40T 48
CONFIGURABLE INDICATORS - ALARM UNITS
Main applications
• Thermostats
• Humidity switches
• Mould cooling units
• Industrial refrigerators
• Air conditioning
• Food processing equipment
Main features
• Faceplate configurable input
• Protected by a personal code
• Configurable by a serial link
• Transmitter power supply incorporated
• Custom thermocouple linearisation
available
• Internal linearisation for engineering
units
• Labels provided for the more common
physical units
• Sampling time and trip intervention
programmable between 15 and
120msec with resolution between
4000 and 16000 steps
• Retransmission of the measured
variable signal
• 3 trip points, completely configurable
from the faceplate
• 4 trip points completely configurable
from keyboard
• RS485 optically isolated serial line
Protocol : GEFRAN CENCAL or
MODBUS RTU
• Rapid configuration from PC with
Winstrum package
GENERAL
Microprocessor based indicator in both
48x48 (1/16 DIN) formats
manufactured with SMT.
The instruments have a lexan
membrane faceplate (guaranteed to
IP65) which has 3 keys, a 4 digit
display and 3 indicating LED’s for the
output statuses.
The input signal can be selected from a
wide range of sensors:
• Thermocouples of type: J,K,R,S,T, B,
E, N, L GOST, U, G, D, C
• Resistance thermometers Pt100,
Pt100J 2 / 3 wire
• PTC and NTC themistors
• Linear inputs 0 to 60/12 to 60mV ,
0 to 20/4 to 20mA,
0 to 10/2 to 10/0 to 5/1 to 5/0 to 1/0,
2 to1V
The selection is made using the
faceplate keys and correct input
terminals.
No external shunt or adapter is
required.
A digital input (24Vdc/5mA) is available for
resetting, hold, flash, peak handling or
releasing latch. The instruments have a
maximum of 4 outputs that can be
mechanical relays (5A/250V) or logic
outputs 24V±10% (10Vmin / 20mA).
One output of 4 to 20mA (max. 500Ω)
is available for retranmitting the
measured input signal.
The retransmission output, the digital
input and the third output are
alternatives.
The options include a triac output that
can directly drive resistive loads up to a
maximum of 1A at 240V.
The programming of the instrument is
made easy by grouping the parameters
in function blocks (CFG for the alarm
hysteresis, Inp for the inputs, Out for
the outputs...) and by a simplified data
entry menu.
The configuration can be simplified
even further using the PC programming
kit made up of a connection cable and
a menu guide program that runs under
Windows (technical data GF_eXpress).
A configurable personal software
protection code (password protection)
can be used to restrict the levels of
editing and displaying the configuration
parameters.
TECHNICAL DATA
I
NPUTS
Accuracy 0,2% f.s. ±1digit.
Sampling time 120msec for
temperature sensors, configurable for
linear inputs down to a minimum of
15msec with reduction of the resolution
to 4000 steps.
Configurable decimal point position for
linear inputs, for TC, RTD, PTC and
NTC inputs, only one decimal digit is
allowed in the maximum display range
of -199.9 to 999.9, with indication of
open circuit thermocouple or RTD, PTC
or NTC in open or short circuit,
indication of over- and under-range for
linear inputs.
TC - Thermocouple
J 0 to 1000°C / 32 to 1832°F
K 0 to 1300°C / 32 to 2372°F
R 0 to 1750°C / 32 to 3182°F
S 0 to 1750°C / 32 to 3182°F
T -200 to 400°C / -328 to 752°F
B 44 to 1800°C / 111 to 3272°F
E -100 to 750°C / -148 to 1382°F
N 0 to 1300°C / 32 to 2372°F
L-GOST 0 to 600°C / 32 to 1112°F
U -200 to 400°C / -328 to 752°F
G 0 to 2300°C / 32 to 4172°F
D 0 to 2300°C / 32 to 4172°F
C 0 to 2300°C / 32 to 4172°F
custom -1999 to 9999