Max. non-linearity error See t.P parameter at page 3
For correct and safe
installation, follow the
instructions and
observe the warnings
contained in this
manual.
Faceplate protection IP65
Working / Storage temperatures 0...50°C / -20...70°C
Relative humidity 20 to 85%, non-condensing
Installation Panel mounting
Weight 90g for the complete version
Resolution
(function of settable sample time)
120msec, >13bit - 8000 points
60msec, >13bit - 8000 points (only for linear inputs)
30msec, >12bit - 4000 points (only for linear inputs)
15msec, >11bit - 2000 points (only for linear inputs)
Thermocouples
J, K, R, S, T, B, E, N
(IEC 584-1, CEI EN 60584-1, 60584-2)
L GOST, U, G, D, C
Custom linearization available on request
Cold junction error 0,1° / °C
RTD type (scale configurable within indicated
range, with or without decimal point)
Max. RTD line resistance
DIN 43760 (PT100), JPT100
20Ω
PTC type / NTC type 990Ω, 25°C / 1KΩ, 25°C
°C / °F selection Faceplate configurable
Linear scale ranges
-1999 to 9999 (with 4 digit display)
-999 to 999 (with 3 digit display)
-99 to 99 (with 2 digit display)
Configurable decimal point position, possible 32
segment linearization
(option) Power supply for 2wire transmitter
18V ±10%, 30 mA
1.2 V DC for potentiometer > 100 Ω (version P77)
Power supply (switching)
11...27 V DC, 18...27VAC ±10%,
50/60Hz, 3VA (not isolated)
Display
2, 3, 4 digits, red, height 14 mm
Keys 3 mechanical keys (Raise, Lower, F)
Accuracy
0.2% f.s. at 25°C ambient temperature, ts=120msec
Main input
TC, RTD, PTC, NTC
60 mV, 1 V, 5 V, 10 V, Ri ≥ 500KΩ
20 mA, Ri = 50Ω
adjustable digital filter
76
36
54
8
30
69,5
43
83
72
1 • INSTALLATION
• Dimensions and cut-out: Panel mounting
Panel mounting:
Fix the device with the bracket provided before making any electrical connections.
To mount two or more devices side by side, use the cut-out dimensions shown above.
CE MARKING: EMC (electromagnetic compatibility) conformity to EEC Directive
89/336/CEE with reference to the generic Standard EN61000-6-2 (immunity in
industrial environments) and EN50081-1 (emission in residential environments).
BT (low voltage) conformity to Directive 73/23/CEE as modified by Directive 93/68.
MAINTENANCE: Repairs must be done out only by trained and specialized personnel.
Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.).
Use of these solvents can reduce the mechanical reliability of the device. Use a cloth
dampened in ethyl alcohol or water to clean the external plastic case.
SERVICE: GEFRAN has a service department. The warranty excludes defects caused
by any use not conforming to these instructions.
2 • TECHNICAL SPECIFICATIONS
FUNCTION CABLE LENGTH USED
TC input probe 0,8 mm2compensated 5 mt
“PT100” input probe 1 mm
2
3 mt
Power supply cable 1 mm
2
1 mt
EMC conformity has been tested with the following connections
!
8
4T 72
UNIVERSAL TEMPERATURE INDICATOR
SOFTWARE VERSION 1.0x / 2.0x
code 81606A / edition 0.5 - 05/04
USER’S MANUAL

9
Available thermocouples:
J, K, R, S, T, B, E, N,
L, U, G, D, C
- Respect polarities
- For extensions, use
compensated cable
appropriate for
thermocouple.
Use wires of adequate
thickness (min. 1mm
2
)
PT100, JPT100,
PTC, NTC
dc current
linear input
20mA, Ri = 50Ω
(signal must be isolated
from power supply)
dc voltage linear input
60mV, 1V, 5V, 10V,
Ri ≥ 500KΩ
(signal must be isolated
from power supply)
“Raise” and “Lower” keys:
These keys are used for any operation that requires
a numerical parameter to be raised or lowered. ••
The speed of change is proportional to the time the
key is pressed. •• The operation is not cyclic: once
the maximum (minimum) limit is reached, there will
be no further increase (decrease) of the value, even
if the key remains pressed.
The keys can be configured to perform reset, hold,
display of the peak value, etc. as determined by the
‘t.U.’ and ‘t.d.’ parameters on the ‘In’ menu.
3 • DESCRIPTION OF FRONT PANEL
Function key:
Gives access to different configuration stages •• Confirms
any parameter changes
Standard:
11...27Vdc ±10%
18...27Vac ±10%
50/60Hz, 3VA max.
not isolated
• Linear (V)
• Pt100 / PTC / NTC
3
1
2
2
1
+
-
• Linear (I)
4
1
2
-
+
• Power supply
11
12
~
~
+
-
• Thermocouples
2
1
4
2
3
1
-
+
-
Ri = 50Ω
4...20mA
• Linear input with 2-wire transmitter
PWR
12411321
!
Label with engineering unit
4 • CONNECTIONS
3-wire Pt100
2-wire PTC /
NTC / Pt100
+
PV display: Indication of process variable
Indication of ‘HI’ or ‘Lo’ out of range •• Indication of
open circuit (br) or short circuit (Er) •• Display of
configuration and calibration messages
5108976
T
T
• Linear input for potentiometer
4
2
3
1
R >100Ω
+ 1,2V
-
• Device structure: identification of boards
S3
S4
CPU board
PROBE POWER board
RTD, PTC, NTC
input
ON
OFF
Transmitter and
potentiometer
power supply
OFF
ON
S3
S4
S9
S8
S5
S1
S4
S6
S3
S7
Voltage
1V
24V (18V)
Jumpers
S4 - S6B - S7A
S6B - S7A
Probe power supply
• Inputs
5 • PROGRAMMING and CONFIGURATION
I F
P.V.
Process variable
Password
P A
PA = 99
P r
U.C.
Custom linearization
User calibration
YES
NO
LEVEL 1 DISPLAY
L n
Protection code
Information display
I n
Input settings
F
Pressed for
approx. 2 sec.
Keep the F key
pressed to browse
the menus.
Release the F key
to enter the
displayed menu.
Press the F key to
access the
parameters.
Keep the F key
pressed to exit any
menu at any time.