Gefran 650 Data Sheet

Dimensions 48×48×80 mm (1/16 DIN)
650
1/16 DIN PID TEMPERATURE CONTROLLER
Main features
• Operator interface with large LCD Display, customizable, with choice of colors
• Scrolling diagnostics messages,
congurable, in the selected language
Easy, guided conguration, copy/paste parameters even with power off
• Preventive maintenance with energy counters (kWh) and load switching
• 16 function block applications
• Timer, setpoint and algorithm programmer for controlling motorized valves
• Advanced tuning of control parameters
• Different password levels
• Universal input configurable for thermocouples, resistance thermometers, linear inputs
• Remote setpoint input
• Relay, logic, isolated analog outputs
• Up to two CT inputs for interrupted load diagnostics
• RS485 serial communication in Modbus RTU
• Removable faceplate for immediate replacement
• Sampling time 60ms
PROFILE
Operator interface
Large LCD display with customization of colors assigned to PV and SV display, of color of plastic faceplate, and of logo. Scrolling alphameric display of 25 mes­sages (32 letters each), completely confi­gurable and savable, in three languages. Thanks to language selection and clear scrolling messages for diagnostics, alarms, and process state, the controller speaks the user’s language.
Easy Configuration
Guided configuration for manual-free pro­gramming, with a few essential parameters and on-line help messages. Ability to clone configuration among con­trollers, even with power off and in the field, thanks to a mini portable configurator with Zapper battery. Extended configuration, creation of work recipes, and firmware updates via PC and GF_eXpress software, even without powe­ring the controllers. Thanks to the Smart Configurator function, you obtain the required parameter recipe by answering a few simple questions. Local configuration and operation with only four keys assigned to LEDs that ser­ve as feedback for the pressed key and as guide to specify appropriate steps.
The initial parameters can always be reset, both from the keypad and from the GF_eX­press Software tool.
Diagnostics, Preventive Maintenance, and Energy Monitor
Complete diagnostics for broken or incor­rectly connected probe, total or partial load break, out of range variables, and control loop faults. Thanks to the switching count and to the settable alarm thresholds, you can pro­gram preventive maintenance to replace worn actuators. An internal energy counter with alarm for abnormal variations totalizes energy con­sumptions and costs for constant control
Function block applications
Sixteen AND, OR, Timer Function Blocks let you create customizable logic sequen­ces for complete and flexible machine con­trol. The controller’s hardware resources are exploited completely, without any need for external devices such as timers and small PLCs
Tuning
Advanced tuning algorithms ensure stable and accurate control even with critical or very rapid thermal systems, engaging au­tomatically when necessary.
Timer
Three types of timers let you set delay ti­mes before activating the control, hold ti­mes on the setpoint value, and timed chan­ges of programmed setpoints.
Setpoint Programmer
Models with twelve ramp and hold steps, groupable in four programs, with enable inputs and event outputs, are available for applications with setpoint profiles. On-board configuration and graphic confi­guration with GF_eXpress.
Valve Positioner
Models to control motorized valves, wi­thout feedback. Valve position is calculated and shown on the display.
General characteristics
The controller is completely software con­figurable without accessing the internal electronics. The universal main input accepts thermo­couple sensors, resistance thermometers, and linears. The controller can be replaced at any time simply by removing the faceplate, without any additional procedures.
DISPLAY AND KEYS
1
2
3
4 6
5
1. Temperature unit of measurement or number of program running.
2. State of outputs OUT1, OU2, OUT3, OUT4.
3. Controller function states:
RUN = setpoint programmer active;
_/- = setpoint ramp active;
TUN = PID parameters tuning active;
MAN = manual/automatic (off = automatic control, on
= manual control);
9
REM = remote setpoint enabled;
SP1/2 = setpoint active (off = setpoint 1,
on = setpoint 2).
8
7
4. Work mode key (manual/automatic) in standard mode. A function can be assigned via parameter but1. The key is active only when the display shows the process variable
5. Up/down keys: raise/lower the value of the parameter di­splayed on the SV or PV display.
6. F key: lets you navigate among controller menus and para­meters. Confirms the parameter value and selects the next parameter.
7. Key pressed signals.
8. SV display: setpoint value, description of parameters, dia­gnostics and alarm messages. Configurable with parameter dS.SP (default = setpoint).
9. PV display: process variable, parameter values.
DIMENSIONS AND DRILLING TEMPLATE
58 mm
2.28 in 48 mm
1.89 in
80 mm
3.15 in
48 mm
1.89 in
10 mm
0.39 in
70 mm
2.76 in
70 mm
2.76 in
+0.6
- 0.0
1.78 in
45 mm
+0.6
45 mm
- 0.0
1.78 in
Dimensions mm/in
TECHNICAL DATA
OPERATOR INTERFACE
DISPLAY
KEYPAD
INPUTS
MAIN INPUT
AUXILIARY INPUT
CT
(ammeter)
INPUT
Type LCD black background Screen area (L x H) 35 × 30 mm Lighting Backlit with LEDs, life > 40,000 hours @ 25°C PV display Number of digits: 4 to 7 segments, with decimal point
Digit height: 17 mm Color: white or “custom”
SV display Number of digits: 5 to 14 segments, with decimal point
Digit height: 7.5 mm Color: green or “custom”
Unit of measurement Selectable, °C, °F or custom 1
Color: same as PV display
Controller state signals Number: 6 (RUN, MAN, _/-, REM, SP1/2)
Color: amber
Output state signals Number: 4 (1, 2, 3, 4)
Color: red Number of keys: 4 silicon (Man/Auto, INC, DEC, F) Type: mechanical
Sensor type TC, RTD (PT100, JPT100), IR ES1B, DC linear sensor Accuracy TC inputs:
Calibration accuracy: < +/- (0,25% of reading value in °C +0,1°C) Linearization accuracy: 0,1% of reading value Cold junction accuracy: < +/- 1,5°C a 25°C room temperature) Cold junction compensation: > 30:1 rejection to the change of the room temperature RTD input: Calibration accuracy: < +/- (0,15% of reading value in °C +0,4°C) Temperature drift: < +/- (0,005% of reading value in °C +0,015°C )/°C from 25°C room temperature Linearization accuracy: 0,1% of reading value Linear inputs: Calibration accuracy:< 0,1% full scale
Temperature drift: < +/- 0,005% full scale /°C at 25°C room temperature Sampling time 60 ms / 120 ms, selectable Digital filter 0,0...20,0 s Temperature unit of measu­rement Signal interval Type: linear
TC (thermocouple) input RTD (resistance thermometer) input
DC linear input 0...60 mV input impedance (Ri): > 70 kΩ
Remote setpoint 0...1 V, 0...10 V, 0/4...20 mA Scale 0...1 V input impedance (Ri): > 15 kΩ
Accuracy 0,1% f.s. ±1 digit @25 °C
Type Isolated via external transformer
Accuracy ±2% f.s. ±1 digit @25 °C
Degrees C / F, selectable from keypad
Scale: -1999...9999, settable decimal point
Thermocouple: J, K, R, S, T, C, D
Linearization: ITS90 or custom
Resistance thermometer: PT100, JPT100
Input impedance (Ri): ≥ 30 kΩ
Linearization: DIN 43760 or custom
Max. line resistance: 20 Ω
0...1 V input impedance (Ri): > 15 kΩ
0...5 V / 0...10 V input impedance (Ri): > 30 kΩ
0/4...20 mA input impedance (Ri): 50 Ω
Linearization: linear or custom
0...10 V input impedance (Ri): > 30 kΩ
0/4...20 mA input impedance (Ri): 50 Ω
Number: 2 max
Max. capacity: x / 50 mA AC
Line frequency: 50/60 Hz
Input impedance (Ri): 10 Ω
1) Programming is done with the GF_eXpress configuration program.
DIGITAL INPUTS
OUTPUTS
ALARMS
CONTROL FUNCTIONS
CONTROL
SETPOINT
PROGRAMMER
MULTIPLE
SETPOINTS
LOGIC
OPERATIONS
TIMER FUNCTION
1
Type voltage-free contact, or
NPN 24 V - 4,5 mA, or PNP 12/24 V - max 3,6 mA
(for detail see electrical connections)
Isolation 500 V Number 3 max
Relay (R)
Number: 4 max Type of relay contact: NO Max. current: 5 A, 250 VAC Minimum load: 5 V, 10 mA Life cycle: > 100.000 operations
Double isolation Logic (D)
Number: 2 max
Type: for solid-state relays
Voltage: 24 V ±10% (min 10 V @20 mA)
Isolated from main input Triac ( long life relè) (T)
Number: 1 max
Load: resistive
Voltage: 75...264 VAC
Current max: 1 A
Isolation 3 kV
snubber circuit integrated zero crossing switching Continuous (C)
Number: 1 max
Current: 4...20mA
< 500 Ω
R
out
Resolution: 12 bit
Isolated from main input Analog retransmission (A1)
Number: 1 max
0...10 V, max 20 mA, R
0...20 mA, 4...20 mA, R
Resolution: 12 bit
: > 500 Ω
out
: < 500 Ω
out
Isolated from main input Number of alarm functions 4 max, assignable to an output
Possible configurations Maximum, minimum, symmetric, absolute/relative, exclusion at firing,
memory, reset from keypad and/or contact, LBA, HB
HBB Hold Back Band if enabled with Programmer function
Type Single loop Control PID, ON/OFF, single action heat or cool, double action heat/cool Control output Continuous or ON/OFF
Cycle time: constant or optimized (BF) Control output for motori­zed valves
OPEN/CLOSE for floating motorized valve on Relay, Solid-state, Triac
outputs Number of programs Max 4
Start / Stop / Reset / Skip via digital inputs and/or outputs from logic
operations
Output state: Run /Hold / Ready / End Number of steps Max 12, each with own setpoint, ramp time and hold time
Times settable in HH:MM or MM:SS
Max 4 consents, configurable for ramp and for hold
Max 4 events, configurable in ramp and in hold Number of setpoints Max 4, selectable from digital input
Each setpoint change is subject to set ramp, different for up and down
ramp Function blocks Max 16, with 4 input variables per block.
The result can act on the state of the controller, of the programmer on
alarms and outputs.
Each function contains an incorporated timer block timer. Modes START / STOP
STABILIZATION (timer is on when PV enters a band set around setpoint;
at end of count you can activate an output, shut down SW or change
SP1/SP2)
FIRING (timed activation of control after power on)
1) Programming is done with the GF_eXpress configuration program.
ENERGY COUNTER
Calculation done on nominal line voltage and nominal load power or on rms current measured on load via CT Short circuit or open circuit (LBA alarm)
DIAGNOSTIC
Interrupted or partially interrupted load (HB alarm) Short circuit of control output (SSR alarm)
RETENTIVE MEMORY
Type EEPROM Max. number of writes 1.000.000
SERIAL INTERFACE
Type RS485 Baudrate 1200, 2400, 4800, 9600, 19.200, 38.400, 57.600, 115.200 bit/s Protocoll MODBUS RTU
Isolated from main input
GENERAL DATA
Operating voltage 100...240 VAC/VDC ±10%, 50/60 Hz
(on request 20...27 VAC/VDC ±10%)
POWER SUPPLY
CONNECTIONS
AMBIENT
CONDITIONS
PROTECTION LEVEL IP 65 on front panel (as per IEC 68-2-3)
ASSEMBLY
DIMENSIONS 48 X 48 mm (1/16 DIN),
WEIGHT 0,16 kg
CE STANDARDS
Power dissipation 5 W max Protections Overvoltage 300 V / 35 V Connection Screw terminals and crimp connector, max. wire section 1 mm Serial configuration port
Connector: microUSB (for USB connection) Inputs and outputs Screw terminals and crimp connector, max. wire section 2,5 mm
Use Indoor Altitudine 2,000 m max Operating temperature -10 ... +55 °C (as per IEC 68-2-14) Storage temperature -20 ... +70 °C (as per IEC 68-2-14) Relative humidity 20...85% RH non-condensing (as per IEC 68-2-3)
Positioning On panel, removable faceplate Installation regulations Installation category: II; Pollution degree: 2
Isolation: double
Depth: 80 mm
EMC (electromagnetic compa­tibility)
Conforms to Directiv 2014/30/EU with reference to standard EN 61326-1
emission in industrial environment class A for models 650 LV
emission in residential environment class B for models 650 HV Safety: LVD Conforms to Directiv 2014/35/EU with reference to standard EN61010-1
2
2
ACCESSORIES
Code Description
F060800 Cable for programming with PC, USB-TTL 3 V with USB – microUSB connectors, length 1.8 m
F043958 “GF_eXpress” software CD
F060909 Configuration kit for new instruments GF_eXK-3-0-0
F060908 Portable configurator, complete with cable and Zapper
51968 Rubber gasket 48×48 front-box
51250 Fastening box to panel
51294 Protection of contacts at box bottom
51454 18 contacts at box bottom
330200 Current transformer (CT) 50/0.05 A
330201 Current transformer (CT) 25/0.05 A
CONNECTION DIAGRAM
OUT 2
OUT 3
OPTIONS
NO
NO
NO
6
5
4
3
2
1
+
-
C
+
-
RS485
second current transformer for 2-phase / 3-phase load
+
C
-
7
8
9
10
11
12
OUT 1 (main)
+
TT
-
+
A1
-
COM
IN 1
A (Data +)
B (Data -)
+
5 V, 10 V
-
~
PWR
~
19
20
21
22
23
24
7
8
9
10
11
12
+
C
-
~
C
~
7
8
9
10
11
12
OUT 2
OUT 3
OUT 4
C
IN 2
IN 1
COM
current transformer current transformer
CT1
second current
CT2
transformer for 2-phase / 3-phase load
7
8
9
10
11
12
A (Data +)
B (Data -)
COM
CT1
CT2
LEGEND
~
Power supply
PWR
~
+
Linear input in voltage / current
-
Input for current transformer
+ SPR
Remote Set-point
- SPR
7
8
9
10
11
12
A (Data +)
B (Data -)
COM
IN 3
IN 2
IN 1
+ SPR
7
+
A1
RS485
Isolated digital inputs
+
Thermocouple input
-
Input
T
JPT100
PT100
T
2 / 3 wires
8
9
10
11
12
-
COM
IN 3
IN 2
IN 1
NO
Relay output
C
C
~
~
Long-life solid state relay output
+
C
DC analog output
-
+
Isolated analog output
A1
-
7
8
9
10
11
12
+
-
- SPR
A (Data +)
B (Data -)
COM
IN 3
IN 2
IN 1
Logic output
RS485 serial line
ATTENTION: For correct installation, read the warnings in the instruction manual.
!
ORDER METHODS
Ordering code
Model
Controller ­Programmer P Valve V
Output 1
Relay R Static D Analog 4...20mA C
Output 2 - 3 - 4
1 Relay (5A) R-0-0 1 Static D-0-0 2 Relay (5A) R-R-0 1 Static + 1 relay D-R-0
1 Relay (5A) + 1 Long Life relay R-T-0
1 Static + 1 Long Life relay D-T-0 3 Relay (5A total) R-R-R
Remote Set Point - W retransmission ­CT inputs - Digital inputs ­Serial communication
Absent 0-0-0-0-0 CT1 0-0-1-0-0 CT1 + CT2 0-0-2-0-0 CT1 + 2 DI 0-0-1-2-0 CT1 + CT2+2 DI 0-0-2-2-0 CT1 + RS485 0-0-1-0-1 CT1 + CT2+RS485 0-0-2-0-1 3 DI 0-0-0-3-0 3 DI + RS485 0-0-0-3-1 3 DI + SPR 1-0-0-3-0 3 DI + W 0/4...20mA/0...10V 0-1-0-3-0 1 DI + W + RS485 0-1-0-1-1
650 X XX X X X X X X X X X X- - - -
Supply
20-27Vac/dc 0 100-240Vac 1
Functions
Logical operations LF
Display
Green setpoint G
Power supply 100...240 VAC
Inputs Outputs
Code F Model
Valves
Programmer
DigitalCTSPR
F060558 650-D-R00-00000-1-G 1 1
F059574 650-R-R00-00000-1-G 2 F060566 650-D-R00-00120-1-G 2 1 1 1 F060562 650-D-RR0-00000-1-G 2 1 F065788 650-R-RR0-00000-1-G 3 F065789 650-R-RT0-00000-1-G 2 1 F065790 650-D-RR0-00030-1-G 3 2 1 F060567 650-D-RR0-00200-1-G 2 2 1 F060564 650-C-RR0-00000-1-G 2 1 F060573 650-D-R00-01030-1-G 3 1 1 1 F065791 650-R-R00-01030-1-G 3 2 1 F060574 650-R-RR0-00101-1-G 1 3 • F060563 650-D-RRR-00000-1-G 3 1 F065792 650-R-RRR-00000-1-G 4 F060575 650-D-RRR-00220-1LFG 2 2 3 1 • F060576 650-D-RRR-00031-1LFG 3 3 1 • F065793 650-D-RRR-00201-1LFG 2 3 1 • F065794 650-D-RR0-01011-1LFG 1 2 1 1 • F060577 650-C-RRR-10030-1LFG 3 1 3 1
F060578 650V-R-RRR-00000-1-G 4 F060561 650V-R-RRR-00030-1-G 3 4 F060565 650P-D-RRR-00000-1-G 3 1
F060560 650P-D-RRR-00030-1LFG 3 3 1 • F060579 650-D-RRR-01030-1LFG 3 3 1 1
Relay
Triac
Logic
Analog I
RS485
Analog V/I
Total Number of Outputs
Logic functions
2 outputs
3 outputs
4 outputs
5 outputs
Power supply 20...27 VAC/VDC
Inputs Outputs
Code F Model
Valves
Programmer
DigitalCTSPR
F065795 650-D-R00-00000-0-G 1 1
F065796 650-R-R00-00000-0-G 2 F065797 650-D-R00-00120-0-G 2 1 1 1 F065798 650-D-RR0-00000-0-G 2 1 F065799 650-R-RR0-00000-0-G 3 F065800 650-R-RT0-00000-0-G 2 1 F065801 650-D-RR0-00030-0-G 3 2 1 F065802 650-D-RR0-00200-0-G 2 2 1 F065803 650-C-RR0-00000-0-G 2 1 F065804 650-D-R00-01030-0-G 3 1 1 1 F065805 650-R-R00-01030-0-G 3 2 1 F065806 650-R-RR0-00101-0-G 1 3 • F065807 650-D-RRR-00000-0-G 3 1 F065808 650-R-RRR-00000-0-G 4 F065809 650-D-RRR-00220-0LFG 2 2 3 1 • F065810 650-D-RRR-00031-0LFG 3 3 1 • F065811 650-D-RRR-00201-0LFG 2 3 1 • F065812 650-D-RR0-01011-0LFG 1 2 1 1 • F065813 650-C-RRR-10030-0LFG 3 1 3 1
F065818 650V-R-RRR-00000-0-G 4 F065819 650V-R-RRR-00030-0-G 3 4 F065820 650P-D-RRR-00000-0-G 3 1
F065821 650P-D-RRR-00030-0LFG 3 3 1 • F065822 650-D-RRR-01030-0LFG 3 3 1 1
Relay
Triac
Logic
Analog I
Analog V/I
RS485
Logic functions
Total Number of Outputs
2 outputs
3 outputs
4 outputs
5 outputs
Please contact GEFRAN for information on available codes.
Conformity TC N° RUД-IT.AЛ32.b.01762
FM
UL
FM approvals project NO: 0003054712
Conformity C/UL/US File no. E216851
EMC (electromagnetic compatibility): conforms to directive 2014/30/EU with reference to standard EN 61326-1 emission in industrial environment class A for models 650 LV emission in residential environment class B for models 650 HV Safety LVD: conforms to directive 2014/35/EU with reference to standard EN61010-1
GEFRAN spa via Sebina,74 - 25050 Provaglio d’Iseo (BS)
Tel. 03098881 - fax 0309539063 - Internet: http://www.gefran.com
DTS_650_09-2016_ENG