Gefran 600 OF Data Sheet

Main applications
• Small industrial ovens
• Pipe welders
• Temperature control units
• Dryers
• Climatic cells and test benches
600 OF
“OPEN FRAME” CONTROLLER
Main features
• Universal input configurable from faceplate
• Accuracy better than 0.2% f.s. under nominal conditions
• Up to 5 outputs, relay, logic, for control, alarms
• Hot/cold function with selection of cooling liquid
• 3 alarms with completely configurable function
• Software alarm for load interrupt or probe in short circuit (LBA)
• Self-tuning, Auto-tuning, Soft-start, bumpless Man/Auto function
• Double set, set ramp, timed output function
• Setpoint programmer functions with 3 configurable steps
• Configurable internal buzzer
• Optically isolated RS485 serial communication, protocol: MODBUS RTU
• Self-diagnosis
• Panel mounting
• Screw connections with removable terminals
PROFILE
Microprocessor controller, format 44x91 (1/16 DIN) manufactured using SMT. Provides a complete operator interface. It has 4 keys, two green LED displays, each
with 4 digits, 4 red signal LED’s for the 4
logic or relay outputs, and 3 other program­mable LED’s to signal the various operatio­nal states of the instrument. Can be connected to an external keyboard for custom solutions. The main input for process variable is uni­versal, and many types of signals can be connected: thermocouples, resistance ther­mometers, thermistors, normalized linear inputs, all with possibility of custom lineari­zation using the faceplate keys. The type of input is selected from the faceplate keys; no external shunts are required. Control functions are selectable from classic mode or from setpoint programmer mode with 3 settable steps. With the isolated digital input you can select: one of the two presettable setpoints, select Manual-Automatic mode, reset the alarms memory, or enable the hold function. The instrument can have up to 5 outputs: relay (5A at 250Vac/30Vdc cos_= 1) or logic 15V ±10% (12V min at 30mA). The function of each output is freely configurable from the faceplate keys. In addition to con­trol and alarm outputs, you can have outputs that repeat the state of the digital input and values alarm limits acquired from serial line. Another output (±15Vdc 20mA max.) is avai-
lable to power external transmitters. The serial communication option (available in RS485 standard) allows connection to supervision systems and PLCs with the MODBUS RTU protocol. Instrument pro­gramming is facilitated by grouping para­meters in functional blocks (CFG for control parameters, Inp for inputs, Out for outputs, etc.). The instrument can also select display para­meters based on hardware configuration, automatically masking irrele­vant parameters. The instrument is supplied with an “EASY” configuration with just a few parameters (only those for the model orde­red and essential for controller operation). In this way, you just have to set the setpoint and alarm, and launch selftuning from the button. The 600OF does all the rest. A PC programming kit is available for even simpler configuration, composed of a cable and a guided program for Windows envi­ronment (see data sheet code WINSTRUM). Compact “Open Frame” mechanical struc­ture makes the 600OF easy to use even on small panels and housings.
TECHNICAL DATA
INPUTS
Accuracy 0,2% f.s. ±1digit. Sampling time 120msec.
TC - Thermocouple
J 0...1000°C / 32...1832°F K 0...1300°C / 32...2372°F R 0...1750°C / 32...3182°F S 0...1750°C / 32...3182°F T -200...400°C / -328...752°F custom -1999...9999
(B, E, N, L-GOST, U, G, D, C, etc.)
RTD 2/3 wires
PT100 -200...850°C / -328...1562°F JPT100 -200...600°C / -328...1112°F
PTC
990Ω, 25°C -55...120°C / -67...248°F
NTC
1KΩ, 25°C -10...70°C / 14...158°F
DC - Linear
With scale settable from:-1999...9999
0...60mV / 12...60mV
0...10V / 2...10V
0...5V / 1...5V
0...1V / 0,2...1V
0...20mA / 4...20mA Input impedance:
Ri > 1M _ for 60mV,1V Ri > 10K _ for 5V, 10V Ri = 50 _ for 20mA 32-segment custom linearization can be inserted.
Digital input
Ri = 4,7K. (24V, 5mA) insulation 1500V or no-voltage contact. Function configurable for man/auto selection, local/remote (setpoint from serial line, setpoint1/setpoint2; Set/reset outputs, start/stop functions from tuning, software on/off, reset alarms memory, hold.
OUTPUTS
5 configurable outputs:
• OUT1 available in relay or logic
• OUT2, OUT3, OUT4: relay only
• OUT6: logic only Freely assignable to control functions and single alarms in “OR” or “AND”. Can be slaved to front panel key or aux. digital input.
Relay
With contacts: 5A at 250Vac/30Vdc, cos_=1
Logic
15Vdc ±10% (12V min a 30mA)
POwer SUPPly
1100...240Vac ± 10%; 50/60Hz, 8VA max. Protection by internal fuse not serviceable by user
TraNSmITTer POwer SUPPly
+15V ±10% non-stabilized, 20mA max Short-circuit protection
ambIeNT cONdITION
Working temperature range: 0...50°C Storage temperature range -20...70°C Humidity: 20...85%Ur non condensing
cONTrOl
On/Off, P, PD, PID for heating and coo­ling, with parameters settable from keys. Cooling setpoint relative to heating setpoint. Setpoint programming function with 3 pro­gram steps settable with times from 0.0 to 99059 minutes
Manual reset -999...999 digit
Power reset -100,0...100,0%
Cycle time 0...200sec
Softstart 0,0...500,0 min
For each action:
Proportional band 0,0...999,9% f.s.
Integral time 0,0...99,99 min
Derivative time 0,0...99,99 min
Max power limit 0,0...100,0%
• Hysteresis settable for each alarm
• Alarm assigned to current input with different operating modes.
weIghT
160g in complete version
Buzzer (Output 5)
Settable signal type
External keyboard
5 pin connector for 4 external keys
Serial line
Isolated RS485 Protocol: MODBUS
FACEPLATE DESCRIPTION
A – Indication of process variable (PV), green digits height 10mm
B – Indication of setpoint (SV), green digits height 7mm C – “Function” key D – “Lower” key E – “Raise” key F – Auto/Man selection G – Function indicators, red LEDs H – Indication of output states, red LEDs
alarmS
• 3 alarms settable as absolute, deviation, symmetrical deviation to setpoint with direct or reverse function.
• Alarm point can be set anywhere on selected scale
• Alarms can be masked with exclusion at power-on, with memory, with delayed trip
• LBA alarm for setting control