning in Stop
ON = Selftuning in Start
R
3
bit
SELFTUNING
OFF = Selftuning in Stop
ON = Selftuning in Start
R/W
SELFTUNING
This function is valid for single-action (either heat or cool) systems and for double-action (heat/cool) systems. Selftuning is activated to calculate the best control parameters when starting the process. The variable (example: temperature) must be the one assumed at zero power (room temperature). The controller supplies the maximum power set until reaching an intermediate point between starting value and the setpoint, then resets power. The PID parameters are calculated by evaluating superelongation and the time needed to reach the peak (N.B.: This action is not considered in ON/OFF control). When the function is completed, it disengages automatically, and the control proceeds to reach the setpoint.
Peak
T
S.P.
t.a.
Time
Process variable
S.P. - t.a.
2
Selftuning
How to activate selftuning: A. Activation at switch-on
1. Set the setpoint to the desired value.
2. Enable selftuning by setting parameter Stu to 2
3. Switch off the instrument.
4. Make sure that temperature is near room temperature.
5. Switch on the instrument.
B. Activation via serial command
1. Make sure that temperature is near room temperature.
2. Set the setpoint to the desired value.
3. Run the Start Selftuning command.
see: CONTROLS - PID parameters
296
R
Autotuning and selftuning enable state
(FLG_PID)
bit 3 Selftuning on 6 Autotuning on
305*
R/W
Instrument state (STATUS_W)
See: Table of instrument settings
Autotuning Selftuning Softstart continuous
0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 5 YES NO YES 6 Autotuning One-shot 8* WAIT NO NO 9 GO NO NO 10* WAIT YES NO 11 GO YES NO 12* WAIT NO YES 13 GO NO YES
(*) +16 with automatic switching in GO if PV-SP > 0.5% f.s. +32 with automatic switching in GO if PV-SP > 1% f.s. +64 with automatic switching in GO if PV-SP > 2% f.s. +128 with automatic switching in GO if PV-SP > 4% f.s.
Page 57
5780963B_MSW_GFW_11-2012_ENG
SOFTSTART
If enabled, this function partializes power based on a percentage of time elapsed since instrument switch-on compared to the set time of 0.0 ... 500.0 min (“SoFt” parameter CFG phase). Softstart is an alternative to selftuning and is activated after each instrument switch-on. Softstart is reset when switching to manual.
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
0
Selftuning, autotuning, softstart table
263
SP.S
R/W
Softstart setpoint
(preheating hot runners)
100
Read state
63
bit
STATE SOFTSTART
OFF = NO Active Softstart
ON = Active Softstar
R
START MODE
699*
P.ONT
R/W
Start modes at Power-On
0* Function at previous state 1 Software shutdown 2 Software startup
(*) digital input states always have priority
30
bit
RESTART
SOFTSTART
OFF = ON = Restart of Softstart
R/W
0
zone1
0
zone20zone3
Autotuning Selftuning Softstart continuous
0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 5 YES NO YES 6 Autotuning One-shot 8* WAIT NO NO 9 GO NO NO 10* WAIT YES NO 11 GO YES NO 12* WAIT NO YES 13 GO NO YES
(*) +16 with automatic switching in GO if PV-SP > 0.5% f.s. +32 with automatic switching in GO if PV-SP > 1% f.s. +64 with automatic switching in GO if PV-SP > 2% f.s. +128 with automatic switching in GO if PV-SP > 4% f.s.
Page 58
58 80963B_MSW_GFW_11-2012_ENG
SOFTWARE SHUTDOWN
Running the software shutdown procedure causes the following:
1) Reset of Autotuning, Selftuning and Softstart.
2) Digital input enabled only if assigned to SW shutdown function.
3) In case of switch-on after SW shutdown, any ramp for the set (set gradient) starts from the PV.
4) Outputs OFF: except for signals them of reference rL.4 and rL.6 that they come forced ON
5) Reset of HB alarm.
6) Reset of LBA alarm.
7) The Heat and Cool bit on the state word STATUS and POWER are reset.
8) At shutdown, the current power is saved. At switch-on, integral power is recalculated as the difference between saved power and proportional power; this calculation is defined as “desaturation at switch-on.”
9) In case of Geflex, the state of alarms (AL1...AL4, ALHBTA1...ALHBTA3) is reset.
9) Alarms AL 1… AL 4 can be enable or disable through the parameter oFF.t.
68
bit
STATE of DIGITAL
INPUT 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
STATE of DIGITAL
INPUT 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
See: Table of digital input functions
140
diG.
R/W
Digital input function
0
See: Table of digital input functions
618
diG.2
R/W
Digital input 2 function
11
bit
SOFTWARE LAUNCH/
SHUTDOWN
OFF = On software
ON =Off software
R/W
Read state
305*
R/W
Instrument (STATUS_W)
0
See: Table of state settings
700
OFF.T
R/W
Modes at software shutdown
0
0 Outputs rL.1- rL.2 - rL.3 - rL.5 = OFF Outputs rL.4 - rL.6 = ON Alarms AL.1 -AL.2 -AL.3 - AL.4 disabled
1 Outputs rL.1- rL.2 - rL.3 - rL.5 = OFF Outputs rL.4 - rL.6 = ON Alarms AL.1 -AL.2 -AL.3 - AL.4 enabled
+16 restart softstart (if enabled) at software relaunch
Page 59
5980963B_MSW_GFW_11-2012_ENG
FAULT ACTION POWER
You can decide what power to supply in case of broken probe.
FAP is the reference power for parameter FAP.
Average power is the average power calculated in the last 300 sec.
The alarm reset and reference power update take place only at switch-on or after a setpoint change.
The alarm is not activated if the control (Ctr) is ON/OFF type, during Selftuning and in Manual.
OTHER FUNCTIONS
POWER ALARM
The alarm signals any power changes (OuP) after the process variable (PV) has stabilized on the setpoint (SP). The
time beyond which the process variable is considered stable is 300 sec.
The reference power update take place only at switch-on or after a setpoint change.
If the process variable leaves the stabilization band after the first stabilization, this does not influence the alarm.
In case of SBR:
- if the PV has not yet stabilized, either the average power over the last 5 minutes or FAP power is supplied (depending on
the setting of the HOT parameter).
- if the PV has stabilized the average power over the last 5 minutes is supplied.
Function:
If necessary, assign an output (rL.2...6) for the power alarm.
Set the band (b.ST) within which the process variable is considered stable after 300 sec. have elapsed.
Set the band (b.PF) outside which the alarm is activated after time PF.t has elapsed.
The reference power is the active power after 300 sec. have elapsed.
The alarm reset and reference power update take place only at switch-on or after a setpoint change.
265
xot
R/W
Select special functions
0
See: Hot runners table - Setpoint Settings
Read state
26*
bit
STATE OF HB ALARM
OR POWER_FAULT
OFF = Alarm off
ON = Alarm on
R
228
fa.p
R/W
Fault action power (supplied in
conditions of broken probe)
-100,0 ..100,0 %
0,0
80
bit
State of power alarm
OFF = Alarm off
ON = Alarm on
R
Page 60
60 80963B_MSW_GFW_11-2012_ENG
261
b.st
R/W
Stability band
(alarm power function)
0,0 ...
.....100,0 % f.s.
0,0
262
b.pf
R/W
Alarm power band
(alarm power function)
0,0 ...100,0 %
0,0
260
pf.t
R/W
Delay time for alarm power activation
0 ...999 sec
0
160*
rL.1
R/W
Allocation of reference signal
See: Generic alarms –Table of reference signals
163*
rL.2
R/W
Allocation of reference signal
166*
rL.3
R/W
Allocation of reference signal
- OR Output
170*
rL.4
R/W
Allocation of reference signal
- AND Output
171*
rL.5
R/W
Allocation of reference signal
- OR Output
172*
rL.6
R/W
Allocation of reference signal
- AND Output
The parameters for alarm power are:
The alarm is not activated if the control (Ctr) is ON/OFF type, during Selftuning and in Manual.
5 min.
PF.t
SP
SP + b.St
SP - b.St
Average power + b.PF
Alarm power
Average power
Power
ON
Average power - b.PF
Process
variable
0
zone1
0
zone20zone3
1
zone1
1
zone21zone3
2
zone1
2
zone22zone3
35
zone1
35
zone235zone3
4
zone1
4
zone24zone3
160
zone1
160
zone2
160
zone3
Page 61
6180963B_MSW_GFW_11-2012_ENG
Power
Process
variable
SP
SP S
t.a.
SoP
Controller in open loop
Controller in closed loop
SoF
Read state
63
bit
STATE OF SOFTSTART
OFF = Softstart in Stop
ON = Softstart in Start
R
147
SOF
R/W
Softstart time
0.0 ...500,0 min
0,0
263
SP.S
R/W
Softstart setpoint
100
264
SO.P
R/W
Softstart power
-100,00....
....100,0 %
0,0
SOFTSTART FOR PREHEATING
This function lets you deliver a settable power (So.P) for time (SoF), after which normal control is resumed by means of PID control. Activation is only at switch-on, with manual-automatic switching during Softstart (the time restarts from 0), and if the process variable is below setpoint SP.S.
From SW version 2.02:
With softstart time SoF = 0, preheat condition PV <SP.S with settable power SO.P is continuously checked.
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
0
Selftuning, autotuning, softstart table
HEATING OUTPUT (Fast cycle)
For outputs rL.1 (Out 1) and rL.2 (Out 2) you can set a fast cycle time (0.1 ... 20,0 sec) by setting the parameter to 64 (Heat) or 65 (Cool).
160*
rL.1
R/W
Allocation of reference signal
See: Generic alarms -Table of reference signals
163*
rL.2
R/W
Allocation of reference signal
0
zone1
0
zone20zone3
1
zone1
1
zone21zone3
Autotuning Selftuning Softstart continuous
0 NO NO NO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4 NO NO YES 5 YES NO YES 6 Autotuning One-shot 8* WAIT NO NO 9 GO NO NO 10* WAIT YES NO 11 GO YES NO 12* WAIT NO YES 13 GO NO YES
(*) +16 with automatic switching in GO if PV-SP > 0.5% f.s. +32 with automatic switching in GO if PV-SP > 1% f.s. +64 with automatic switching in GO if PV-SP > 2% f.s. +128 with automatic switching in GO if PV-SP > 4% f.s.
Lo.L...HI.L
Page 62
62 80963B_MSW_GFW_11-2012_ENG
SSR CONTROL MODES
ON Modality
The GFW has the following power control modes:
- PA modulation via variation of phase angle
- ZC, BF, HSC modulation via variation of number of conduction cycles with zero crossing trigger. PA phase angle: this mode controls power on the load via modulation of the phase angle. ZC zero crossing: this type of operation reduces EMC emissions. This mode controls power on the load via a series of conduction ON and non conduction OFF cycles. The cycle time is constant and can be set from 1 to 200 sec (or from 0.1 to 20.0 sec).
BF burst ring: this mode controls power on the load via a series of conduction ON and non conduction OFF cycles. The ratio of the number
of ON cycles to OFF cycles is proportional to the power value to be supplied to the load. The repeat period or cycle time is kept to a minimum for each power value.
Parameter bF.Cy denes the minimum number of conduction cycles, settable from 1 to 10.
In case of 3-phase load without neutral or closed delta, BF.Cy >= 5 has to be set to ensure correct operation (balancing of current in the 3 loads).
HSC Half Single Cycle: this mode corresponds to a BF that includes ON and OFF half-cycles. It is useful for reducing icker with short-wave
IR loads (and is applied only to single-phase or 3-phase with neutre or open delta loads).
Start mode is set with parameter Hd.5 Control of maximum rms current (whose value is set in parameter Fu.tA) can always be enabled with parameter Hd.5 in every power-on mode. The cycle time can be set with two different resolutions in seconds or tenths of a second based on the type of heat or cool function assigned to outputs rL1 and rL2. The use of short cycle times (< 2-3 sec) is always recommended in case of control with SSRs.
POWER CONTROL
703*
xd.5
R/W
Enable trigger modes
Table of trigger modes
+ 32 only for ZC/BF modes: enable delay triggering + 64 linear phase Softstart in power +128 phase Softstart for IR lamps + 256 phase Softstart for shutdown in software ON/OFF switching
Settings
Trigger mode in nor-
mal operation (*)
Phase angle PA
(Phase Angle)
Full wave
Variable cycle time ZC (zero crossing)
Variable cycle time
BF (Burst Firing)
Set: Ct = 0
Slow
set:
0,1<CT<20,0
sec
Fast
set:
0,1<CT<20,0
sec
rL.1 = +64
HSC
(Half Single Cycle)
Ramp of Softstart
Trigger
mode in
normal
operation (*)
rigger
BF
mode
RMS in
softstart
Current
control in
normal
operation
0 NO ZC/BF - NO
NO
1 YES ZC/BF - NO
NO 2 NO PA - NO NO 3 YES PA - NO NO 4 NO ZC/BF HSC NO NO 5 YES ZC/BF HSC NO NO 6 NO PA - NO NO 7 YES PA - NO NO 8 NO ZC/BF - YES NO 9 YES ZC/BF - YES NO
10 NO PA - YES NO 11 YES PA - YES NO 12 NO ZC/BF HSC YES NO 13 YES ZC/BF HSC YES NO 14 NO PA - YES NO 15 YES PA - YES NO 16 NO ZC/BF - NO YES 17 YES ZC/BF - NO YES 18 NO PA - NO YES 19 YES PA - NO YES 20 NO ZC/BF HSC NO YES 21 YES ZC/BF HSC NO YES 22 NO PA - NO YES 23 YES PA - NO YES 24 NO ZC/BF - YES YES 25 YES ZC/BF - YES YES 26 NO PA - YES YES 27 YES PA - YES YES 28 NO ZC/BF HSC YES YES 29 YES ZC/BF HSC YES YES 30 NO PA - YES YES 31 YES PA - YES YES
141
zone1
141
zone2
141
zone3
DIP 5 = OFF (Resistive load)
32
zone1
32
zone232zone3
DIP 5 = ON (Inductive load)
Page 63
6380963B_MSW_GFW_11-2012_ENG
DELAY TRIGGERING
In ring modes ZC and BF, with inductive loads, this function inserts delay triggering in the rst cycle.
The delay is expressed in degrees settable in parameter dL.t, from 0 to 90 degrees. The function is enabled with parameter Hd.5 (+32). The function activates automatically if there are OFF conditions for a time exceeding the one settable in dL.oF (if =0 the fun­ction is as if disabled).
Optimised Delay-Triggering value for transformer: 60°
◊ Optimised Delay-Triggering value for 3-phase transformer: 90°, 90°, 60°
708*
DL.T
R/W
Delay triggering
(rst trigger only)
738*
DL.oF
R/W
Minimum non-conduction time to
reactivate delay triggering
NB: In case of a 3-phase load, you can set a different value from parameter PS.tA for each zone (ex. to control an unbalanced 3-phase load).
SOFTSTART or START RAMP
This type of start can be enabled either in phase control or pulse train mode and acts via control of the conduction angle. It is enabled with parameter Hd.5. The softstart ramp starts from a zero conduction angle and reaches the angle set in parameter PS.HI in the time set in parameter PS.tm, from 0.1 to 60.0 sec.
With parameter Hd.5 (+64), you can congure a linear softstart in power, i.e., starting from zero you reach the power
value corresponding to the maximum conduction angle set in PS.HI. Softstart ends before the set time if power reaches the corresponding value set in manual control or calculated by PID. Control of maximum peak current can be enabled with parameter Hd.5 during the ramp phase; peak value is settable
in parameter PS.tA. This function is useful in case of short circuit on the load of loads with high temperature coefcients to automatically adjust start time to the load. The softstart ramp activates at the rst start after power-ON and after a software reboot. It can be reactivated via
software control by writing bit 108 or automatically if there are OFF conditions for a time exceeding the one settable in PS.oF (if =0 the function is as if disabled). The ramp can also be enabled with parameter Hd.5 (+256) after a software shutdown, i.e., zero is reached in the set time from delivered power.
630*
PS.xI
R/W
maximum phase of phase softstart ramp
705*
R/W
Duration of phase softstart ramp
629*
PS.of
R/W
Minimum non-conduction time to reacti-
vate phase softstart ramp
706*
PS.ta
R/W
Maximum peak current limit during
phase softstart ramp
108*
bit
OFF = Restart not enabled
ON = Restart enabled
R/W
Restart of phase
softstart ramp
NB: In case of a 3-phase load, you can set a different value from parameter FU.tA for each zone (ex. to control an unbalanced 3-phase load).
707*
FU.tA
R/W
Max. limit of RMS current in normal op
0,0 ...999,9 A
704*
bF.Cy
R/W
Min. number of cycles in BF mode
1 ...10
Model
40A 60A 100A 150A 200A 250A
Default zone 1...3
40,0 60,0 100,0 150,0 200,0 250,0
PS.tn
R
0.0 ...100,0 %
0.1 ...60,0 s
0 ...999 s
0.0 ...999,9 A
100,0
zone1
100,0
zone2
100,0
zone3
10,0
zone1
10,0
zone2
10,0
zone3
2
zone1
2
zone22zone3
106*
bit
State of phase
softstart ramp
R
OFF = Ramp not active
ON = Ramp active
107*
bit
State of phase softstart ramp
R
OFF = Ramp not ended
ON = Ramp ended
0 ... 90 °
0 ... 10000ms
60
zone1
60
zone260zone3
10
zone1
10
zone210zone3
Model 40A 60A 100A 150A 200A 250A
Default zone 1...3 110,0 170,0 280,0 420,0 560,0 700,0
1
zone1
1
zone21zone3
DIP 5 = OFF (Resistive load)
5
zone1
5
zone25zone3
DIP 5 = ON (Inductive load)
Page 64
64 80963B_MSW_GFW_11-2012_ENG
FEEDBACK MODES
The GFW has the following power control modes: V-voltage V
2
-squared voltage I-current I
2
-squared current P-power A control mode is enabled with parameter Hd.6.
Voltage feedback (V) To keep voltage on the load constant, this compensates possible variations in line voltage with reference to the rated voltage saved in riF.V. (expressed in Vrms). The voltage value maintained on the load is (ref.V*P%_pid_man/100) and is indicated in the Modbus 757 register.
Voltage feedback (V
2
)
To keep voltage on the load constant, this compensates possible variations in line voltage with reference to the rated voltage saved in riF.V. (expressed in Vrms). The voltage value maintained on the load is (rif.V*
V (P%_pid_man/100)), and is indicated in the Modbus 757 register.
Current feedback (I) To keep current on the load constant, this compensates possible variations in line voltage and/or variations in load impedance with reference to the rated current saved in riF.I. (expressed in Arms). The current value maintained on the load is (rif.I*P%_pid_man/100), and is indicated in the Modbus 757 register.
Current feedback (I
2
)
To keep current on the load constant, this compensates possible variations in line voltage and/or variations in load impedance with reference to the rated current saved in riF.I. (expressed in Arms). The current value maintained on the load is (rif.I*
V (P%_pid_man/100)), and is indicated in the Modbus 757 register.
Power feedback P
To keep power on the load constant, this compensates both variations in line voltage and variations in load impedance with reference to the rated power saved in riF.P. (expressed in kWatt). The current value maintained on the load is (rif.P*P%_pid_man/100), and is indicated in the Modbus 757 register.
IMPORTANT!
Feedback calibration can be activated from the digital input (parameters DIG and DIG.2) or by serial control (ref. bit113), and if requested MUST be activated only with Hd.6=0 (the required Hd.6 value can be set only after calibration) and preferably with maximum power on the load (ex. P_man or P_pid at 100%). If you change function mode (PA, ZC, BF, HSC), you have to re-run the Feedback calibration procedure.
Voltage V (or current I or power P) feedback corrects the % of conduction with a maximum settable value in parameter Cor. V (or Cor.I or Cor.P).
For non-linear loads (ex.: Super Kanthal or Silicon Carbide) the automatic calibration procedure is NOT NECESSARY. Set the value of parameters ref.V, ref. I, ref. P based on the specic nominal of the load shown on the data-sheet (ref. GFW In­stallation Guide).
Page 65
6580963B_MSW_GFW_11-2012_ENG
730*
xd.6
R/W
Enable feedback modes Table of feedback modes
0.0 ...100,0 %
Feedback ON
0 None 1 V2 (Voltage) 2 I
2
(Current) 3 P (Power) 4 None 5 V (Linear voltage) 6 I (Linear current)
731*
COR.V
R/W
Maximum correction of voltage feedback
0.0 ...100,0 %
732*
COR.i
R/W
Maximum correction of current feedback
0.0 ...100,0 %
733*
COR.p
R/W
Maximum correction of power feedback
0.0 ...999,9 V
734*
Rif.V
R/W
Voltage feedback reference
0.0 ...999,9 A
735*
Rif.i
R/W
Current feedback reference
0.0 ...99,99 kW
736*
Rif.p
R/W
Power feedback reference
113*
bit
Calibration of voltage
feedback reference
R/W
OFF = Calibration not enabled
ON = Calibration enabled
NOTE: For other information see the hardware manual
READ STATE
757*
ARif
R
Reference of Feedback
0
zone1
0
zone20zone3
100,0
zone1
100,0
zone2
100,0
zone3
100,0
zone1
100,0
zone2
100,0
zone3
100,0
zone1
100,0
zone2
100,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0,0
zone1
0,0
zone2
0,0
zone3
0.0 ...999,9 V
Setpoint of V, I, P to maintain
on load
0.0 ...999,9 A
0.0 ...99,99 kW
741*
fb.It
R/W
Feedback response speed
0.1 ...5,0
% / 60msec
0,3
zona1
0,3
zona2
0,3
zona3
Page 66
66 80963B_MSW_GFW_11-2012_ENG
This function acts by enabling the control to search for the most appropriate input combinations.
Example 1: 4 loads 380V- 32A (zone 1), 16A (zone 2), 25A (zone 3), 40A (maximum current is 73A in case of simultaneity of conduction). Current limit I.HEU=50A. The following combinations of conduction are possible:
(to dene the number of combinations, remember that the
combinations without repetitions are = n! / (k!*(n-k)!) ) I1+I2 = 48A I1+I3 = 57A I2+I3 = 41A I1+I2+I3 = 73A
The combinations corresponding to current values below the limit value are: I1+I2 = 48A I2+I3 = 41A The one with lower current is given by zone 2 and zone 3.
In the single cycle time for the enabled zones, the delivery of power may be reduced to respect the maximum current limit. The time distribution for activation of the zones is calculated at the start of each cycle: Ptot = P1+ P2 (if P2>P3) + P3 (if P3>P2) Simultaneity is allowed for zones 2 and 3.
If P1= 100%, P2= 100%, P3= 100% Ptot=200%; since Ptot>100%, the conduction time of the zone x is obtained by Px * (100/Ptot) P1,2,3 delivered = 100%*0.5 = 50%
If P1= 100%, P2= 50%, P3= 0% Ptot=150%; since Ptot>100%, the conduction time of the zone x is obtained by Px * (100/Ptot) P1 delivered = 100%*0.66 = 67% P2 delivered = 50%*0.66 = 33% P3 delivered = 0%*0.66 = 0%
ON Zone 1 ON Zone 2 / 3
Cycle time
ON Zone 1 ON Zone 2
Cycle time
HEURISTIC CONTROL POWER
It is useful to be able to limit the delivery of total power to the loads in order to avoid input peaks from the single-phase power line. This condition occurs during switch-on phases when the machine is cold; the demand for heating power is 100% until temperatures near the setpoint are reached. It is also useful to avoid simultaneity of conduction when there is ON-OFF modulation for temperature maintenance. The cycle time must be identical for all zones; the power percentage for each zone is limited to that necessary to
maintain current within set limits.
Page 67
6780963B_MSW_GFW_11-2012_ENG
HETEROGENEOUS POWER CONTROL
This function matches that of a thermal cutout that disconnects the load based on instantaneous input. The load is disconnected based on a preset priority.
Zone 1 has priority: in case of overload, zone 3 is disconnected, followed by zone 2, etc.
683
I.XET
R/W
Maximum current for heterogeneous
power control
0,0
682
hd.4
R/W
Enable heterogeneous
power control
0
Table for enabling heterogeneous power
681
I.XEU
R/W
Maximum current for heuristic power
control
0,0
680
hd.3
R/W
Enable heuristic
power control
0
NOTE: Only for GFW with CTs present and outputs OUT1...OUT3 with slow cycle time (1...200sec)
Table for enabling heuristic power
ZONE 1 ZONE 2 ZONE 3 0 3 X X 5 X X 6 X X 7 X X X
ZONE 1 ZONE 2 ZONE 3
0 1 X 2 X 3 X X 4 X 5 X X 6 X X 7 X X X
0.0 ...999,9 A
0.0 ...999,9 A
Page 68
68 80963B_MSW_GFW_11-2012_ENG
Virtual instrument control is activated by means of parameter hd.1. By setting parameters S.In and S.Ou you can enable the writing of some parameters via serial line, set the value of inputs and the state of outputs. You have to enable alarm setpoints AL1, ..., AL4 when write operations are continuous, and you don’t have to keep the last value in eeprom. Enabling the PV input means being able to exclude the local Tc or RTD acquisition and replace it with the value written in the register VALUE_F. Enabling digital input IN lets you set the state of this input, for example to run MAN/AUTO switching with the writing of bit 7 in the register V_IN_OUT. Likewise, you can set the on/off state of outputs OUT1, ..., OUT10 and of the LEDs by writing bits in the register V_IN_OUT.
191
hd.1
R/W
Enable multiset
instrument control via serial
0
Table for multiset/ virtual instrument
Enable Enable Multiset virtual instrument
0 1 X 2 X 3 X X
VIRTUAL INSTRUMENT CONTROL
224
s.In
R/W
Control inputs from serial
0 ... 255
225
s.0v
R/W
Control outputs from serial
0 ... 1023
0
Outputs Out10 Out9 Out8 Out7 Out6 Out5 Out4 Out3 Out2 Out1
Bit 9 8 7 6 5 4 3 2 1 0
628
s.LI
R/W
Control LEDs and digital inputs from
serial
0 ... 1023
0
Input LED D2 D1 out4 out3 out2 out1 DI2 DI1 ER RN
Bit 9 8 7 6 5 4 3 2 1 0
Parameter bit Resource enabled Address of Format Name of register image register S.In 0 (**) Alarm setpoint AL1 341 word AL1_RAM (**) 1 (**) Alarm setpoint AL2 342 word AL2_RAM (**) 2 (**) Alarm setpoint AL3 343 word AL3_RAM (**) 3 (**) Alarm setpoint AL4 321 word AL4_RAM (**) 4 Input In.1 347 word SERIAL_IN1 (**) 6 (**) Input In.2 348 word SERIAL_IN2 (**) 7 (**) Input In.3 578 word SERIAL_IN3 (**) 8 (**) Input In.4 579 word SERIAL_IN4 (**) 9 (**) Input In.5 580 word SERIAL_IN5 (**) 10 (**) Input In.A 581 word SERIAL_INA (**)
S.Ou 0 Output OUT 1 344 word, bit 0 V_IN_OUT 1 Output OUT 2 344 word, bit 1 V_IN_OUT 2 Output OUT 3 344 word, bit 2 V_IN_OUT 4 Output OUT 5 (relays) 344 word, bit 4 V_IN_OUT 4 Output OUT 5 (continuous) 639 word SERIAL_OUT5C* 5 Output OUT 6 (relays) 344 word, bit 5 V_IN_OUT 5 Output OUT 6 (continuous) 640 word SERIAL_OUT6C* 6 Output OUT 7 (relays) 344 word, bit 6 V_IN_OUT 6 Output OUT 7 (continuous) 641 word SERIAL_OUT7C* 7 Output OUT 8 (relays) 344 word, bit 7 V_IN_OUT 7 Output OUT 8 (continuous) 642 word SERIAL_OUT8C* 8 Output OUT 9 344 word, bit 8 V_IN_OUT 9 Output OUT 10 344 word, bit 9 V_IN_OUT
S.LI 0 Led RN 351 word, bit 0 V_X_LEDS 1 Led ER 351 word, bit 1 V_X_LEDS 2 Led D1 351 word, bit 2 V_X_LEDS 3 Led D2 351 word, bit 3 V_X_LEDS 4 Led O1 351 word, bit 4 V_X_LEDS 5 Led O2 351 word, bit 5 V_X_LEDS 6 Led O3 351 word, bit 6 V_X_LEDS 7 Led O4 351 word, bit 7 V_X_LEDS 8 Input D1 344 word, bit 10 V_IN_OUT 9 Input D2 344 word, bit 11 V_IN_OUT
Table of virtual register addresses
0
zone1
0
zone20zone3
Inputs In.A In.5 In.4 In.3 In.2 - In.1 AL4 AL3 AL2 AL1
Bit 10 9 8 7 6 5 4 3 2 1 0
Page 69
6980963B_MSW_GFW_11-2012_ENG
HW/SW INFORMATION
The following data registers can be used to identify the controller HW/SW and check its operation.
122
UPD
R
Software version code
606
Er.2
R
Self-diagnosis
error code for auxiliary input 2
0 No Error 1 Lo (process variable value < Lo.S) 2 Hi (process variable value > Hi.S) 3 ERR [third wire interrupted for PT100 or input values below minimum limits (ex. for TC with connection error)] 4 SBR (probe interrupted or input values beyond maximum limits)
85
Err
R
Self-diagnosis
error code for main input
Table of main input errors
508
(.xd1
R Hardware configuration codes 1
bit 0 = 1 INPUT AUX absent 1 = 1 INPUT AUX TC / 60mV 2 -
3 = 1 FIELDBUS ETH4 (ProNet)
4 = 1 FIELDBUS ETH5 5 = 1 FIELDBUS ETH6 6 = 1 FIELDBUS absent 7 = 1 FIELDBUS Modbus
8 = 1 FIELDBUS Probus
9 = 1 FIELDBUS CanOpen 10 = 1 FIELDBUS DeviceNet 11 = 1 FIELDBUS Ethernet 12 = 1 FIELDBUS Euromap66 13 = 1 FIELDBUS ETH3 14 = 1 FIELDBUS ETH2 (Ethercat) 15 = 1 FIELDBUS ETH1 (Ethernet IP)
Table of hardware conguration codes 1
190
(.xd
R Hardware configuration codes
bit 0 = 1 COOL OUTPUT absent 1 = 1 COOL OUTPUT relay 2 = 1 COOL OUTPUT logic 3 = 1 COOL OUTPUT continuous 0...20mA / 0...10V 4 = 1 COOL OUTPUT triac 250Vac 1A 5 ­ 6 = GFW-M no power 7 = 1 GFW-M 40A 8 = 1 GFW-M 60A 9 = 1 GFW-M 100A 10 = 1 GFW-M 150A 11 = 1 GFW-M 200A 12 = 1 GFW-M 250A 13 = 1 GFW-M El.Fuse
Table of hardware conguration codes
550
Er.3
R
Self-diagnosis
error code for auxiliary input 3
551
Er.4
R
Self-diagnosis
error code for auxiliary input 4
552
Er.5
R
Self-diagnosis
error code for auxiliary input 5
543
(.xd2
R Hardware configuration codes 2
bit 0 = 1 GFW-E1 no power 1 = 1 GFW-E1 40A 2 = 1 GFW-E1 60A 3 = 1 GFW-E1 100A 4 = 1 GFW-E1 150A 5 = 1 GFW-E1 200A 6 = 1 GFW-E1 250A 7 = 1 GFW-E1 El. Fuse 8 = 1 GFW-E2 no power 9 = 1 GFW-E2 40A 10 = 1 GFW-E2 60A 11 = 1 GFW-E2 100A 12 = 1 GFW-E2 150A 13 = 1 GFW-E2 200A 14 = 1 GFW-E2 250A 15 = 1 GFW-E2 El. Fuse
Table of hardware conguration codes 2
Page 70
70 80963B_MSW_GFW_11-2012_ENG
693 697
Upd.F
R Fieldbus software version
695
Cod.F
R Fieldbus node
696
bAu.F
R Fieldbus baudrate
346
R Jumper
bit OFF ON
0 State jumper S1 1 State jumper S2 2 State jumper S7-1: (*) 3 State jumper S7-2: (*) 4 State jumper S7-3: (*) 5 State jumper S7-4: (*) 6 State jumper S7-5: resistive load inductive load 7 State jumper S7-6: - Conguration parameters
of default
8 State jumper S7-7: GFX4/GFW Simulation 4 GFX
Table of jumper states
197
Ld.st
R/W
RN LED status function
16
Val. Function 0 RUN 1 MAN/AUTO controller 2 LOC / REM 3 HOLD 4 Selftuning on 5 Autotuning on 6 Repeat digital input INDIG1 7 Serial 1 dialog 8 State of OUT 2 zone 1 9 Softstart running 10 Indication of SP1...SP2 (SP1 with pilot input inactive and LED off) 11 Repeat digital input INDIG2 12 Input in error (LO, Hi, Err, Sbr) 13 Serial 2 dialog 14 Repeat digital input INDIG3
+ 16 LED ashing if active (code 8 excluded)
Table of LED functions
619
Ld.2
R/W
ER LED status function
12
620
Ld.3
R/W
Function of LED DI1
6
621
Ld.4
R/W
Function of LED DI2
11
622
Ld.s
R/W
Function of LED O1
1
0 Disabled 1 Repetition of state OUT 1 2 Repetition of state OUT 2 3 Repetition of state OUT 3 4 State key
5 Repetition of state OUT 5
6 Repetition of state OUT 6 7 Repetition of state OUT 7 8 Repetition of state OUT 8 9 Repetition of state OUT 9 10 Repetition of state OUT 10
+ 16 LED ashing if active
Table of OUT LED functions
623
Ld.6
R/W
Function of LED O2
2
624
Ld.7
R/W
Function of LED O3
3
625
Ld.8
R/W
Function of LED Button
4
120
R
Manufact - Trade Mark (Gefran)
5000
121
R
Device ID (GFW)
214
Name of manufacturer
Product ID
Profibus
bAu.F baudrate
0 12.00 Mbit/s
1 6.00 Mbit/s
2 3.00 Mbit/s
3 1.50 Mbit/s
4 500.00 Kbit/s
5 187.50 Kbit/s
6 93.75 Kbit/s
7 45.45 Kbit/s
8 19.20 Kbit/s
9 9.60 Kbit/s
Canopen
bAu.F baudrate
0 1000 Kbit/s
1 800 Kbit/s
2 500 Kbit/s
3 250 Kbit/s
4 125 Kbit/s
5 100 Kbit/s
6 50 Kbit/s
7 20 Kbit/s
8 10 Kbit/s
Devicenet
bAu.F baudrate
0 125 Kbit/s
1 250 Kbit/s
2 500 Kbit/s
Ethernet
bAu.F baudrate
0 100 Mbit/s
1 10 Mbit/s
S7- 1 S7- 2 S7- 3 S7- 4 (*) FUNCTION MODES OFF OFF OFF OFF 3 single-phase loads OFF ON OFF OFF 3 independent single-phase loads in open delta ON ON OFF OFF 3-phase load open delta / star with neutral ON ON ON OFF 3-phase load closed delta ON OFF OFF ON 3-phase star load without neutral ON OFF OFF OFF 3-phase star load without neutral with BIFASE control ON OFF ON OFF 3-phase closed star load with BIFASE control
Page 71
7180963B_MSW_GFW_11-2012_ENG
305*
R/W
bit 0 ­ 1 Select SP1/SP2 (*) 2 Start/Stop Selftuning (*) 3 Select ON/OFF 4 Select AUTO/MAN 5 Start/Stop Autotuning (*) 6 Select LOC/REM (*)
Table of state settings
467*
R
State (STATUS)
bit 0 AL.1 or AL.2 or AL.3 or AL.4 or ALHB.TA1 or ALHB.TA2 or ALHB.TA3 or Power Fault 1 Input Lo 2 Input Hi 3 Input Err 4 Input Sbr 5 heat 6 cool 7 LBA 8 AL.1 9 AL.2 10 AL.3 11 AL.4 12 ALHB or Power Fault 13 ON/OFF 14 AUTO/MAN 15 LOC/REM
Table of state
Current state (STATUS_W)
698*
R
State saved in eeprom
(STATUS_W_EEP)
LED status refers to the corresponding parameter, with the following special cases:
- LED RN (green) on: hotkey functionality
- LED RN (green) + LED ER (red) both ashing rapidly: autobaud in progress
- LED ER (red) on: error in one of main inputs (Lo, Hi, Err, Sbr)
- LED ER (red) ashing: temperature alarm ((OVER_HEAT or TEMPERATURE_SENSOR_BROKEN) or alarm of SHORT_CIRCUIT_CURRENT or SSR_SAFETY or FUSE_OPEN (only for singlephase conguration).
- LED ER (red) + LED Ox (yellow) both ashing: HB alarm or POWER_FAIL in zone x
- All LEDs ashing rapidly: ROTATION123 alarm (only for threephase conguration)
- All LEDs ashing rapidly except LED DI1: jumper conguration not provided
- All LEDs ashing rapidly except LED DI2: 30%_UNBALANCED_ERROR alarm (only for threephase conguration)
- All LEDs ashing rapidly except LED O1: SHORT_CIRCUIT_CURRENT alarm (only for threephase conguration)
- All LEDs ashing rapidly except LED O2: TRIPHASE_MISSING_LINE_ERROR alarm (only for threephase conguration)
- All LEDs ashing rapidly except LED O3: SSR_SAFETY alarm (only for threephase conguration)
- All LEDs ashing rapidly except LED BUT: FUSE_OPEN alarm (only for threephase conguration)
469*
R
State 1 (STATUS1)
bit 0 AL.1 or AL.2 or AL.3 or AL.4 or ALHB.TA1 or ALHB.TA2 or ALHB.TA3 or Power Fault 1 Input Lo 2 Input Hi 3 Input Err 4 Input Sbr 7 LBA 8 AL.1 9 AL.2 10 AL.3 11 AL.4 12 ALHB.TA1 13 ALHB.TA2 14 ALHB.TA3 15 Selftuning on
Table of state 1
632*
R
State 2 (STATUS2)
bit 0 AL.1 1 AL.2 2 AL.3 3 AL.4 4 AL.HB1 5 AL.HB2 6 AL.HB3 7 AL.Lo 8 AL.Hi 9 AL.Err 10 AL.Sbr 11 AL.LBA 12 AL.Power
Table of state 2
(*) only for zone 1 (GFW-M)
0
zone1
0
zone20zone3
0
zone1
0
zone20zone3
Page 72
72 80963B_MSW_GFW_11-2012_ENG
633
R
State 3 (STATUS3)
Table of state 3
634
R
State 4 (STATUS4)
Table of state 4
702
R
Voltage status
Table of voltage status
Functionality key
bit 0 Temperature sensor broken 1 over heat 2 phase_softstart_active 3 phase_softstart_end 4 frequency_warning or monophase_missing_line_warning 5 60Hz 6 short_circuit_current in softstart di fase 7 over_peak_current in softstart di fase 8 over_rms_current a regime 9 SSR_Safety (24V fan presence or SSR hardware over temperature) 10 Fuse open 11 Current polarity check
12 over_peak_current_projection in softstart di fase
bit 0 frequency_warning 1 10% unbalanced_line_warning 2 20% unbalanced_line_warning 3 30% unbalanced_line_warning 4 rotation123_error 5 three-phase_missing_line_error 6 60Hz
bit 3 AL.SSR short 1 4 AL.SSR short 2 5 AL.SSR short 3 6 No voltage 1 7 No voltage 2 8 No Voltage 3 9 No current 1 10 No current 2 11 No current 3
(*) with key pressed, the state of the RN and BUT LEDs is steadily on; the LEDs switch off after 2/3 seconds to indicate switching to ready state. Example: To activate calibration of the HB alarm, keep the key pressed for 3 seconds, release the key and then press it again for another 3 seconds.
LED RN (green) ashing
LED BUT (yellow) off
Key
pressed
> 3 sec (*)
Key
pressed
> 3 sec (*)
Key
pressed
> 3 sec (*)
Key pressed
> 1 sec (*)
Key pressed
> 1 sec (*)
Normal
operation
LED RN (green) steadily on
LED BUT (yellow) 1 ash
every second.
Ready for
calibration HB alarm
LED RN (green) ashing
rapidly
LED BUT (yellow) ashing
rapidly
Calibration HB alarm
LED RN (green) ashing
rapidly
LED BUT (yellow) ashing
rapidly
Reset PF alarms
with latch
LED RN (green) steadily on
LED BUT (yellow) 2 ashes
every second
Presetting for reset
PF alarms with latch
LED RN (green) off
LED BUT (yellow) off
Reset FUSE_OPEN/SHORT_
CIRCUIT_CURRENT alarms
Monophase conguration
LED RN (green) ashing LED ER (red) ashing LED BUT (yellow) off
3-phase conguration
All LEDs ash rapidly except for
LED BUT (yellow) FUSE_OPEN alarm or LED 01 (yellow) SHORT_CIRCUIT_CURRENT alarm
FUSE_OPEN /
SHORT_CIRCUIT_CURRENT alarms
Key
pressed
> 2 sec (*)
Page 73
7380963B_MSW_GFW_11-2012_ENG
PARAMETERS
INSTRUMENT CONFIGURATION SHEET
627
par.2
R/W
Select parity - Serial 2
626
bav.2
R/W
Select Baudrate - Serial 2
47
par
R/W
Select parity - Serial 1
45
baV
R/W
Select Baudrate - Serial 1
Denitionofparameter Note
Assigned
value
INSTALLATION OF MODBUS SERIAL NETWORK
46
(od
R
Device identification code
403
dP.S
R/W Decimal point position for input scale
401
Lo.S
R/W Minimum scale limit for main input
402
xi.S
R/W Maximum scale limit for main input
519
23
ofs.
R/W Main input offset correction
400
tYP.
R/W
Probe, signal, enable, custom
linearization and main input scale
MAIN INPUT PID
ANALOG INPUT
24
flt
R/W low pass digital filter for input signal
179
fld
R/W Digital filter on oscillations of input signal
86
S.00
R/W
Engineering value attributed to Point 0
(minimum value of input scale)
87
S.01
R/W Engineering value attributed to Point 1
0
470
P. V.
R
Read of process variable (PV)
engineering value
85
Err
R Self-diagnosis error code for main input
573
tP.A
R/W
analog input
574
LS.A
R/W
Minimum scale limit
analog input
577
oFS.A
R/W Offset correction for analog input
576
Flt.A
R/W
Low pass digital filter
analog input
572
In.A
R
Value of the ingegneristico reading
analog input
575
kS.A
R/W
Maximum scale limit
analog input
349
DPV
R
Read of engineering value of
process variable (PV) filtered by FLd
88
S.02
R/W Engineering value attributed to Point 2
89
S.03
R/W Engineering value attributed to Point 3
Page 74
74 80963B_MSW_GFW_11-2012_ENG
117
S.31
R/W Engineering value attributed to Point 31
90
S.04
R/W Engineering value attributed to Point 4
91
S.05
R/W Engineering value attributed to Point 5
92
S.06
R/W Engineering value attributed to Point 6
93
S.07
R/W Engineering value attributed to Point 7
94
S.08
R/W Engineering value attributed to Point 8
95
S.09
R/W Engineering value attributed to Point 9
96
S.10
R/W Engineering value attributed to Point 10
97
S.11
R/W Engineering value attributed to Point 11
98
S.12
R/W Engineering value attributed to Point 12
99
S.13
R/W Engineering value attributed to Point 13
100
S.14
R/W Engineering value attributed to Point 14
101
S.15
R/W Engineering value attributed to Point 15
102
S.16
R/W Engineering value attributed to Point 16
103
S.17
R/W Engineering value attributed to Point 17
104
S.18
R/W Engineering value attributed to Point 18
105
S.19
R/W Engineering value attributed to Point 19
106
S.20
R/W Engineering value attributed to Point 20
107
S.21
R/W Engineering value attributed to Point 21
108
S.22
R/W Engineering value attributed to Point 22
109
S.23
R/W Engineering value attributed to Point 23
110
S.24
R/W Engineering value attributed to Point 24
111
S.25
R/W Engineering value attributed to Point 25
112
S.26
R/W Engineering value attributed to Point 26
113
S.27
R/W Engineering value attributed to Point 27
114
S.28
R/W Engineering value attributed to Point 28
115
S.29
R/W Engineering value attributed to Point 29
116
S.30
R/W Engineering value attributed to Point 30
Page 75
7580963B_MSW_GFW_11-2012_ENG
LOAD CURRENT VALUE
295
S.35
R/W
Engineering value of input signal
corresponding to temperature of 50°C.
294
S.34
R/W
Engineering value attributed to
maximum value of the input scale.
293
S.33
R/W
Engineering value attributed to minimum
value of the input scale
118
S.32
R/W
Engineering value attributed to Point 32
(maximum value of input scale))
220*
o.tA1
R/W
Offset correction CT input
(phase 1)
415
o.tA2
R/W
Offset correction CT input
(phase 2)
416
o.tA3
R/W
Offset correction CT input
(phase 3)
227*
473 - 139
I.ta1
R
Instantaneous CT input value
(phase 1)
490
I.ta2
R
Instantaneous CT input value
(phase 2)
491
I.ta3
R
Instantaneous CT input value
(phase 3)
219*
FT.TA
R/W
CT input digital filter (phases 1, 2 and 3)
468*
I.1oN
R
CT input value with output on
(phase 1)
498
I.2oN
R
CT input value with output on
(phase 2)
499
I.3oN
R
CT input value with output on
(phase 3)
754
Ld.A.t
R
Current on 3-phase load
709*
I.tAP
R
Peak ammeter input during phase
softstart ramp
716*
CoS.F
R
Power factor in hundredths
753*
Ld.A
R
Current on load
VALUE OF LOAD VOLTAGE
751*
LD.U
R
Voltage on load
752
LD.U.T
R
Voltage on 3-phase load
With 3-phase load
With 3-phase load
With 3-phase load
With 3-phase load
748
L.ta3
R
Minimum limit of CT ammeter
input scale (phase 3)
With 3-phase load
414
k.ta3
R
Maximum limit of CT ammeter
input scale (phase 3)
With 3-phase load
747
L.ta2
R
Minimum limit of CT ammeter
input scale (phase 2)
With 3-phase load
413
k.ta2
R
Maximum limit of CT ammeter
input scale (phase 2)
With 3-phase load
746*
L.ta1
R
Minimum limit of CT ammeter
input scale (phase1)
405*
k.ta1
R
Maximum limit of CT ammeter
input scale (phase 1)
Page 76
76 80963B_MSW_GFW_11-2012_ENG
LINE VOLTAGE VALUE
411*
o.tU1
R/W
Offset correction voltmeter transformer
input TV (phase 1)
419
o.tU2
R/W
Offset correction voltmeter transformer
input TV (phase 2)
With 3-phase load
420
o.tU3
R/W
Offset correction voltmeter transformer
input TV (phase 3)
With 3-phase load
412*
FT.TU
R/W
Digital filter TV auxiliary input
(phase 1, 2, 3)
492
1.tU2
R
Voltmeter input value (phase 2)
493
1.tU3
R
Voltmeter input value (phase 3)
232*
485
1.tU1
R
Voltmeter input value (phase 1)
496
1.UF2
R
Value filtered Voltmeter input (phase 2)
497
1.UF3
R
Value filtered Voltmeter input (phase 3)
322*
1.UF1
R
Value filtered Voltmeter input (phase 1)
315*
FrEq
R
Voltage frequency in tenths of Hz
POWER ON LOAD
720
LD.P.T
R
Power on 3-phase load
749*
LD.I
R
Impedance on load
719*
LD.P
R
Power on load
750
LD.I.T
R
Impedance on 3-phase load
With 3-phase load
With 3-phase load
With 3-phase load
With 3-phase load
455
L.t 3
R
Minimum limit of TV voltmeter
input scale (phase 3)
With 3-phase load
418
k.t 3
R
Maximum limit of CT voltmeter
input scale (phase 3)
With 3-phase load
454
L.t 2
R
Minimum limit of TV voltmeter
input scale (phase 2)
With 3-phase load
417
k.t 2
R
Maximum limit of TV voltmeter
input scale (phase 2)
With 3-phase load
453*
L.t 1
R
Minimum limit of TV voltmeter
input scale (phase1)
410*
k.t 1
R
Maximum limit of TV voltmeter
input scale (phase 1)
531*
Ld.E1
R
Energia sul carico
541
Ld.E1.t
R
Energia sul carico trifase
510*
Ld.E2
R
Energia sul carico
541
Ld.E2.t
R
Energia sul carico trifase
114*
bit
Azzeramento
Ld.E1
R/W
OFF = ­ON = Azzeramento Ld.E1
115*
bit
Azzeramento
Ld.E2
R/W
OFF = ­ON = Azzeramento Ld.E2
Page 77
7780963B_MSW_GFW_11-2012_ENG
603
XS.2
R/W
Maximum limit auxiliary input scale 2
605
oFS.2
R/W
Offset correction for auxiliary input 2
602
In.2
R
Value of auxiliary input 2
606
Er.2
R
Error code for self-diagnosis
of auxiliary input 2
559
XS.3
R/W
Maximum limit of auxiliary input scale 3
560
XS.4
R/W
Maximum limit of auxiliary input scale 4
561
XS.5
R/W
Maximum limit of auxiliary input scale 5
565
oFS.3
R/W
Offset for auxiliary input correction 3
566
oFS.4
R/W
Offset for auxiliary input correction 4
567
oFS.5
R/W
Offset for auxiliary input correction 5
547
In.3
R
Value of auxiliary input 3
548
In.4
R
Value of auxiliary input 4
549
In.5
R
Value of auxiliary input 5
550
Er.3
R
Error code for self-diagnosis
of auxiliary input 3
551
Er.4
R
Error code for self-diagnosis
of auxiliary input 4
552
Er.5
R
Error code for self-diagnosis
of auxiliary input 5
556
LS.3
R/W
Minimum limit of auxiliary input scale 3
557
LS.4
R/W
Minimum limit of auxiliary input scale 4
558
LS.5
R/W
Minimum limit of auxiliary input scale 5
404
LS.2
R/W
Minimum limit auxiliary input scale
AUXILIARY ANALOG INPUTS (LIN/TC)
194
AI.2
R/W
Select type of auxiliary input sensor 2
181
tp.2
R/W
Definition of auxiliary analog input
function 2
677
dP.2
R/W
Decimal point position for auxiliary input
scale 2
553
AI.3
R/W
Select type of auxiliary sensor input 3
554
AI.4
R/W
Select type of auxiliary sensor input 4
555
AI.5
R/W
Select type of auxiliary sensor input 5
568
dP.3
R/W
Decimal point position for the auxiliary
input scale 3
569
dP.4
R/W
Decimal point position for the auxiliary
input scale 4
570
dP.5
R/W
Decimal point position for the auxiliary
input scale 5
604
FLt.2
R/W
Digital filter for auxiliary input 2
562
FLt.3
R/W Digital filter for auxiliary input 3
Page 78
78 80963B_MSW_GFW_11-2012_ENG
GENERIC ALARMS AL1, AL2, AL3 and AL4
215
a1.r
R/W
Select reference variable alarm 1
216
A2.r
R/W
Select reference variable alarm 2
217
A3.r
R/W
Select reference variable alarm 3
218
A4.r
R/W
Select reference variable alarm 4
12
475 - 177
AL.1
R/W
Setpoint alarm 1 (scale points)
13
476 - 178
AL.2
R/W
Setpoint alarm 2 (scale points)
14
52 - 479
AL.3
R/W
Setpoint alarm 3 (scale points)
58
480
AL.4
R/W
Setpoint alarm 4 (scale points)
27
187
XY.1
R/W
Hysteresis for alarm 1
30
188
XY.2
R/W
Hysteresis for alarm 2
53
189
XY.3
R/W
Hysteresis for alarm 3
59
XY.4
R/W
Hysteresis for alarm 4
406
a1.t
R/W
Alarm type 1
407
A2.t
R/W
Alarm type 2
408
54
A3.t
R/W
Alarm type 3
409
A4.t
R/W
Alarm type 4
46
bit
AL1 direct/inverse R/W
47
bit
AL1 absolute/relative R/W
48
bit
AL1 normal/symmetrical R/W
49
bit
AL1 disabled at switch on R/W
50
bit
AL1 with memory R/W
DIGITAL INPUTS
140
diG.
R/W
Function of digital input
618
diG.2
R/W
Function of digital input 2
68
bit
STATE OF DIGITAL
INPUT 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
STATE OF DIGITAL
INPUT 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
317
R
State of digital inputs INPUT DIG
563
FLt.4
R/W Digital filter for auxiliary input 4
564
FLt.5
R/W Digital filter for auxiliary input 5
694
diG.3
R/W
Digital input 3 function
67
bit
STATE of DIGITAL
INPUT 3
OFF = Digital input 3 off
ON = Digital input 3 on
R
518
In.PWM R
PWM input value
Page 79
7980963B_MSW_GFW_11-2012_ENG
26
21 - 29 - 143
xI.L
R/W
Highest settable limit SP, SP
remote and absolute alarms
195*
AL.n
R/W
Select number of enabled alarms
140
diG.
R/W
Digital input function
618
diG.2
R/W
Digital input function 2
70
bit
AL4 direct/inverse R/W
71
bit
AL4 absolute/relative R/W
72
bit
AL4 normal/symmetrical R/W
73
bit
AL4 disabled at switch on R/W
74
bit
AL4 with memory R/W
4
bit
STATE OF
ALARM 1
OFF = Alarm off
ON = Alarm on
R
5
bit
STATE OF
ALARM 2
OFF = Alarm off
ON = Alarm on
R
62
bit
STATE OF
ALARM 3
OFF = Alarm off
ON = Alarm on
R
69
bit
STATE OF
ALARM 4
OFF = Alarm off
ON = Alarm on
R
318
R
States of alarm ALSTATE IRQ
79
bit
Reset alarm latch R/W
LBA ALARM (Loop Break Alarm)
195*
AL.n
R/W
Select number of enabled alarms
44
Lb.t
R/W
Delay time for LBA alarm activation
119
Lb.p
R/W
Limit of supplied power in presence of
LBA alarm
8
bit
STATE OF LBA ALARM
OFF = LBA off
ON = LBA alarm on
R
81
bit
Reset LBA alarm R/W
25
20 - 28 - 142
Lo.L
R/W
Lowest settable limit SP, SP remote and absolute alarms
54
bit
AL2 direct/inverse R/W
55
bit
AL2 absolute/relative R/W
56
bit
AL2 normal/symmetrical R/W
57
bit
AL2 disabled at switch on R/W
58
bit
AL2 with memory R/W
36
bit
AL3 direct/inverse R/W
37
bit
AL3 absolute/relative R/W
38
bit
AL3 normal/symmetrical R/W
39
bit
AL3 disabled at switch on R/W
40
bit
AL3 with memory R/W
Page 80
80 80963B_MSW_GFW_11-2012_ENG
759*
Ir..tA.1
R/W
HB Calibration with IR lamp: current at
50% conduction
758*
Ir..tA.0
R/W
HB Calibration with IR lamp: current at
100% conduction
743*
xb.Pw
R/W
Ou.P power in calibration
742*
xb.tA
R/W
CT read in HB calibration
760*
Ir.tA.2
R/W
HB Calibration with IR lamp: current at
30% conduction
761*
Ir.tA.3
R/W
HB Calibration with IR lamp: current at
20% conduction
HB ALARM (Heater Break Alarm)
57*
Xb.f
R/W
HB alarm function
195*
AL.n
R/W
Select number of enabled alarms
55*
A.xb1
R/W
HB alarm setpoint (ammeter input scale
points - Phase 1)
56*
XB.T
R/W
Delay time for HB alarm activation
502
A.xb2
R/W
HB alarm setpoint (ammeter input scale
points - Phase 2)
With three-phase load
737*
xb.P
R/W
Percentage HB alarm setpoint of current
read in HB calibration
452*
xb.t
R/W TV read in HB calibration
767*
Ir.tA.4
R/W
HB Calibration with IR lamp:
current at 15% conduction
768*
Ir.tA.5
R/W
HB Calibration with IR lamp:
current at 10% conduction
769*
Ir.tA.6
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 5% conduction
112*
bit
Calibration HB alarm
setpoint
OFF = Calibration not enabled
ON = Calibration enabled
R/W
445*
Ir.t .0
R/W
HB Calibration with IR lamp: voltage at 100% conduction
446*
Ir.t .1
R/W
HB Calibration with IR lamp:
voltage at 50% conduction
447*
Ir.t .2
R/W
HB Calibration with IR lamp:
voltage at 30% conduction
448*
Ir.t .3
R/W
HB Calibration with IR lamp:
voltage at 20% conduction
450*
Ir.t .5
R/W
HB Calibration with IR lamp:
voltage at 10% conduction
449*
Ir.t .4
R/W
HB Calibration with IR lamp:
voltage at 15% conduction
503
A.xb3
R/W
HB alarm setpoint (ammeter input scale
points - Phase 3)
With three-phase load
382*
Ir.tA.7
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 3% conduction
383*
Ir.tA.8
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 2% conduction
384*
Ir.tA.9
R/W
HB Calibration with IR lamp
(only in mode PA):
current at 1% conduction
Page 81
8180963B_MSW_GFW_11-2012_ENG
451*
Ir.t .6
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 5% conduction
390*
Ir.t .7
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 3% conduction
391*
Ir.t .8
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 2% conduction
392*
Ir.t .9
R/W
HB Calibration with IR lamp
(only in mode PA):
voltage at 1% conduction
ALARM SBR - ERR (Probe in short or connection error)
229
rEL
R/W
Fault action (in case of broken probe)
Sbr, Err Only for main input
228
fa.p
R/W
Fault action power
(supplied in condition of broken probe)
9
bit
STATE OF INPUT IN SBR
OFF = -
ON = Input in SBR
R
85
Err
R Self-diagnosis error code for main input
26*
bit
STATE OF HB ALARM or
POWER_FAULT
OFF = Alarm off
ON = Alarm on
R
76*
bit
State of HB alarm
phase 1TA
OFF = Alarm off
ON = Alarm on
R
77
bit
State of HB alarm
phase 2TA
OFF = Alarm off
ON = Alarm on
R
78
bit
State of HB alarm
phase 3TA
OFF = Alarm off
ON = Alarm on
R
512*
R
States of alarm ALSTATE
(for single-phase loads)
504
R
States of alarm HB ALSTATE_HB
(for 3-phase loads)
744*
xb.tr
R
HB alarm setpoint as function of
power on load
318*
R
State of alarms ALSTATE IRQ
Page 82
82 80963B_MSW_GFW_11-2012_ENG
Power Fault ALARMS (SSR_SHORT, NO_VOLTAGE and NO_CURRENT)
660*
hd.2
R/W
Enable POWER_FAULT alarms
661
dg.t
R/W
Refresh rate
SSR-SHORT
662*
dg.f
R/W
Time lter for alarms
NO_VOLTAGE and NO_CURRENT
98
bit
State of alarm
SSR_SHORT phase 3
OFF = Alarm off
ON = Alarm on
R
99*
bit
State of alarm
NO_VOLTAGE phase 1
OFF = Alarm off
ON = Alarm on
R
100
bit
State of alarm
NO_VOLTAGE phase 2
OFF = Alarm off
ON = Alarm on
R
101
bit
State of alarm
NO_VOLTAGE phase 3
OFF = Alarm off
ON = Alarm on
R
102*
bit
State of alarm
NO_CURRENT phase 1
OFF = Alarm off
ON = Alarm on
R
103
bit
State of alarm
NO_CURRENT phase 2
OFF = Alarm off
ON = Alarm on
R
104
bit
State of alarm
NO_CURRENT phase 3
OFF = Alarm off
ON = Alarm on
R
105
bit
Reset SSR_SHORT / NO_
VOLTAGE / NO_CUR-
RENT alarms
R/W
97
bit
State of alarm
SSR_SHORT phase 2
OFF = Alarm off
ON = Alarm on
R
96*
bit
State of alarm
SSR_SHORT phase 1
OFF = Alarm off
ON = Alarm on
R
With 3-phase load
With 3-phase load
With 3-phase load
With 3-phase load
With 3-phase load
With 3-phase load
ALARM due to overload
655*
R
INNTC_SSR
534*
R
INNTC_LINE
535*
R
INNTC_LOAD
456
fr.n
R/W
Number of replay in case of
FUSE_OPEN / SHORT_
CIRCUIT_CURRENT
109*
bit
FUSE_OPEN / SHORT_
CIRCUIT_CURRENT
RESET ALARMS
R/W
OFF = - ON = Alarms reset FUSE_OPEN / SHORT_CIRCUIT_CURRENT
634*
R
State 4 (STATUS4)
FUSE_OPEN AND SHORT_CIRCUIT_CURRENT ALARMS
Page 83
8380963B_MSW_GFW_11-2012_ENG
OUTPUTS
160*
rL.1
R/W
Allocation of reference signal
163*
rL.2
R/W
Allocation of reference signal
166*
rL.3
R/W
Allocation of reference signal
170*
rL.4
R/W
Allocation of reference signal
171*
rL.5
R/W
Allocation of reference signal
172*
rL.6
R/W
Allocation of reference signal
616
ovt.10
R/W
Allocation of physical output OUT 10
615
ovt.9
R/W
Allocation of physical output OUT 9
607
ovt.1
R/W
Allocation of physical output OUT 1
608
ovt.2
R/W
Allocation of physical output OUT 2
609
ovt.3
R/W
Allocation of physical output OUT 3
611
ovt.5
R/W
Allocation of physical output OUT 5
612
ovt.6
R/W
Allocation of physical output OUT 6
613
ovt.7
R/W
Allocation of physical output OUT 7
614
ovt.8
R/W
Allocation of physical output OUT 8
12*
bit
STATE rL.1
OFF = Signal off
ON = Signal on
R
13*
bit
STATE rL.2
OFF = Signal off
ON = Signal on
R
14*
bit
STATE rL.3
OFF = Signal off
ON = Signal on
R
15*
bit
STATE rL.4
OFF = Signal off
ON = Signal on
R
16*
bit
STATE rL.5
OFF = Signal off
ON = Signal on
R
17*
bit
STATE rL.6
OFF = Signal off
ON = Signal on
R
82
bit
State of output OUT1
OFF = Output off
ON = Output on
R
83
bit
State of output OUT2
OFF = Output off
ON = Output on
R
84
bit
State of output OUT3
OFF = Output off
ON = Output on
R
85
bit
State of output OUT4
OFF = Output off
ON = Output on
R
86
bit
State of output OUT5
OFF = Output off
ON = Output on
R
87
bit
State of output OUT6
OFF = Output off
ON = Output on
R
88
bit
State of output OUT7
OFF = Output off
ON = Output on
R
89
bit
State of output OUT8
OFF = Output off
ON = Output on
R
308*
319
R
State rL.x (MASKOUT_RL)
152*
9
(t.1
R/W
OUT 1 (Heat) cycle time
159*
(t.2
R/W
OUT 2 (Cool) cycle time
Page 84
84 80963B_MSW_GFW_11-2012_ENG
SETPOINT SETTING
181
tp.2
R/W
Auxiliary analog input function
138
16 - 472
sp
R/W
Local setpoint
18
136 - 249
SP.r
R/W
Remote setpoint (SET Gradient for
manual power correction)
25
20 - 28 - 142
Lo.L
R/W
Lowest settable limit SP, SP remote and
absolute alarms
26
21 - 29 - 143
xI.L
R/W
Highest settable limit SP, SP remote and
absolute alarms
10
bit
LOCAL / REMOTE
OFF = Enable local setpoint
ON = Enable remote setpoint
R/W
305*
R/W
State (STATUS_W)
SETPOINT CONTROL
234
22
g.sp
R/W
Set Gradient
259
g.s2
R/W
Set Gradient for SP2
265
xot
R/W
Select special functions
191
hd.1
R/W
Enable multiset instrument
control via serial
230
482
SP.1
R/W
Setpoint 1
231
483
SP.2
R/W
Setpoint 2
140
diG.
R/W
Digital input function
618
diG.2
R/W
Digital input function 2
75
bit
SELECT
SP1 / SP2
OFF = Select SP1
ON = Select SP2
R/W
305*
R/W
State (STATUS_W)
1
137 - 481
spa
R Active setpoint
4
R
Deviation (SPA - PV)
90
bit
State of output OUT9
OFF = Output off
ON = Output on
R
91
bit
State of output OUT10
OFF = Output off
ON = Output on
R
664
R State outputs (MASKOUT_OUT)
Page 85
8580963B_MSW_GFW_11-2012_ENG
766*
P.oFS
R/W
Offset of output power
765*
P..pEr
R/W
Percentage of output power
PID HEAT/ COOL CONTROL
617*
spu
R/W
Power reference
180
(tr
R/W
Control type
5
148 - 149
h.pb
R/W
Proportional band for heating or
hysteresis ON/OFF
7
150
h.1t
R/W
Integral heating time
8
151
h.dt
R/W
Derivative heating time
6
c.pb
R/W
Proportional band for cooling or
hysteresis ON/OFF
76
c.1t
R/W
Integral cooling time
77
c.dt
R/W
Derivative cooling time
513
(.Me
R/W
Select cooling uid
152
9
(t.1
R/W
Cycle time OUT 1 (Heat)
159
(t.2
R/W
Cycle time OUT 2 (Cool)
2*
132 - 471
0v.p
R
Value control outputs
(+Heat / -Cool)
39
484
c.sp
R/W
Cooling setpoint relative to heating
setpoint
78
rst
R/W
Manual reset
(value added to PID input)
516
p.rs
R/W
Reset power
(value added directly to PID output)
79
a.rs
R/W
Antireset
(limits integral PID action)
80
ffd
R/W
Feedforward (value added to PID output
after processing)
42
146
h.p.x
R/W
Maximum limit heating power
254
h.p.L
R/W
Min. limit heating power (not available
for double action heat/cool)
43
c.p.x
R/W
Maximum limit cooling power
255
c.p.L
R/W
Min. limit cooling power (not available
for double action heat/cool)
763*
G.oUt
R/W
Gradient for output control
764*
Lo.P
R/W
Uscita minima di innesco
Page 86
86 80963B_MSW_GFW_11-2012_ENG
AUTOMATIC/MANUAL CONTROL
140
diG.
R/W
Digital input function
2*
132 - 471
0v.p
R
Value control outputs
(+Heat / -Cool)
140
diG.
R/W
Digital input function
618
diG.2
R/W
Digital input function 2
1*
bit
AUTO/MAN
OFF = Automatic
ON =Manual
R/W
305*
R/W
State (STATUS_W)
618
diG.2
R/W
Digital input function 2
64
bit
HOLD
OFF = hold off
ON = hold on
R/W
505*
rif
R/W
Line voltage
506*
(or
R/W
Manual power correction based on line
voltage
18
136 - 249
SP.r
R/W
Remote setpoint (SET Gradient for
power correction
HOLD FUNCTION
MANUAL POWER CORRECTION
AUTOTUNING
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
140
diG.
R/W
Digital input function
618
diG.2
R/W
Digital input function 2
29
bit
AUTOTUNING
OFF = Stop Autotuning
ON = Start Autotuning
R/W
305*
R/W
State (STATUS_W)
92
bit
DIGITAL INPUT
STATE 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
296
R
Enable autotuning and selftuning state
(FLG_PID)
68
bit
DIGITAL INPUT
STATE 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
28
bit
AUTOTUNING STATE
OFF = Autotuning in Stop
ON = Autotuning in Start
R
252*
R/W
MANUAL_POWER
Page 87
8780963B_MSW_GFW_11-2012_ENG
SELFTUNING
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
140
diG.
R/W
Digital input function
618
diG.2
R/W
Digital input function 2
3
bit
SELFTUNING
OFF = Stop Selftuning
ON = Start selftuning
R/W
305*
R/W
State (STATUS_W)
68
bit
DIGITAL INPUT
STATE 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
DIGITAL INPUT
STATE 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
0
bit
SELFTUNING STATE
OFF = Selftuning in Stop
ON = Selftuning in Start
R
296
R
Enable autotuning and selftuning state
(FLG_PID)
SOFTSTART
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
147
SOF
R/W
Softstart time
63
bit
SOFTSTART STATE
OFF = Softstart off
ON = Softstart on
R
140
diG.
R/W
Digital input function
618
diG.2
R/W
Digital input function 2
11
bit
SOFTWARE ON/OFF
OFF = On software
ON =Off software
R/W
305*
R/W
State (STATUS_W)
SOFTWARE SHUTDOWN
68
bit
DIGITAL INPUT
STATE 1
OFF = Digital input 1 off
ON = Digital input 1 on
R
92
bit
DIGITAL INPUT
STATE 2
OFF = Digital input 2 off
ON = Digital input 2 on
R
FAULT ACTION POWER
265
xot
R/W
Select special functions
228
fa.p
R/W
Fault action power
(supplied in conditions of broken probe)
26*
bit
STATE OF HB ALARM
OR POWER_FAULT
OFF = Alarm off
ON = Alarm on
R
80
bit
State of power alarm
(special function)
OFF = Alarm off
ON = Alarm on
R
699*
P.ONT
R/W
Start mode at Power-On
START MODE
700
OFF.t
R/W
Software OFF
Page 88
88 80963B_MSW_GFW_11-2012_ENG
POWER ALARM
261
b.st
R/W
Stability band
(special power alarm function)
262
b.pf
R/W
Power alarm band
(special power alarm function)
260
pf.t
R/W
Power alarm delay time
(special function)
160*
rL.1
R/W
Allocation of reference signal
163*
rL.2
R/W
Allocation of reference signal
166*
rL.3
R/W
Allocation of reference signal
- Output OR
170*
rL.4
R/W
Allocation of reference signal
- Output AND
171*
rL.5
R/W
Allocation of reference signal
- Output OR
172*
rL.6
R/W
Allocation of reference signal
- Output AND
PREHEATING SOFTSTART
31
s.tv
R/W
Enable selftuning,
autotuning, softstart
263
SP.S
R/W
Softstart setpoint (special function)
264
SO.P
R/W
Softstart power
(special function)
147
SOF
R/W
Softstart time
63
bit
STATE OF SOFTSTART
OFF = Softstart in Stop
ON = Softstart in Start
R
HEATING OUTPUT (fast cycle)
160*
rL.1
R/W
Allocation of reference signal
163*
rL.2
R/W
Allocation of reference signal
TRIGGER MODES
703*
Xd.5
R/W
Enable trigger modes
707*
Fv.TA
R/W
Maximum limit of RMS current at normal
operation
630*
PS.XI
R/W
Maximum phase of phase softstart ramp
SOFTSTART
705*
PS.Tm
R/W
Duration of phase softstart ramp
629*
ps.oF
R/W
Minimum non-conduction time to
reactivate phase softstart ramp
706*
ps.tA
R/W
Maximum peak current limit during
phase softstart ramp
704*
BF.(y
R/W
Minimum number of cycles of BF modes
108*
bit
Restart of phase softstart
ramp
OFF = Restart not enabled
ON=Restart enabled
R/W
106*
bit
State of softstart ramp
from phase
OFF = Ramp not ended
ON = ramp ended
R
107*
bit
State of softstart ramp
from phase
OFF = Ramp not ended
ON = ramp ended
R
Page 89
8980963B_MSW_GFW_11-2012_ENG
DELAY TRIGGERING
708*
dL.T
R/W
Delay triggering
(rst trigger only)
738*
dL.OF
R/W
Minimum non-conduction time to
reactivate delay triggering
730*
Xd.6
R/W
Enable feedback modes
FEEDBACK MODES
731*
(or.U
R/W
Maximum correction of voltage feedback
732*
(or.i
R/W
Maximum correction of current feedback
733*
(or.p
R/W
Maximum correction of power feedback
734*
rif.U
R/W
Voltage feedback reference
735*
rif.i
R/W
Current feedback reference
736*
rif.p
R/W
Power feedback reference
113*
bit
Calibration of selected
feedback reference
OFF=Calibration non enabled
ON= Calibration enabled
R/W
HEURISTIC POWER CONTROL
681
682
hd.4
683
I.XET
191
224*
225
628
s.LI
R/W
Control LEDs and digital inputs from
serial
s.0v
R/W
Control outputs from serial
s.In
R/W
Control inputs from serial
hd.1
R/W
Enable multiset instrument
control via serial
R/W
Maximum current for heterogeneous
power control
R/W
Enable heterogeneous
power control
I.XEU
R/W
Maximum current for heuristic power
control
680
hd.3
R/W
Enable heuristic power control
HETEROGENEOUS POWER CONTROL
VIRTUAL INSTRUMENT CONTROL
757*
Arif
R Feedback
Setpoint of V, I, P to maintain on load
741*
fb.It
R/W
Feedback response speed
Page 90
90 80963B_MSW_GFW_11-2012_ENG
HW/SW DATA
197
Ld.st
R/W RN status LED function
619
Ld.2
R/W ER status LED function
620
Ld.3
R/W
DI1 LED function
621
Ld.4
R/W
DI2 LED function
622
Ld.s
R/W O1 LED function
623
Ld.6
R/W O2 LED function
625
Ld.8
R/W O4 LED function
624
Ld.7
R/W O3 LED function
305*
R/W
State (STATUS_W)
122
UPD
R
Software version code
606
Er.2
R
Self-diagnosis error code
for auxiliary input 2
85
Err
R
Self-diagnosis error code
for main input
190
(.xd
R Hardware configuration codes
121
R
Device ID (GFW)
120
R
Manufact - Trade Mark (Gefran)
346
R State of jumper
693 697
UPd.F
R
Fieldbus software version
695
Cod.F
R Fieldbus node
696
bAU.F
R Fieldbus baudrate
550
Er.3
R
Self-diagnosis
error code for auxiliary input 3
551
Er.4
R
Self-diagnosis
error code for auxiliary input 4
552
Er.5
R
Self-diagnosis
error code for auxiliary input 5
543
(.xd2
R Hardware configuration codes 2
508
(.xd1
R Hardware configuration codes 1
Page 91
9180963B_MSW_GFW_11-2012_ENG
469*
R
State 1 (STATUS1)
632*
R
State 2 (STATUS2)
633*
R
State 3 (STATUS3)
634*
R
State 4 (STATUS4)
467*
R
State (STATUS)
702
R
Voltage status
Page 92
92 80963B_MSW_GFW_11-2012_ENG
KEYPAD USE
This charter describes the optional GFW-OP keypad and use mode to display and program parameters.
Membrane keyboard
The following table describes the keypad and its functions:
Symble Reference Description
ESC Escape
Comes back to the higher menu or submenu. Exits from a parameter, or a parameter list. Allows to exit from a message requiring its use.
SAVE No function
FIND No function
RST No function
CUST No function
DISP No function
E Enter
Enters the submenu or the selected parameter, or selects an operation. It is used during the parameter change to confirm the new set value.
^ Up
Moves the selection in a menu or a parameter list highwards. During a parameter change, increases the figure value under the cursor.
v Down
Moves the selection in a menu or a parameter list downwards. During a parameter change, decreases the figure value under the cursor.
< Left Comes back to top menu. During a parameter change, moves the cursor verso rightwards.
> Right
Enters the submenu or the selected parameter. During a parameter change, moves the cursor verso rightwards.
Leds meaning:
LEDs Colour Led meaning
BRK Yellow Led is on when GFW is OFF software
CNT Yellow Led is on when GFW is in manual operating
EN Green Led is on when during power supply
ILIM Red
This led flashes when GFW reaches a current limit condition (if enabled). During normal operation this led is off.
N=0 Yellow Led is on when during softstart ramp
AL Red Led is on when GFW signals an alarm trigger
Description
The program keypad is used to display the state and diagnostic parameters
during operating period; on the back is present a magnetic material strip to x
it on GFW-master frontal or on a metal surface (ex. Electrical panel door). The keypad
is equipped with a connection cable of 70 centimeters.
Liquid crystal display
5 alphameric lines of 21 characters each
Pad keypad
Signal led
Page 93
9380963B_MSW_GFW_11-2012_ENG
Netsurng
Scan of rst and second level menus:
Parameter display
(1) Indication of menu and of parameter position
(2) Modubus address of parameter (node - address 16 bits or address 1 bit)
(3) Parameter description
(4) Depends on the parameter type:
• Numerical parameter: displays the parameter numerical value, in the requested format and measurement unit.
(5) This position displays:
• Numerical parameter: displays the minimum and maximum default values of parameter. These values are displayed in
order by pressing key ►
• Binary parameter: displays the parameter state (ON-OFF, AUTO-MAN, ...)
• Error signals and conditions:
Out of range: you are trying to enter a value outside the min and max limits.
First Level
First Level Second Level
01 STATUS 02 INFO 03 COMMS
04 INPUTS
05 ALARMS
04.01 STATUS
04.02 ANALOG
04.03 MAIN
04.04 AUX 1
04.05 AUX 2
01 STATUS
02 INFO
03 COMMS 04 INPUTS 05 ALARMS
01 STATUS
02 INFO 03 COMMS 04 INPUTS 05 ALARMS
11 VIRTUAL
01 STATUS 02 INFO 03 COMMS 04 INPUTS
down
UP
Right
04.02.01 ADDR:10-400
tyP: input type
0
Def: 0
1 2
3
4
5
Page 94
94 80963B_MSW_GFW_11-2012_ENG
Change parameters
• To access to change mode press key E when the parameter to changed is displayed.
• To save the parameter value, after changing it, press again key E.
• To exit from change mode without saving the value, press key ESC.
• The operations to execute to change the value depend on the type of parameter, as described below.
Numerical parameters
• When E is pressed, to access to change mode, the cursor on number corresponding to unit is activated.
• Use keys ◄ and ► to move cursor on all the numbers, included the non-signiant zeroes, which are not normally
displayed.
• With keys ▲ and ▼ the number under cursor is increased or decreased.
• Press E to conrm the change or ESC to cancel it.
Scan parameters
01.01 ADDR:10-751
Ld.V: load voltage
257.9 V
01.20 ADDR:10-252
Manual Power:
29.0 %
01.20 ADDR:10-753
Ld.A: load current
15.0 A
01 STATUS
02 INFO 03 COMMS 04 INPUTS 05 ALARMS
down
UP
Right
04.02.01 ADDR: 10-400 tyP: input type
0
DeF: 0
04.02.01 ADDR: 10-400 tyP: input type
000000000000
0
DeF: 0
Page 95
GEFRAN spa
via Sebina, 74
25050 Provaglio d’Iseo (BS) Italy
Tel. +39 0309888.1
Fax +39 0309839063
info@gefran.com
http://www.gefran.com
Loading...