We will be glad to receive any possible information which could help us improving this manual. The e-mail address is the following: techdoc@gefran.com.
Before using the product, read the safety instruction section carefully.
Keep the manual in a safe place and available to engineering and installation personnel during the product functioning period.
Gefran S.p.A has the right to modify products, data and dimensions without notice.
The data can only be used for the product description and they can not be understood as legally stated properties.
This manual is updated according to rmware versions V03.06.XX and V03.07.XX.
All rights reserved.
2 AGL50-EV
Table of Contents
Safety Symbol Legend .................................................................................................................... 4
1.1 Discharge time of the DC-Link .............................................................................................................................................6
3.2 Storage and transport ..........................................................................................................................................................7
3.3 Standard ...............................................................................................................................................................................7
3.5 AC Output ............................................................................................................................................................................. 9
3.6 Open-Loop and Closed-Loop control section .....................................................................................................................10
4.1 Power Section ....................................................................................................................................................................13
4.5 RS 485 Serial Interface ......................................................................................................................................................18
4.5.1 RS485 serial terminals ..................................................................................................................................................................18
4.5.2 Serial protocol ...............................................................................................................................................................................18
5.2 Moving through the drive main menu .................................................................................................................................21
5.3 Scrolling through the drive parameters ..............................................................................................................................22
7.2.1 Lift-dedicated digital output functions............................................................................................................................................29
7.3 Ramp Function ...................................................................................................................................................................30
7.3.1 Space calculation and acceleration / deceleration ramps settings ...............................................................................................30
7.3.2 Short Floor Function .....................................................................................................................................................................31
7.4 Startup Menu ......................................................................................................................................................................32
7.6 Timer 1 function ..................................................................................................................................................................38
8.3 List of drive alarm events ...................................................................................................................................................41
Indicates a procedure, condition, or statement that, if not strictly observed, could result in personal injury or
death.
Indicates a procedure, condition, or statement that, if not strictly observed, could result in damage to or destruction of equipment.
Indicates a procedure, condition, or statement that should be strictly followed in order to optimize these applications.
Note!
Indicates an essential or important procedure, condition, or statement.
1 - Safety Precautions
According to the EEC standards the AGL50-EV and accessories must be used only after checking that the
machine has been produced using those safety devices required by the 89/392/EEC set of rules, as far as the
machine industry is concerned. These standards do not apply in the Americas, but may need to be considered in equipment being shipped to Europe.
Drive systems cause mechanical motion. It is the responsibility of the user to insure that any such motion
does not result in an unsafe condition. Factory provided interlocks and operating limits should not be bypas-
sed or modied.
Electrical Shock and Burn Hazard:
When using instruments such as oscilloscopes to work on live equipment, the oscilloscope’s chassis should
be grounded and a differential amplier input should be used. Care should be used in the selection of probes
and leads and in the adjustment of the oscilloscope so that accurate readings may be made. See instrument
anufacturer’s instruction book for proper operation and adjustments to the instrument.
Fire and Explosion Hazard:
Fires or explosions might result from mounting Drives in hazardous areas such as locations where ammable
or combustible vapors or dusts are present. Drives should be installed away from hazardous areas, even if
used with motors suitable for use in these locations.
Strain Hazard:
Improper lifting practices can cause serious or fatal injury. Lift only with adequate equipment and trained
personnel.
Drives and motors must be ground connected according to the NEC.
Replace all covers before applying power to the Drive. Failure to do so may result in death or serious injury.
Adjustable frequency drives are electrical apparatus for use in industrial installations. Parts of the Drives are
energized during operation. The electrical installation and the opening of the device should therefore only be
carried out by qualied personnel. Improper installation of motors or Drives may therefore cause the failure of
the device as well as serious injury to persons or material damage. Drive is not equipped with motor overspeed protection logic other than that controlled by software. Follow the instructions given in this manual and
observe the local and national safety regulations applicable.
Always connect the Drive to the protective ground (PE) via the marked connection terminals (PE2) and the
housing (PE1). AGL50-EV Drives and AC Input lters have ground discharge currents greater than 3.5 mA.
EN 50178 species that with discharge currents greater than 3.5 mA the protective conductor ground connection (PE1) must be xed type and doubled for redundancy.
The drive may cause accidental motion in the event of a failure, even if it is disabled, unless it has been
disconnected from the AC input feeder.
Never open the device or covers while the AC Input power supply is switched on. Minimum time to wait before
working on the terminals or inside the device is listed in section 1.1.
4 AGL50-EV
Do not connect power supply voltage that exceeds the standard specication voltage uctuation permissible.
Warning
Caution
If excessive voltage is applied to the Drive, damage to the internal components will result.
Do not operate the Drive without the ground wire connected. The motor chassis should be grounded to earth
through a ground lead separate from all other equipment ground leads to prevent noise coupling.
The grounding connector shall be sized in accordance with the NEC or Canadian Electrical Code.
The connection shall be made by a UL listed or CSA certied closed-loop terminal connector sized for the
wire gauge involved. The connector is to be xed using the crimp tool specied by the connector manufactu-
rer.
Do not perform a megger test between the Drive terminals or on the control circuit terminals.
Because the ambient temperature greatly affects Drive life and reliability, do not install the Drive in any location that exceeds the allowable temperature.
If the Drive’s Fault Alarm is activated, consult the chapter 8. TROUBLESHOOTING of this instruction book,
and after correcting the problem, resume operation. Do not reset the alarm automatically by external sequence, etc.
Be sure to remove the desicant dryer packet(s) when unpacking the Drive. (If not removed these packets may
become lodged in the fan or air passages and cause the Drive to overheat).
The Drive must be mounted on a wall that is constructed of heat resistant material. While the Drive is opera-
ting, the temperature of the Drive’s cooling ns can rise to a temperature of 194° F (90°C).
Note!
Do not touch or damage any components when handling the device. The changing of the isolation gaps or the
removing of the isolation and covers is not permissible.
Protect the device from impermissible environmental conditions (temperature, humidity, shock etc.)
No voltage should be connected to the output of the drive (terminals U2, V2 W2). The parallel connection of
several drives via the outputs and the direct connection of the inputs and outputs (bypass) are not permissible.
A capacitative load (e.g. Var compensation capacitors) should not be connected to the output of the drive
(terminals U2, V2, W2).
The electrical commissioning should only be carried out by qualied personnel, who are also responsible for
the provision of a suitable ground connection and a protected power supply feeder in accordance with the
local and national regulations. The motor must be protected against overloads.
No dielectric tests should be carried out on parts of the drive. A suitable measuring instrument (internal resi-
stance of at least 10 kΏ/V) should be used for measuring the signal voltages.
In case of a three phase supply not symmetrical to ground, an insulation loss of one of the devices connected to the same network can cause functional problem to the drive, if the use of a delta/wye transformer is
avoided (see par. 3.4).
If the Drives have been stored for longer than two years, the operation of the DC link capacitors may be
impaired and must be “reformed”.
Before commissioning devices that have been stored for long periods, connect them to a power supply for
two hours with no load connected in order to regenerate the capacitors, (the input voltage has to be applied
without enabling the drive).
Note!
The terms “Inverter”, “Controller” and “Drive” are sometimes used interchangably throughout the industry. We
will use the term “Drive” in this document.
AGL50-EV 5
1.1 Discharge time of the DC-Link
TypeInTime (seconds)
204010.1300
205513300
207517.7300
Tabella 1.1 DC Link Discharge Times
This is the minimum time that must be elapsed since a Drive is disconnected from the AC Input before an operator may
service parts inside the Drive to avoid electric shock hazard.
Condition:
These values consider a turn off for a Drive supplied at 480Vac +10%, without any option, ( the charge
for the switching supply is the regulation card, the keypad and the 24Vdc fans “if mounted”).
The Drive is disabled. This represents the worst case condition.
2 - Introduction
AGL50-EV is a series of dedicated drives used to control lift asynchronous motors ranging from 4 to 7.5 kW.
Thanks to the special lift application software, it is best used in case of plant modernization and, in general, in all open
loop applications up to 1 m/s.
The easy and adaptable programming procedure can be managed via the alphanumeric keyboard or via the PC congurator and it allows the drive fast commissioning.
Available options on demand:
- External EMC input lters
- External Input / Output chokes
- External braking resistors (connected between terminals C and BR1).
6 AGL50-EV
3 - Environment
Attention
3.1 Environmental Conditions
Installation location ��������������������� Pollution degree 2 or lower (free from direct sunligth, vibration, dust, corrosive or inammable
gases, fog, vapour oil and dripped water, avoid saline environment)
Installation altitude ���������������������� Max 2000m (3281 feet) above sea level; above 1000m a current reduction of 1.2% for every
100m (328 feet) of additional height applies.
Mechanical conditions for installation ������� Vibrational stress: EN 60721-3-3 Class 3M1
Operation temperature ������������������ -10…50°C (14°…122°F). At above 40°, 2% derating for each °C, at 50°, 20% derating.
Air humidity (operation) ������������������ 5 % to 85 %, 1 g/m3 to 25 g/m3 without moisture condensation or icing (Class 3K3 as per
EN50178)
Air pressure (operation) [kPa] ������������� 86 to 106 (Class 3K3 as per EN50178)
Drive shall operate under environmental service conditions (climatic, mechanical, pollution, ...) dened in
EN61800-2 as for “usual service conditions”.
3.2 Storage and transport
Temperature:
storage ������������������������������ -20…+55°C (-4…+131°F), (class 1K4 as per EN50178)
transport ����������������������������� -20…+60°C (-4…+140°F), class 2K3 as per EN50178,
Air humidity :
storage ������������������������������ 5% to 95 % (Class 1K3 as per EN50178)
1) Drives are designed to be powered from standard three phase lines that are electrically symmetrical with respect
to ground (TN or TT network).
2) In case of supply with IT network, the use of delta/wye transformer is mandatory, with a secondary three phase
wiring referred to ground.
In case of a three phase supply not symmetrical to ground, an insulation loss of one of the devices connected to the same network can cause functional problem to the drive, if the use of a delta/wye transformer is
avoided.
Please refer to the following connection sample.
Mains connection and inverter output
The drivea must be connected to an AC mains supply capable of delivering a symmetrical short circuit current lower or
equal to the values indicated on table. For the use of an AC input choke see chapter 4.
Note from the table the allowable mains voltages. The cycle direction of the phases is free.
Voltages lower than the min. tolerance values can cause the block of the inverter.
Adjustable Frequency Drives and AC Input lters have ground discharge currents greater than 3.5 mA. EN 50178 species
that with discharge currents greater than 3.5 mA the protective conductor ground connection (PE1) must be xed type.
8 AGL50-EV
AC Input Current
Note!
The Input current of the Drive depends on the operating state of the connected motor. The tables (chapter
3.4) shows the values corresponding to rated continuous service, keeping into account typical output power
factor for each size.
3.5 AC Output
Type204020552075
Pnmot (recommended motor output):
@ Uln=400Vac; fsw=default [kW]45.57.5
@ Uln=460Vac; fsw=default [Hp]57.510
U2 Max output voltage[V]0.98 x Uln (AC Input voltage)
f2 Max output frequency[Hz]500 Hz (V/f)
InRated output current::
@ Uln=400Vac; fsw=default [A]10.11317.7
@ Uln=480Vac; fsw=default [A]8.611.714.9
Switching frequency fsw (Default) (5)[kHz]8
Switching frequency fsw (higher) (5)[kHz]10,12
Iovld[A]Short term overload current. 170% of In for 10s on 100s.
Derating factor
Kv (1)0.87
Kt (2)0.8
Kf(3)0.85; 0.7
Kalt (4)1.2
Braking unit intervention threshold (@ 380 V - 480 V)[Vdc]ON = 780 Vdc, OFF= 770 Vdc (6)
(1): Derating factor for mains voltage at 460 Vac
(2): Derating factor for 50°C ambient temperature (2 % each °C > 40 °C)
(3): Derating factor for higher switching frequency
(4): Derating factor for installation at altitudes above 1000 meters a.s.l.. Value to be applied at each 100 m increase
above 1000 m
(5) It is possible to set a xed switching frequency (from 4 to 12 kHz depending on size and with derating where applicable).
Otherwise it is possible to set a variable switching frequency between two levels (hswf and Iswf) dened according
to size, heat sink temperature and stator frequency:
TypeHigher sw frequency
[kHz]
Lower sw frequency
[kHz]
F out
[Hz]
T
[°C]
204084364
205584360
207584360
The output of the Drive is ground fault and phase to phase output short protected.
Nota!
The connection of an external voltage to the output terminals of the Drive is not permissible! It is allowed to
disconnect the motor from the Drive output, after the Drive has been disabled.
The rated value of direct current output ( Icont ) depends on the ambient temperature ( KT ) and the switching frequency
( Kf) if higher than the default setting:
Icont = In x Kt x Kf
(6) With parameter P.344 “BU threshold factor” is possible change the threshold in use:
Reference value ����������������������� 0.1 Hz (Resolution of Reference preset via terminals)
0.1 Hz (Resolution of Reference preset via interface)
10 AGL50-EV
3.8 Dimensions and installation guidelines
104 (4.09)
212 (8.35)
190 (7.48)
4.6 (0.18)
15.5 (0.61)
130 (5.12)
221 (8.70)
176.5 (6.95)
122 (4.80)
M4
54.5 (2.15)
212 (8.35)
104 (4.09)
202 (7.95)
190 (7.48)
104 (4.09)
5 (0.2)
M4
123 (7.84)
M4
mm (inches)
Wall mounting Mounting with external dissipator
TypeWeight
[kg][lbs]
2040 ... 20753.06.6
AGL50-EV 11
Mounting Clearance
10mm
0.39()
150 mm (6)
50 mm (1.97)
20 mm
(0.79)
150 mm (6)
10mm
(0.39)
The Drives must be mounted in such a way that the free ow of air is ensured.
The clearance to the device must be at least 150 mm (6 inches).
A space of at least 50 mm (2 inches) must be ensured at the front.
Maximum angle of inclination: 30° with respect to the vertical axis.
Devices that generate a large amount of heat must not be mounted in the direct vicinity of the frequency inverter.
Fastening screws should be re-tightened after a few days of operation.
12 AGL50-EV
4 - Wiring Procedure
4.1 Power Section
U1/L1, V1/L2, W1/L3 AC mains voltage (3 x 380 V (-15%) ... 3 x 480 V (+10%)
PE1 Mains ground connection (on terminal)
BR1 Braking unit resistor command (braking resistor must be connected between BR1 and C)
The inverter must be fused on the AC Input side.
Use fast-acting fuses only. Use the fuses shown in the table below.
Connections with three-phase inductance on AC input will improve the DC link capacitors life time.
Sizes
DC link capacitor hours
of service life [h]
TypeCodeTypeCode
EuropaAmerica
204010000GRD2/20F4D15A70P20S7G48
205510000GRD2/25F4D16A70P30S7I50
207510000GRD2/25F4D16A70P30S7I50
External fuses of the Power Section DC input side
Tightening
torque (min)
Use fast-acting fuses only. Use the fuses shown in the table below.
Sizes
TypeCodeTypeCode
EuropaAmerica
2040GRD2/20F4D15A70P20S7G48
2055GRD2/25F4D16A70P30S7I50
2075GRD2/25F4D16A70P30S7I50
Fuse manufacturers: Type GRD... , Z14... 14 x 51 mm Jean Müller, Eltville
A70... Ferraz
FWP... Bussmann
Input chokes
The three-phase mains choke is strongly recommended in order to:
- limit the RMS input current of the AGL50-EV inverter.
- increase the life of intermediate circuit capacitors and reliability of input diodes.
- reduce the harmonic distortion of the current absorbed by the grid to typical values of 70% (with rated current)
SizesTHDIn @ 400 V [A]TypeCode
2040
205513LR3y-2055S7AB5
< 70 %
9LR3y-2040S7AAG
207516LR3y-2075S7AB6
AGL50-EV 13
Use the following AC chokes to reduce the line current THD even more (< 35%).
Warning
SizesTHDIn @ 400 V [A]TypeCode
2040
205512LR3y-2055-35%S7HB2
< 35%
8LR3y-2040-35%S7HB1
207515LR3y-2075-35%S7FO9
Output chokes
Output chokes are used to reduce the effects of the dv/dt of the power modules (IGBT). Voltage fronts can damage the
electrical insulation of the motors or, if the motor cables are long (typically more than 100 m in length) or highly capacitive, they can cause drive malfunctions and the repeated generation of overcurrent (OC) or desaturation (OCH) alarms.
The output chokes are listed in the table below:
Sizes
Mains
inductance
[mH]
Rated
current
[A]
Saturation
current
[A]
TypeCode
20400.8710.120LU3-QX02S7FL3
20550.871634LU3-005S7FG3
20750.512757LU3-011S7FG4
Internal braking unit
Internal braking units with external braking resistors (wired between terminals C and BR1) are used to prevent dangerous
DC link voltage levels in case of braking. Technical data of the internal braking unit (50% duty cycle)
SizesRated current
[Arms]
Peak current
[Apeak]
Minimum braking R value
[Ohm]
20405.78100
20558.51267
20758.51267
Braking Resistors
The braking resistors can be subject to unforeseen overloads due to possible failures.
The resistors have to be protected using thermal protection devices. Such devices do not have to interrupt
the circuit where the resistor is inserted but their auxiliary contact must interrupt the power supply of the drive
power section. In case the resistor foresees the precence of a protection contact, such contact has to be used
together with the one belonging to the thermal protection device.
Recommended resistors for use with internal braking unit:
Max Overload
energy, 30”- duty-
cycle 25%
[kJ]
Pn cont
(*)
[W]
SizesResistor typeCode
Max Overload
energy, 1”- duty-
cycle 10%
2040RF 200 100RS8SA151.54200100
2055RF 200 68RS8SA141.5420068
2075RF 400 68RS8SA163.51040068
Resistors protection degree: IP44.
The braking resistor is optional and has always to be mounted externally.
(*) rated power with continuous operation. Without heat sink.
If the resistors are mounted on unpainted radiation plates (thermal resistance shown) the power ratings are
those shown in the table below. In overload conditions, heavier duty cycles can be set proportional to the
power ratings.
14 AGL50-EV
Rbr
[Ohm]
Sizes
Warning
Caution
Radiator Therm. Res.
( °C/W )
RF 200 100R0.75400
RF 200 68R0.55550
RF 400 68R0.4750
Optional EMC lters
An external EMI lter can be used to meet the requirements of EN 12015.
P Cont. serv.
( W )
SizesFilter typeCode
EN61800-3
(Motor cable length)
2040EMI-FTF-480-7S7GHL5 m
2055EMI-FTF-480-16S7GHO5 m
2075EMI-FTF-480-16S7GHO5 m
4.2 EMC compliant electrical cabinet wiring rules
In a domestic environment, this product may cause radio inference, in which case supplementary mitigation
measures may be required.
Panels and cabinets
Mounting panel and cabinet (including the doors) have to be grounded, with a direct connection to the ground bus, using
strapwire.
Removal of the paint from the support areas
The paint should be removed from the choke, mounting panel and chassis support areas.
The anodized aluminium does not conduct.
Ground terminals of the inverter
The inverters are provided with two ground terminals: one must be connected to the ground bus and the other to the lter.
Ground terminal of the choke
The earth terminal of the choke must be connected to the ground bus.
Shielding of cables for analog signals
Analog signals must be shielded (each signal must be contained in the screen united with the zero volt), the same is true
for the constant references (E.g.. 10V). The shield must be grounded at 360° using the omega connectors available on
the support panel of the regulation board. This is in front of the terminals strip on the bar above the board.
Note!
Cable shields should be grounded at one end only.
Min. distance between signal and power cables
The minimum distance between parallel signals and power cables is 30cm (12 inches). Possible crossings have to be
made at 90°. In case of double cabinets (entry to the insde of the cabinet on both sides with 2 different panels installed)
it is advisable to have all signals cables conveyed into troughs mounted on the inverter side (front) and to pass motor
cables on the other side (back) trough. In case of single cabinets, it is advisable to let the power cable run vertically, while
signal cables run horizontally, keeping the maximum possible distance.
Shielding of the supply for an AC motor
The AC motors have to be supplied through a four pole shielded cable (three phases plus a green/yellow ground wire),
or through four unshielded cables, which are inserted inside a metal channel. It is important that a direct connection (four
cables) between the panel grounding and the motor ground has been made and that the fourth cable had been inserted
in a shield.
AGL50-EV 15
Ground connection to both sides of the cable shield (AC motor)
Schermo/Shield
Connettore Omega
Omega connector
Area non verniciata
Not painted area
Pannello di fissaggio
Mounting panel
The shield of the supply cable of the AC motors must be grounded on both sides in order to obtain 360° contact, that
means the whole shield. This can be accomplished using suitable metallic EMC cables press grounded at a full 360° at
the input of the cabinet and of the motor’s terminal strip. If this connection is not possible, the shielded cables should
be brought inside the cabinet and connected with an omega connector to the mounting panel. The same must be done
on the motor side. In case a 360° connection on the motor’s terminal strip is not possible, the shield must be grounded
before entering into the terminal strip. This should be done on the metal support of the motor, using an omega connector
(see gure). In case a metal duct has to be used, it should be grounded at a full 360° where possible.
Pigtail avoidence
While grounding the shieldes of the cables, one has to use a 360° connection (E.g.: omega bus as in the gure 4.2) with
a pigtail connection to be absolutely avoided. By pigtail is meant the connection to earth ground of the cable shield by
means of an additional wire.
Direct connection between the ground bus and motor chassis
Independently from ground-connection of the motor’s chassis, it must always be connected to the ground wire (yellow/
green) coming from the panel ground bus.
Max length of the AC motor’s cables inside the cabinet
From the grounding of the screen side cabinet of the inverter terminal strip, the supply’s cables have to measure 5 meters
(16.4 feet) maximum.
Mounting sequence for EMI-... lters with inverter
In case of inverters, these lters have to be serie-connected between the inverter and the AC mains. The connection
between the lter and inverter’s terminals must be done with a four poles cable, whose max.length is 30 cm. (12 inches).
If that connection is longer, the cable must be shielded.
Grounding of EMI-... lters with inverter
The yellow/green ground wire of the four poles cable must be connected on one side directly to one of the two gounding
terminals of the inverter, the other side to one of the two lters grounding terminals. The other grounding terminal of the
lter must be brought directly to the grounding bus of the cabinet.
Figura 4.2.OMEGA plug: grounding 360° of a shielded cable.
4.3 Cooling fans
No connection is required, the internal fans are power supplied by an internal circuit.
SizesHeat dissipation)Fan capacity
Heat sink
[W]
[m3/h]
204018020-
20552052 x 20-
20752802 x 2011
16 AGL50-EV
Internal
[m3/h]
4.4 Regulation Section
Strip1
Strip2
141618
19
212725
20
23
24
222826
9
11
3
1
5
4
2
6
131517
7
10
12
8
S T R I P 1
Term. Designation Function (Signal level MAX)
1/3 n.a.
5 Analog output 1 VOLTAGE programmable analog output (0...10V)
11 Digital output 1+ Programmable digital output (Optomos)
Default : I100 = [51] Contactor (+30V / 40mA)
13 Digital output 1-Programmable OPEN COLLECTOR digital output (negative terminal)
15 RS485 Link+ Link+ (RxA / TxA) signal of RS 485 serial line
17 RS485 Link- Link- (RxB / TxB) signal of RS 485 serial line
19 RS 485 eq. ref. Equipotential reference of RS 485 serial line
21 COM Relay 1Common contact RELAY 1 digital output (250Vac / 2A, 30Vdc / 2A)
23 Digital output 1 Programmable RELAY digital output, NO contact (250Vac / 2A, 30Vdc / 2A)
Default : I101 = [54] Brake cont
25 COM Relay 2Common contact RELAY 2 digital output (250Vac / 2A, 30Vdc / 2A)
17 Digital output 2 Programmable RELAY digital output, NO contact (250Vac / 2A, 30Vdc / 2A)
Default : I102 = [02] No alarms
S T R I P 2
Term. Designation Function (Signal level MAX)
2/4 n.a.
6 COM analog. In/Out Potential reference of analog inputs/outputs -
8 Analog input 1Programmable VOLTAGE analog input
Default : I.200 = [1] -10...+10V (±10V / 0.5mA)
10 0 V 24 0 V 24 potential reference
Programmable digital inputs (24Vdc/ 5mA, 12...30Vdc max)
12 Digital input 1Default : I.000 = Enable src
14 Digital input 2 Default : I.001 = Run Fwd src
16 Digital input 3Default : I.002 = Run Rev src
18 Digital input 4Default : I.003 = Freq sel 1 src
20 Digital input 5Default : I.004 = Freq sel 2 src
22 Digital input 6Default : I.005 = Freq sel 3 src
24 COM Digital inputs 0 potential reference of digital inputs
26 0 V 24 0 V 24 potential reference
28 + 24V OUT + 24 Vdc potential voltage reference (+21Vdc / 75mA)
n.a. = not assigned
AGL50-EV 17
4.5 RS 485 Serial Interface
XS1 - Drive Side
XS2 - PC Side
The RS 485 serial line on the drives of the AGL50-EV series allows the data transmission through a loop made of two
symmetrical conductors, which are twisted with a common shield. The maximum transmission speed is 38400 Baud.
The transmission is performed via a standard RS 485 differential signal (half-duplex).
If two or more drives are connected on the serial line (Multidrop conguration), the OPT-QX option has to be used on each
device.
This option has to be inserted between the inverter terminals and the transmission data cable.
With the Multidrop conguration it is possible to connect a maximum of 20 units of AGL50-EV inverters (for further details
see the OPT-QX manual).
The shield of serial line cable must be connected to the ground.
4.5.1 RS485 serial terminals
The RS 485 serial line is supplied through 15, 17 and 19 terminals, placed on the regulation card of the inverter.
The differential signal is transmitted on the Pin 15 (TxA/RxA) and on the Pin 17 (TxB/RxB). Terminal 19 is used as
equipotential reference of the serial line.
Note!
As for the connection of the serial line, make sure that the power cables and the cables controlling the contactors and the auxiliary relays are located into different panduits.
4.5.2 Serial protocol
The serial protocol is set via the “I.600 - Serial link cfg” parameter, which allows the selection of the following types:
proprietary protocol FoxLink, RTU Modbus (default) and Jbus.
The serial address is set via the “I.602 - Device address” parameter. Further details about the parameter transmission,
the parameter type and the value range can be found in the tables of Chapter 7.1 (INTERFACE Menu / Serial Conguration).
Table 4.6.1: Recommended Cable Section and Length for the Connection of Encoders
+24V
E
External
024V
Cable section [mm2] 0.22 0.5 0.75 1 1.5
Max Length. m [feet] 27 [88] 62 [203] 93 [305] 125 [410] 150 [492]
Requirements:
Digital encoder:
• max frequency: 25 kHz (select the appropriate number of pulses depending on required max. speed)
• Channels :
- one-channel: A (one-channel complementary A-,NOT allowed)
- two-channel: A and B (two-channel complementary A- and B-, NOT allowed).
Encoder loss detection is not possible.
• Power supply: + 24V externally supplied.
• The digital inputs common (terminal 24) have to be rightly connected to the external supply:
- to 0 V of supplier, if the encoder is PNP type
- to + 24 V of supplier, if the encoder is NPN type.
Note!
If Digital input 5 and Digital input 6 are used as encoder input, I.004 and I.005 must be set to [0] None.
Than encoder feedback parametrizzation must be execute.
AGL50-EV 19
5 - Drive Keypad Operation
Caution
Codice parametro
(Menu + numero da 000 a 999)
Menu:
d
S
I
=DISPLAY
=STARTUP
=INTERFACE
F
P
A
C
=FREQ & RAMPS
=PARAMETER
=APPLICATION
=COMMAND
Limit Alarm
Prg
RevFwd
In this chapter the parameters management is described, by using the drive keypad.
5.1 Keypad
Changes made to parameter have immediate effect on drive operation, but are not automatically stored in
permanent memory. An explicit command is required to permanently store the parameters: “C.000 Save
parameters”.
RevFwdLimit AlarmPrg
Prg
Enter
Prg Scroll menù: Allows navigation thruogh the drive main menu (d.xxx, S.xxx, I.xxx, F.xxx, P.xxx, A.xxx and
C.xxx). Also used to exit the editing mode of a parameter without appling the changes.
E Enter key: Used to enter the editing mode of the selected parameter or to conrm the value.
▲UP key: Used to scroll up through parameters or to increase numeric values while in editing mode; it can
also be used to increase motorpotentiometer reference value, when F.000 Motorpot ref parameter
is displayed (F, FREQ RAMP menu).
▼DOWN key: Used to scroll down through parameters or to decrease numeric values while in editing mode; it
can also be used to decrease motorpotentiometer reference values, when F.000 Motorpot ref
parameter is displayed (F, FREQ RAMP menu).
I Start key: Used to START the drive via keypad; requirements:
+24V between 12 & 26 terminals (Enable)
+24 V between 14 & 26 terminals (Run Fwd) or + 24 V between 16 & 26 terminals (Run Rev)
PRG (Yellow Led) Flashes if the parameters have not been permanently saved to memory.
REV (Green Led) Reverse running
FWD (Green Led) Clockwise motor rotation
Limit (Yellow Led) Inverter limit state
Alarm (Red Led) Inverter alarm state
Note!
The FWD LED lights up during the direct current injection phase (start and stop).
20 AGL50-EV
5.2 Moving through the drive main menu
settings
Soon after, the keypad display will show d.000 Output frequency parameter of DISPLAY menu.
0.00
Prg
Prg
d.000
Prg
S.000
Prg
I.000
Prg
F.000
Prg
P.000
Prg
Menu of read-only parameters (display)
Menu of basic drive start up parameters
Menu of input/output drive settings
(digital/analog)
Menu of multi frequencies and ramps
Menu of read/write drive parameters
A.000
Prg
C.000
Menu of PID function settings
Menu of control-type parameters
(Save, Load default, etc.)
AGL50-EV 21
5.3 Scrolling through the drive parameters
----------------
S.000
S.001
S.100
S.901
E
Decrease
Increase
E
To confirm
new setting
S.200
10.0
0.0
-200.0
STARTUP menu example:
5.4 Parameters modication
Example: how to change a frequency reference (STARTUP menù ).
Note!
Same procedure is also valid to Enable/Disable a function (ex.: S.301 Auto boost en) or program the drive I/
Os (i.e.: I.100 Dig output 1 cfg, etc. …).
22 AGL50-EV
6 - Commissioning suggestions
Before changing the parameter settings make sure that the starting values are default values.
Change the parameters one at the time; if the change on any parameter is not effective, restore the parameter initial value before changing another one.
• In order to avoid problems linked to running comfort, it is advisable to perform a preliminary control of the motor
parameters.
Check in the STARTUP menu that the value set in the following parameters corresponds to the motor nameplate
data:
S.100 Base voltage Inverter maximum output voltage (Vrms).
S.101 Base frequency Motor base frequency (Hz).
S.150 Motor rated curr Motor rated current (Arms).
S.151 Motor pole pairs Number of motor polepairs.
S.152 Motor power fact (cos phi) Motor input power factor with rated current and voltage.
• In order to avoid too high settings of the acceleration and deceleration values (jerk), make sure that the slowing-down
distances correspond to those listed in the table:
Suggested slowing-down distances
Plant rated speed (m/s)0,60,81,0
Suggested slowing-down distance (mm)80010001300
Such distances grant a high running comfort with the factory set jerk values.
• The default speed levels can be selected on the terminal 18. It is advisable to use the frequencies as follows:
S.200 Frequency ref 0 Slow speed: it is the oor reaching speed (frequency)
S.201 Frequency ref 1 High speed: it is the rated speed (frequency) required by the motor for that
specic plant.
Other speeds (maintenance, rephasing procedure etc.) can be selected as per table 7.2.
• In the open loop plants (without encoder), the boost can be increased if the lift car tends to rotate in the opposite
direction during the starting phase or if it can not start in spite the running speed has been set (S.300 Manual boost,
default = 3). The boost should be gradually increased by 1% at the time. Too high values cause the intervention of
the current limit alarm.
AGL50-EV 23
7 - Default lift conguration
Lift commands are part of a dedicated control word. Each command is assigned to a physical digital input terminal. All
the main commands are given from the DI on the standard regulation board (see table 7.1).
Similarly, lift digital outputs are congured to perform the most common functions needed to realize a standard application, such as run and brake contactor control logic.
In AGL50-EV drives, commands are always coming from Lift Control Word. It is possible to issue the Run Fwd or Run Rev commands from keypad, in order to simplify the startup procedure.
Frequency references are coming from the multi-speed selector, which is the required setting for most applications.
However, it is possible to use other sources for the frequency reference, such as analog inputs or Motopotentiometer.
Ramps are initialized to a standard set of jerks and acceleration/deceleration that should meet the requirements of most
low speed applications. It is possible, though not recommended, to disable the S-shape and use linear proles (F.250 =
0). In that case the jerk parameters will have no effect.
7.1 Command Logic
In the standard version, drive commands may come from several different sources (keypad, terminals, serial line etc.).
In the Lift version the parameter dening the source of the commands can only assume the following values:
P.000 Cmd source sel = “[0]CtrlWordOnly”
Command assignment
Drive commandSource parameterDeafult settingPossible settingI PA
SettingTerminal
Enable srcI.000[2] DI 112[0] False100
[1] True
[2] DI 1
[3] DI 2
[4] DI 3
[5] DI 4
[6] DI 5
[7] DI 6
[8] DI 7
[9] DI 8
[10] DI Exp 1
[11] DI Exp 2
[12] DI Exp 3
[13] DI Exp 4
[14] AND 1
[15] AND 2
[16] AND 3
[17] OR 1
[18] OR 2
[19] OR 3
[20] NOT 1
[21] NOT 2
[22] NOT 3
[23] NOT 4
[24] FrqSel match
[25] Short Floor g
[26] Contactor (fw 03-07)
[27] Timer 1 (fw 03-07)
Run Fwd srcI.001[3] DI 214See list of I.000101
Run Rev srcI.002[4] DI 316See list of I.000102
Freq Sel 1 srcI.003[5] DI 418See list of I.000103
Freq Sel 2 srcI.004[6] DI 520See list of I.000104
Freq Sel 3 srcI.005[7] DI 622See list of I.000105
Freq Sel 4 srcI.006[0] FalseSee list of I.000106
Ramp Sel 1 srcI.007[25] Short Floor FlgSee list of I.000107
Ramp Sel 2 srcI.008[0] FalseSee list of I.000108
Ext fault srcI.009[0] FalseSee list of I.000109
Src Reset AllarmI.010[0] FalsoSee list of I.000110
Bak pwr act srcI.011[0] FalseSee list of I.000111
Forced stop srcI.012[0] FalseSee list of I.000185
Table 7.1 – Command assignment
24 AGL50-EV
Each command may come from any of the drive digital input terminals (either standard or expanded), or can be a logical
combination of terminal inputs, obtained by using the drive internal programmable area
It is anyway possible to assign commands different from the default ones:
For example, if we want the Enable command to come from the digital input 3 of the drive (terminal 16 on the regulation
board), we have to set parameter I.000 Enable src to the value “[4] DI 3”.
Note:
If the source of a command is specied as an expanded DI, and the I/O expansion board is not mounted, the
command will always be inactive (FALSE).
A brief description of each command follows.
Enable src The Enable command must always be present, in order to activate the inverter output bridge. If the
Enable input is not present, or the Enable signal is removed at any time during the Lift sequence,
the output stage of the drive is disabled, and the Run contactor is open, regardless of the status of
all the other inputs.
Run Fwd src(Upward command)
Closing the input 14, the upward Lift sequence is started (see Figure 7.1).
Run Rev src(Downward command)Closing the input 16, the downward Lift sequence is started (see Figure 7.1).
Note:
Note:
The direction of the motion can also be reversed by setting a negative frequency reference. With a negative
frequency reference, the Run Fwd src command will cause a downward motion, while a Run Rev src command will cause the cabin to move upward.
The lifting sequence will not start if both Run Fwd src and Run Rev src commands are activated at the same
time.
Freq Sel 1 ... 4 src (Selection of the speed reference)
The binary code dened by the status of these signals selects the frequency reference (speed) for
the ramp generator (see Fig.7.2), according to the following table:
Freq Sel 4Freq Sel 3Freq Sel 2Freq Sel 1CodeActive frequency reference
The last multi-frequency has also a special meaning when using the backup power supply. If the drive is
being fed by the backup power supply, the frequency reference is clamped to the value dened by the parameter F.115.
If the backup power supply is not used, F.115 can be used as one of the multi-frequencies and is selected by
setting to TRUE all the selectors (Freq Sel 1 to Freq Sel 4).
AGL50-EV 25
Ramp Sel 1 ... 2The binary code dened by the status of these signals selects the set of parameters for ramp pro-
le (jerks, acceleration and deceleration). By default, the rst ramp selector is commanded by the
ShortFloorFl (see chapter 7.3), while the second ramp selector is xed to FALSE. Therefore, the rst
ramp set is normally active, and the drive will automatically switch to the second ramp set whenever
a short oor is detected (see Fig.7.5).
External faultActivation of this command, will cause the drive to trip with an external fault alarm. If the alarm oc-
curs while a lift sequence is in process, the sequence is immediately aborted and the Run contactor
is open. In order to restore drive operation, an explicit Alarm Reset command is needed.
Fault reset src (Alarm reset) Activation of this command will restore drive operation after a trip.
Bak pwr act src This command tells to the drive that a backup power supply is being used. See chapter 9 for a de-
tailed description.
In order to simplify the drive startup, it is possible to issue Run Fwd src or Run Rev src commands from the “I-O” keys
of the drive keypad.
Typical example:
The user wants to execute tuning of the motor resistance, but does not want to issue the start sequence from the external
PLC. In this case, it is possible to program the drive as follows:
- Set parameter P.000 Cmd source sel = “[1] CtlWrd & kpd”
- Set parameter I.000 Enable src = “[1] True”
- Set parameter I.001 RunFwd src = “[1] True”
- Issue the command for tuning, by setting C.100 Measure stator R = [1]; the drive keypad will show the message
“tune”.
- Press the “I” key; the keypad will show the message “run”, meaning that the tuning procedure is in progress. Wait
until the procedure ends, and the keypad will show the message “done”.
Nota:
The motor output contacts must be closed during the tuning procedure, in order to allow current to ow into
the motor. Either hard-wire the RUN contactor closed during tuning procedure, or connect the dedicated
output of the drive to the RUN contactor.
- Once the tuning procedure is nished, restore the original settings for the parameters above, following the order:
I.001 Run Fwd src = “[3] DI 2”
I.000 Enable src = “[2] DI 1”
P.000 Cmd source sel = “[0] CtrlWordOnly”
26 AGL50-EV
K1MK2MK3M
C
D
BR1
U1/L1
W1/L3
V1/L2
K1M
PE1
3 Ph
AC
mains
U2/T1
W2/T3
V2/T2
PE2
K2M K3M
L1F1
3 Ph
Motor
+
K3MK2M
-
FR
FR(R)
L02
L01
Enable
Safety contacts
Run Fwd src
Run Rev src
Freq Sel 1 src
Regulation Board
Brake cont
Power Board
Brake
Brake cont
Braking resistor
12
14
16
18
20
Src Sel Freq 2
22
Src Sel Freq 3
28
25
27
RO 2
Motor not in Alarm
21
23
RO 1
DI 1
DI 2
DI 3
DI 4
DI 5
+24Vdc
DI 3
DI 6
11
13
DO 1 (NPN)
Contactor
+24V (terminal 28)
0V (terminal 26)
Load
11
13
DO 1 (PNP)
+24V28)(terminal
0V (terminal 26)
Load
Contactor
24
024V26
COM-DI
Note!
Fig.7.1 – Lift standard wiring
The connections indicated for command inputs represent the most common solution for an PNP typecommand.
Digital I/Os with internal supply.
AGL50-EV 27
7.2 Lift Sequence
I.000 Enable
I.001 Run Fwd
XOR
I.002 Run Rev
I.003 ... I.006
Freq Sel 1...4
10
D.007 Actual
speed
(Motor speed)
D.002 Output
current
(Inverter)
[51] Run
contactor
(*)
[45] DCbraking
(Motor)
(*)
[55] Lift
start (*)
(*): See 7.2.1
12 34567
[54] Brake
contactor
(*)
Timing diagrams of the lift sequence are reported in Fig. 7.2 and Fig. 7.3.
Fig. 7.2 – Standard lift sequence
1. S.250 Cont close delay (Default : 0,20)
2. S.251 Magnet time (Default : 1)
3. S.252 Brake open delay (Default : 0,20)
4. S.253 Smooth start dly (Default : 0)
5. S.254 DCBrake stp time (Default : 1)
6. S.255 Brake close dly (Default : 0,20)
7. S.256 Cont open delay (Default : 0,20)
Note:
Lift sequence will not start if there is no current owing on any of the motor windings during the initial injection
of DC-current. The minimum amount of current necessary to release the mechanical brake and initiate the lift
sequence is dened by A.087 Current pres thr. By setting the parameter to “0”, current check is disabled,
and the lift sequence will start even if the motor is disconnected from the drive.
28 AGL50-EV
10
Acceleration
567
a
b
b
a
P.440 Freq Thr1
S.201 Freq Ref1(F.101)
S.200Freq Ref0 (F.100)
Deceleration (**)
Jerk dec ini (**)
Jerk dec end (**)
Jerk dec end (**)
Jerk dec ini (**)
Deceleration (**)
I.000 Enable
I.001 Run Fwd
XOR
I.002 Run Rev
I.003 ... I.006
Freq Sel 1...4
D.007 Actual
speed
(Motor speed)
[51] Run
contactor
(*)
[45] DCbraking
(Motor)
(*)
[55] Lift
start (*)
(*): See 7.2.1
(**) S.230 ... S.245
[54] Brake
contactor
(*)
Fig. 7.3 – Detailed stopping sequence
a) S.260 Lift Stop Mode = [0] DC brake at stop
b) S.260 Lift Stop Mode = [1] Normal stop (Default)
7.2.1 Lift-dedicated digital output functions
Several specic functions can be programmed on the drive digital outputs, in order to check the correctness of the lift
sequence and to improve the interaction with the external sequencer. Here follows a list of the functions that can be
useful in lift applications.
DO Programming code Function description
[0] Drive ready TRUE when the drive is ready to accept a valid RUN command. Meaning that the drive
[1] Alarm state TRUE when the drive is in alarm status. Alarm reset is needed to restore operation
[2] Not in alarm TRUE when the drive is not in Alarm status.
[3] Motor run TRUE when the inverter output bridge is enabled and operating.
[4] Motor stop TRUE when the inverter output bridge is not operating (all six switches are open).
[5] Rev rotation TRUE when the motor is rotating counter-clockwise.
[31] Freq > thr1 TRUE when the motor speed (measured or estimated) is above the threshold dened
[32] Freq < thr1 TRUE when the motor speed (measured or estimated) is below the threshold dened by
[45] DC braking TRUE when DC injection is in progress.
AGL50-EV 29
is not in alarm, the dc-link pre-charge is completed and the safe-start interlock logic is
cleared.
by parameters P.440 and P.441.
parameters P.440 and P.441. This function is normally used to detect zero speed (see
sequence in Fig.7.2).
[51] Contactor TRUE when the Run contactor has to be closed, either for upward or downward motion.
[52] Contactor UP TRUE when the Run contactor for upward motion has to be closed.
[53] Contactor DOWN TRUE when the Run contactor for downward motion has to be closed.
[54] Brake cont TRUE when the mechanical brake has to be released.
[55] Lift start TRUE when the inverter output bridge is operating and no DC injection is being operated.
[78] Timer 1 out TRUE when the Timer function output is 1.
7.2.2 Speed indication
At power-on the drive keypad shows the speed of the lift car (parameter d.007), expressed in mm/s. Likewise, all the
variables related to the speed of the motor (d.008, d.302) are expressed in mm/s. The conversion between electrical Hz
and car speed is automatically performed by the drive, as explained in the following chapter. The conversion ratio can
also be overwritten by the user, by setting parameter P.600.
The parameter to be shown at power-on can be congured by setting the parameter P.580.
7.3 Ramp Function
Four independent jerks are available for each prole, together with linear acceleration and deceleration times. All prole
parameters are expressed in terms of car linear quantities. The equivalence between car speed v(m/s) and inverter output
frequency f(Hz) is automatically performed by the drive, based on the value of the following parameters:
- fb: S.101 Base frequency (Hz)
- vN: S.180 Car max speed (m/s)
The ramp prole is shown in Fig.6. Prole number 1 has been used as an example, but the same applies to all the four
available proles. The increase or decrease of the jerk values causes the increase or decrease of the running comfort.
Motor speed
D.007 Output speed
S.231-Acceleration 1
S.230-Jerk acc ini 1
Acceleration
S.232-Jerk acc end 1
S.233-Jerk dec ini 1S.235-Jerk dec end 1
S.234-Deceleration 1
Fig.7.4 – Lift ramp prole
7.3.1 Space calculation and acceleration / deceleration ramps settings
The space covered by the lift car during acceleration and deceleration ramps can be calculated off-line by the drive, by
executing the command: C.060 Calculate space . The results of the calculation can be monitored into the parameters:
d.500 Lift spacespace covered by the lift car (expressed in meters) when accelerating from zero to the
maximum speed (dened by S.180) and then immediately decelerating back to zero(one
oor travel)
d.501 Lift accel space space covered by the lift car (expressed in meters) when accelerating from zero to the
maximum speed (dened by S.180).
d.502 Lift decel space pace covered by the lift car (expressed in meters) when decelerating from the maximum
speed (dened by S.180) to zero.
Knowing the space needed to accelerate and decelerate the lift car with the ramp set in use, is useful to determine
whether the ramps are compatible with the position of the oor sensors before actually starting the drive. For example,
30 AGL50-EV
if the deceleration ramp is too slow, as compared to the re-aligning distance, the lift car could stop after the oor level.
If acceleration and/or deceleration ramps are too fast, the drive may reach the output current limit. In this case, the drive
will automatically clamp the current to a safe value, with a resulting loss of output torque. If the drive remains in limit
condition for the time specied by the parameter P.181 - Clamp alm HldOff (default setting is 1 second), an alarm will
be issued (“LF - Limiter fault”) and the lift sequence will be aborted. It is strongly recommended not to operate the drive
in current limit, since the desired speed prole cannot be achieved in that case, resulting in undesired oscillations. If the
drive reaches the current limit during the acceleration or deceleration phases, it is advised to slow down the ramps, until
the limit condition is avoided.
7.3.2 Short Floor Function
Sometimes, the space between adjacent oors is not constant, and there is one oor that may be nearer to the next one.
That situation is normally referred as “Short Floor”. It could happen that due to the reduced distance, the lift is required
to decelerate to the leveling speed, when the acceleration ramp to normal speed is still in progress. This will lengthen
the approaching phase, unless countermeasures are taken.
The drive is able to detect a Short Floor, by looking at the sequence.
The ag “ShortFloorFl” is set if the deceleration command is given during the acceleration phase.
I.007 Ramp sel 1 src = “[25] ShortFloorFl”
The ag is reset when the stop command is given, or when the sequence is aborted.
“ShortFloorFl” is default used to control the short oor, using the second set of ramps.
The regulation of the parameters from S.240 to S. 245 allows to dene the area to be covered before reaching the oor.
In case of short oor, if the lift overcomes the oor it means that the lift speed was too high and it is therefore necessary to
increase the jerk values (parameters S.242, S.243, S.244). If the plant works for a too long time with a low speed before
reaching the oor, the jerk values have to be decreased (parameters S.242, S.243, S.244).
A typical short oor sequence is reported in Fig. 7.5 .
I.000 Enable
I.001 Run Fwd
XOR
I.002 Run Rev
I.003 ... I.006
Freq Sel 1...4
D.007 Actual
speed
(Motor speed)
I.007 Ramp sel1src =
[25] ShortfloorFl
10
High speed setpoint
Ramp set 2
Ramp set 1
Ramp set 1
Leveling speed
Smooth start speed
Fig. 7.5 – Short oor sequence
Ramp references: 1 S.240 Jerk acc ini 2 4 S.243 Jerk dec ini 2
2 S.241 Acceleration 2 5 S.244 Deceleration 2
3 S.242 Jerk acc end 2 6 S.245 Jerk dec end 2
AGL50-EV 31
7.4 Startup Menu
Lift version has parameters that are organized with access levels, as follows:
Access levelAccessible parameters
1- Basic display parameters
- Command for save parameters
- P.998
2 (Default)- All level 1 parameters
- Startup parameters
- All commands
3All parameters
The access level is set by the parameter P.998 Param access lev.
Note! .
In order to make drive installation easy, all the parameters needed for standard setup are gathered in the STARTUP
menu. This menu consists of links to parameters present in different drive menus. Therefore, making a change to any of
the parameters in Startup, is equivalent to make the same change to the linked parameter in another menu.
The list of parameters in Startup menu of the lift version follows:
Note!
Menu S - Startup
Code Display (Description) Def. Min. Max
S.000 Mains voltage (linked to P.020) 380 230 480
When using GFeXpress, congurator, all parameters are accessible, regardless of what is specied by parameter P.998.
(*) = Size dependent
(ALIAS): On STARTUP menu only. Parameter code of same parameter on other menu .
Nominal voltage (Vrms) of the AC input mains.
S.001 Mains frequency (linked to P.021) 50 50 60
Nominal frequency (Hz) of the AC input mains.
S.100 Base voltage (linked to P.061) 380 50 528
Maximum inverter output voltage (Vrms). It should be set to motor rated voltage, as shown on the nameplate.
S.101 Base frequency (linked to P.062) 50 25 500
Motor base frequency (Hz). It is the frequency at which the output voltage reaches the motor rated (data on motor nameplate).
S.150 Motor rated curr (linked to P.040) (*) (*) (*)
Motor rated current (Arms). It should be set according to motor nameplate.
S.151 Motor pole pairs (linked to P.041) 2 1 60
Number of pole pairs of the motor (data on motor nameplate).
S.152 Motor power fact (linked to P.042) (*) (*) (*)
Motor input power factor at rated current and rated voltage. It should be set according to nameplate.
S.153 Motor stator R (linked to P.043) (*) (*) (*)
Equivalent resistance of the motor stator windings (Ohm). This value is important for correct operation of the automatic boost,
and slip compensation functions. It should be set to half of the resistance measured between two of the motor input terminals,
with the third terminal open. If unknown, it can be automatically measured by the autotuning command (see S.170).
S.170 Measure stator R (linked to C.100)0.50 0.01 5.00
The execution of this command allows the user to measure the equivalent stator resistance of the motor in use. After the
command is issued, it is necessary to initiate a standard run sequence, by giving enable and start commands. The inverter
will close the run contactor, but will not release the brake, allowing for current to ow in the windings. After the procedure is
successfully completed, the value of S.153 is automatically updated.
32 AGL50-EV
S.180 Car max speed (linked to A.090) 0.50 0.01 5.00
Speed of the lift car (m/s) when the inverter outputs the rated frequency.
S.200 Frequency ref 0 (linked to F.100) 10.0 -F.020 F.020
See description of S.207.
S.201 Frequency ref 1 (linked to F.101) 50.0 -F.020 F.020
See description of S.207.
S.202 Frequency ref 2 (linked to F.102)
S.203 Frequency ref 3 (linked to F.103)
S.204 Frequency ref 4 (linked to F.104)
S.205 Frequency ref 5 (linked to F.105)
S.206 Frequency ref 6 (linked to F.106)
S.207 Frequency ref 7 (linked to F.107) 0.0 -F.020 F.020
Frequency references (Hz) of the inverter. The selection of any of the above references is performed by the dedicated
selectors (Freq Sel 0 to 4). Although only 8 references are present in the startup menu, it is possible to use up to 16 different
references, available in the menu F.
S.220 Smooth start frq (linked to F.116) 2.0 -F.020 F.020
Frequency reference (Hz) used during the smooth start procedure.
S.225 Ramp factor 1 (linked to A.091) 1.00 0.01 2.50
Ramp accel/decel and jerks are dened by the parameters described below. However, for an easy setting, it is possible to
use a common extension factor to speed-up or slow down the ramps. For example, if S.225 is set to 0.5, all the parameters
related to the sets 1 and 3 of ramps (accels, decels and jerks) are halved, resulting in slower ramps.
S.226 Ramp factor 2 (linked to A.092) 1.00 0.01 2.50
Same as S.225, but it applies to the ramp sets 2 and 4.
S.230 Jerk acc ini 1 (linked to F.251) 0.50 0.01 10.00
Jerk (m/s3) applied at the beginning of an acceleration with ramp set 1 (Ramp set 1 is the one used by default, during normal
operation).
S.231 Acceleration 1 (linked to F.201) 0.60 0.01 5.00
Linear acceleration (m/s2) with ramp set 1.
S.232 Jerk acc end 1 (linked to F.252) 1.40 0.01 10.00
Jerk (m/s3) applied at the end of an acceleration with ramp set 1.
S.233 Jerk dec ini 1 (linked to F.253) 1.40 0.01 10.00
Jerk (m/s3) applied at the beginning of a deceleration with ramp set 1.
S.234 Deceleration 1 (linked to F.202) 0.60 0.01 5.00
Linear deceleration (m/s2) with ramp set 1.
S.235 Jerk dec end 1 (linked to F.254) 1.00 0.01 10.00
Jerk (m/s3) applied at the beginning of a deceleration with ramp set 1.
S.240 Jerk acc ini 2 (linked to F.255) 0.50 0.01 10.00
Jerk (m/s3) applied at the beginning of an acceleration with ramp set 2 (Ramp set 2 is the one used by default when a short
oor is detected).
S.241 Acceleration 2 (linked to F.203) 0.60 0.01 5.00
Linear acceleration (m/s2) with ramp set 2.
S.242 Jerk acc end 2 (linked to F.256) 1.40 0.01 10.00
Jerk (m/s3) applied at the beginning of a deceleration with ramp set 2.
S.243 Jerk dec ini 2 (linked to F.257) 1.40 0.01 10.00
Jerk (m/s3) applied at the beginning of a deceleration with ramp set 2.
S.244 Deceleration 2 (linked to F.204) 0.60 0.01 5.00
AGL50-EV 33
Linear deceleration (m/s2) with ramp set 2.
S.245 Jerk dec end 2 (linked to F.258) 1.00 0.01 10.00
Jerk (m/s3) applied at the beginning of a deceleration with ramp set 2.
S.250 Cont close delay (linked to A.080) 0.20 0.00 10.00
Delay time (s) for safe closing or the run contactor.
S.251 Magnet time (linked to A.081) 1.00 0.00 10.00
Duration (s) of the initial magnetization of the motor with DC injection.
S.252 Brake open delay (linked to A.082) 0.20 0.00 10.00
Delay time (s) between the open command and effective opening of the mechanical brake.
S.253 Smooth start dly (linked to A.083) 0.00 0.00 10.00
Duration (s) of the smooth start phase.
S.254 DCBrake stp time (linked to A.084) 1.00 0.00 10.00
Duration (s) of the stopping phase, after the speed has fallen below the zero threshold (dened by parameter P.440). During
this phase, the inverter can either output a DC current, or maintain a low frequency, in order to compensate for the slip
(default), as programmed by S.260.
S.255 Brake close dly (linked to A.085) 0.20 0.00 10.00
Delay time (s) between the close command and the effective engagement of the mechanical brake.
S.256 Cont open delay (linked to A.086) 0.20 0.00 10.00
Delay time (s) between the open command and the affective opening of the run contactor.
S.260 Lift stop mode (linked to A.220) [1] Normal stop
After the car speed falls below the zero threshold (dened by P.440), the inverter can be programmed to brake with DC
injection (S.260 = 0), or to maintain a low frequency output in order to compensate for the estimated slip (S.260 = 1). The
latter is set by default.
Possible selections: [0] DC brake at stop
[1] Normal stop
S.300 Manual boost [%] (linked to P.120) 3.0 0.0 25.0
Voltage boost (% of motor rated voltage) applied at low frequency in order to maintain the machine ux.
S.301 Auto boost en (linked to P.122) [0] Disable
The automatic boost allows for precise compensation of the resistive voltage drop due to the winding resistance, keeping the
ux at its rated value regardless of the load level and output frequency. For correct operation of this function, a precise value
of the equivalent stator resistance is needed.
Possible selections: [0] Disable
[1] Enable
S.310 Slip compensat (linked to P.100) 50 0 250
Amount of slip compensation (% of rated slip, calculated from nameplates) during motoring (power ows from motor to load).
S.311 Slip comp regen (linked to P.102) 50 0 250
Amount of slip compensation (% of rated slip, calculated from nameplates) during regeneration (power ows back from load
to motor).
S.312 Slip comp lter (linked to P.101) 0.3 0.0 10.0
Time constant (s) of the lter used for slip compensation. The lower this value, the faster the compensation, with improved
speed control. Excessively fast slip compensation may cause unwanted oscillations.
S.320 DC braking level (linked to P.300) 75 0 100
Amount of current (% of drive rated current) injected during magnetization and stopping phases.
S.400 Control mode (linked to P.010) [0] V/f OpenLoop
Set this parameter to “[0] Open loop V/f” when there is no encoder feedback available.
Set to “[1] Closed loop V/f” otherwise.
Possible selections: [0] V/f OpenLoop
[1] V/f ClsdLoop
34 AGL50-EV
S.401 Encoder ppr (linked to I.501) 1024 1 9999
Resolution of the encoder in use, expressed in number of pulses per mechanical revolution (ppr). It is a nameplate data of
the encoder.
S.450 Spd ctrl P-gainH (linked to P.172) 2.0 0.0 100.0
Proportional gain of speed PI regulator.
S.451 Spd ctrl I-gainH (linked to P.173) 1.0 0.0 100.0
Integral gain of speed PI regulator.
S.452 Spd PI High lim (linked to P.176) 10.0 0.0 100.0
Maximum allowed output of the speed PI regulator (% of maximum frequency, F.020). It represents the maximum amount of
slip that is allowed during motoring operation.
S.453 Spd PI Low lim (linked to P.177) -10.0 -100.0 0.0
Minimum allowed output of the speed PI regulator (% of maximum frequency, F.020). It represents the maximum amount of
slip (negative) that is allowed during braking operation.
Note!
S.901 Save parameters (linked to C.000)
It is possible to congure gain scheduling for the speed PI regulator.
The execution of this command will save all the parameters into the permanent memory of the drive. All unsaved settings will
be lost if the power is cycled.
AGL50-EV 35
7.5 Menù Display
d.000 Output frequency Drive output frequencyHz 0.01 001
d.001 Frequency ref Drive frequency referenceHz 0.01 002
d.002 Output current Drive output current (rms)A 0.1 003
d.003 Output voltage Drive output voltage (rms)V 1 004
d.004 DC link voltage DC Bus drive voltage (DC)V 1 005
d.052 Motor OL Motor overload (100% = alarm threshold)% 0.1 012
d.053 Brake res OL Braking resistor overload (100%=alarm thr)% 0.1 013
d.100 Dig inp status Digital inputs status acquired by the drive (terminal or virtual) 014
d.101 Term inp status Digital inputs terminal status of the drive regulat. Board 015
d.102 Vir dig inp stat Virtual digital inputs status from drive serial link 016
d.120 Exp dig inp stat Expansion digital inputs status (optional terminal or virtual) 017
d.121 Exp term inp Expansion digital inputs terminal status of the drive expansion board 018
d.122 Vir exp dig inp Expansion virtual digital inputs status from drive serial link 019
d.150 Dig out status Digital outputs status on the terminals of the drive regulation board 020
(commanded by DO functions or virtual DO)
d.151 Drv dig out sta Digital outputs status, commanded by DO functions 021
d.152 Vir dig out sta Virtual digital outputs status, commanded via serial link 022
d.170 Exp dig out sta Expansion digital outputs status on the terminals of the drive regulation board 023
(commanded by DO functions or virtual DO)
d.171 Exp DrvDigOutSta Expansion digital outputs status, commanded by DO functions 024
d.172 Exp VirDigOutSta Expansion virtual digital outputs status 025
(commanded via serial link)
d.200 An in 1 cnf mon Analog input 1 destination; 026
it shows the function associated to this analog input
[0] Null funct
[1] Rif freq 1
[2] Rif freq 2
[3] Fatt liv Bst
[4] Fatt liv OT
[5] FattLiv Vred
[6] Fatt liv DCB
[7] FattEst Ramp
[8] FattRif freq
[9] VelPI LimFac
[10] MltFrq ch 1
[11] MltFrq ch 2
d.201 An in 1 monitor Analog input 1 output block % value 027
d.202 An in 1 term mon Analog input 1 input block % value 028
d.210 Reserved 029
d.211 Reserved 030
d.212 Reserved 031
36 AGL50-EV
d.220 Reserved 032
d.221 Reserved 033
d.222 Reserved 034
d.250 LCW To PLC (0-7) Monitor of the control bits sent to the internal sequencer. Bit 0 to 7 66
d.251 LCW To PLC(8-15) Monitor of the control bits sent to the internal sequencer. Bit 8 to 1567
d.252 LCW Fr PLC (0-7) Monitor of the control bits generated by the internal sequencer. Bit 0 to 7 68
d.253 LCW Fr PLC(8-15) Monitor of the control bits generated by the internal sequencer. Bit 8 to 1569
d.254 LCW FrPLC(16-23) Monitor of the control bits generated by the internal sequencer. Bit 16 to 2370
d.255 LSW (0-7) Monitor of the drive status. Bit 0 to 7. 71
d.300 EncPulses/Sample Number of encoder pulses, 1/100 035
recorded in the time interval dened by parameter I.504.
d.301 Encoder freq Encoder frequency reading (Motor frequency)Hz 0.01 036
The timer function allows to apply delays and pulses to an input signal selected from a pick list.
Menu A - APPLICATION
Cod. Display (Description) Def. Min. Max
A.320 Timer 1 mode 0 0 5
Select working mode of Timer 1
[0] Disable
[1] On delay
[2] Off delay
[3] On/Off delay
[4] Pulse
[5] Sym asher
[0] Disable Output is always 0ff
Timer 1in
Timer 1 out
Tt<T
Timer 1in
Timer 1 out
TT
T
[1] On delay The closure of the Input (On) is transferred on Output after pre-set time has elapsed.
[2] Off delay The closure of the Input (On) is transferred immediately on the Output.
The opening of the Input (Off) initiates the pre-set delay, after which the Output is reset (Off).
38 AGL50-EV
Timer1in
On/Off delay
T=Timer1delay
Pulse
T=Timer1delay
T=Timer 1 delay
T
T
Timer 1in
Timer1out
TT
T
T
Timer 1 out
Tt<T
[3] On/Off delay The closure of the Input (On) is transferred on Output after pre-set time has elapsed.
The opening of the Input (Off) initiates the pre-set delay, after which the Output is reset (Off).
[4] Pulse The closure of the Input (On) is transferred immediately on the Output.
After pre-set time has elapsed, the Output reset (Off).
Symmetrical flasher
Timer 1in
Timer 1 out
TTTTTTt<T
[5] Sym asher The closure of the Input (On) is transferred immediately on the Output.
The Output cycle between On and Off for as long as Input is close (On).
The ratio is 1:1 (time On = time Off)
A.321 Timer 1 set src 0 0 27
Select input signal of Timer 1. See list of I.000
A.322 Timer 1 delay 3.00 0.00 30.00
Set delay of Timer 1. See list of I.000
Example of Timer 1 use:
The default conguration of I.100 “Dig output 1 cfg” is [51] “Contactor”.
For the needs of external sequences is necessary to delay of 3 sec the rising edge.
You can get this behaviour with the Timer 1.
The drive keypad will show a blinking message with code and name of the alarm occurred.
The gure below shows an example of OV Overvoltage alarm condition.
Figure 8.1.1: Alarm Displaying
The active alarm can be acknowledged by pressing the Prg button on the keypad.
This operation will allow menu navigation and parameter editing while the drive is in alarm state (red LEDs blinking).
In order to resume drive operation, an Alarm reset command is necessary.
8.2 Alarm Reset
Alarm reset can be performed in three different ways:
- Alarm reset by keypad: pressing simultaneously Up and Down keys; the reset
action will take effect when the buttons are released.
- Alarm reset by digital input:it can be performed through a programmable digital
input connected to command I.010 Fault reset src =
[6] Digital input 5.
. Alarm reset by Autoreset function:it allows an automatic reset of some drive alarms (see
table 8.3.1), by the settings of P.380, P.381, P.382 and P.383 parameters.
The gure below shows how to reset an alarm by keypad.
Figure 8.2.1: Alarm Reset
40 AGL50-EV
8.3 List of drive alarm events
Table 8.3.1 provides a description of the causes for all the possible alarms.
Table 8.3.1 Alarm event list
ALARM
DESCRIPTION
Cod.Name
EFEF Ext Fault It trips when External fault input is active1YES0
OCOC OverCurrent It trips when an Overcurrent value is detected by output current sensor2YES1
serial
code from
Numerical
Autoreset
H.063
Bit H.062
OUOV OverVoltage
UUUV UnderVoltage
OHOH OverTemperat
OLiOLi Drive OL It trips when the drive overload accumulator exceeded the trip threshold6NO5
OLMOLM Motor OL It trips when the motor overload accumulator exceeded the trip threshold7NO6
OLrOLr Brake res OL
OtOt Inst OverTrq
PHPH Phase loss
FUFU Fuse Blown It trips when the drive input fuses are blown11NO10
OCHOCH Desat Alarm IGBT desaturation or instantaneous overcurrent have been detected12YES11
StSt Serial TO It trips when the serial link time out exceeds the programmed level (I.604 parameter)13YES12
OP1Reserved14NO13
OP2
It trips when the drive DC Bus voltage is higher than the maximun threshold for the
given main voltage setting
It trips when the drive DC Bus voltage is lower than the maximun threshold for the
given main voltage setting
It trips when the drive heatsink temperature detected by the switch sensor exceeds its
threshold (*)
Its intervention occurs when the overload cycle of the external braking resistance
does not correspond to the dened limits.
It trips when the torque delivered by the motor exceeds the programmed level for the
preset time
It trips when the supply phase lack: enabled 30 seconds after one of the supply
phases has been disconnected
Reserved
3YES2
4YES3
5NO4
8NO7
9NO8
10NO9
15NO14
bFbF Bus Fault Drive comunication Bus failure16NO15
OHSOHS OverTemperatIt trips when the drive heatsink temperature exceeds a safety level. (*)17NO16
SHCSHC Short CircShort Circuit between output phases or Ground fault18NO17
OhrRiservato1918
LfLF Limiter fault
PLCPLC Plc fault
EMSKey Em Stp faultReserved22NO21
UHSUHS Under Temperat
PHOPhase Loss Output
It trips when the output current limiter or the DC-Link voltage limiter fail. The failure
can be caused by wrong settings of regulator gains or by the motor load.
"PLC program not active. Lift application does not function.
Run C.050 parameter to reset the alarm."
It trips when the temperature of the drive heatsink is below a safety level (typically
–10°C).
See gure 7.2: it trips during the phase (2) if the current does not exceed the limit
dened
20NO19
21NO20
23NO22
25NO24
*) OH switch sensor threshold and OHS analog sensor threshold depend on the drive size (75 °C ... 85 °C)
AGL50-EV 41
9 - Parameter list
Figure 9.1: Parameters Description Legend
Code
(A)
Name
(B)
PARAMETERPICK LIST
DESCRIPTIONSelection
(C)
Description
Def.
(D)
Min
(E)
Max
(F)
Unit
(G)
Variat.
(H)
IPA
(I)
START-UP
S.000 Mains voltageRated value of the line voltage230400230480V
380
400
420
440
460
480
S.001 Mains frequencyRated value of the line frequency50505060Hz
60
404
(P.020)
405
(P.021)
(A) CODE: Parameter Code, showed on display.
Format=X.YYY:
Stopped motor: possibility to write all parameters.
Running motor: some
parameters are writing
protected (IPA in bold)
All parameters are writing protected excepted:
- F000, F100..F116,
multispeed function
parameters
- P999 Param prot code
- C000 Save parameter
(*)
- C020 Alarm clear
- H500..H511, serial line
commands.
All parameters are writing protected excepted:
- P999 Param prot code
- C000 Save parameter
(*)
- C020 Alarm clear
- H500..H511, serial line
commands.
Stopped motor: possibility to write all parameters.
Running motor: some
parameters are writing
protected (IPA in bold)
Possibility to execute
Save parameter also
with running motor.
A.084 DCBrake stp timeDuration of 0Hz braking at stop1010s0.011320
A.085 Brake close dlyBrake contactor close delay0.20010s0.011321
A.086 Cont open delayRUN contactor open delay0.20010s0.011322
A.087 Current pres thr
A.088 Sel match code
A.090 Car max speed
A.091 Ramp factor 1
A.092 Ramp factor 2
A.220 Lift stop modeLift behavior at stop[0] Dcb at stopDC brake is perfor-
A.221 Lift start seq
NameDESCRIPTIONSelectionDescription
(fw 03-07)
PARAMETERPICK LIST
[1] Analog inp 1Analog input 1
[2] Analog inp 2Analog input 2
[3] Analog inp 3Analog input 3
[4] Encoder freqEncoder frequency
[5] Output currOutput peak current
[6] Output torqueOutput torque
[7] Output powerOutput power
[1] Steady state
[1] Enable
[1] Enable
[1] Enable
Current threshold for inverter output
phases check
Code to be compared to the status of Freq
selectors
Speed of the lift car when the inverter
output frequency is equal to P.062
multiplier for acc/dec and jerks of ramp
sets 1 and 3
multiplier for acc/dec and jerks of ramp
sets 2 and 4
med after the output
frequency is below P.440
threshold
[1] Normal stopDC brake is not perfor-
med at stop
Select working mode of Lift start sequence [0] NormalYou can activate the start
sequence with the Run
Fwd command or Run
Rev command
Def.MinMaxUnitVariat.IPA
100100%11325
00151326
0.500.015.00m/s0.011323
1.000.012.500.011324
1.000.012.500.011327
1011350
0011351
AGL50-EV 59
Code
A.300 AND1 In 1 srcSource of In 1 of logic block AND1see list of I.00000271355
A.301 AND1 In 2 srcSource of In 2 of logic block AND1see list of I.00000271356
A.302 AND2 In 1 srcSource of In 1 of logic block AND2see list of I.00000271357
A.303 AND2 In 2 srcSource of In 2 of logic block AND2see list of I.00000271358
A.304 AND3 In 1 srcSource of In 1 of logic block AND3see list of I.00000271359
A.305 AND3 In 2 srcSource of In 2 of logic block AND3see list of I.00000271360
A.306 OR1 In 1 srcSource of In 1 of logic block OR1see list of I.00000271361
A.307 OR1 In 2 srcSource of In 2 of logic block OR1see list of I.00000271362
A.308 OR2 In 1 srcSource of In 1 of logic block OR2see list of I.00000271363
A.309 OR2 In 2 srcSource of In 2 of logic block OR2see list of I.00000271364
A.310 OR3 In 1 srcSource of In 1 of logic block OR3see list of I.00000271365
A.311 OR3 In 2 srcSource of In 2 of logic block OR3see list of I.00000271366
A.312 NOT1 In srcSource of Input of logic block NOT1see list of I.00000271367
A.313 NOT2 In srcSource of Input of logic block NOT2see list of I.00000271368
A.314 NOT3 In srcSource of Input of logic block NOT3see list of I.00000271369
A.315 NOT4 In srcSource of Input of logic block NOT4see list of I.00000271370
A.320 Timer 1 modeSelect working mode of Timer 1[0] Disable
A.321 Timer 1 set srcSelect input signal of Timer 1See list of I.00000271376
A.322 Timer 1 delaySet delay of Timer 1See list of I.0003.000.0030.00sec0.011377
NameDESCRIPTIONSelectionDescription
PARAMETERPICK LIST
[1] Mltspeed !=0You can activate the
start sequence with
multispeed selection.
The Multispeed value different from zero causes
the start of sequence.
The Run Fwd command
or Run Rev command
must be present.
[1] On delay
[2] Off delay
[3] On/Off delay
[4] Pulse
[5] Sym asher
Def.MinMaxUnitVariat.IPA
0051375
COMMAND
C.000 Save parametersSave parameters command offNo action.offoffdo800
do
C.001 Recall paramRecall last set of saved parameters offNo action. off offdo801
do
C.002 Load defaultRecall of the factory parameters. offNo action. off offdo802
doLoad default parameters.
C.020 Alarm clearReset of the the Alarm List register offNo action. off offdo803
do
C.040 Reserved
C.041 Reserved
C.050 Rst MdplcPrecRun Reset mdplc error at previous run offNo action. off offdo809
doReset mdplc error
C.060 Calculate spaceOff line space evaluation offNo action. off offdo809
doStart
C.070 Reserved
C.071 Reserved
C.100 Measure stator RMotor Autotune command offNo action. off offdo806
doAutotune command.
Save parameters
command.
Recall last set of saved
parameters.
Clear alarm register
command.
60 AGL50-EV
Code
NameDESCRIPTIONSelectionDescription
PARAMETERPICK LIST
Def.MinMaxUnitVariat.IPA
HIDDEN
This menu is not available on the keypad. The setting and the reading of the parameters here contained, can be performed exclusively via serial line or through SBI card.
H.000Virtual digital command002551000
H.001Exp virtual digital command002551001
H.010Virtual digital state002551002
H.011Exp Virtual digital state002551003
H.020Virtual An Output 10-32768327671004
H.021Virtual An Output 20-32768327671005
H.022Exp Virtual An Output 10-32768327671006
H.030
H.031
H.032
H.033
H.034Drive status00655351042
H.040Progress001001009
H.050
H.051
H.052
H.053
H.054
H.055
H.056
H.057
Drive output frequency at 32bit (LSW)
(d.000)
Drive output frequency at 32bit (MSW)
(d.000)
Drive reference frequency at 32bit (LSW)
(d.001)
Drive reference frequency at 32bit (MSW)
(d.001)
Output speed (d.000)*(P.600) at 32bit
(LSW) (d.007)
Output speed (d.000)*(P600)at 32bit
(MSW) (d.007)
Speed Ref (d.001)*(P.600) at 32bit (LSW)
(d.008)
Speed Ref (d.001)*(P.600) at 32bit (MSW)
(d.008)
H.058Encoder freq at 32bit (LSW) (d.301)0- 2
H.059Encoder freq at 32bit (MSW) (d.301)0- 2
H.060
H.061
Encoder speed (d.000)*(P.600) at 32bit
(LSW) (d.302)
Encoder speed (d.000)*(P.600) at 32bit
(MSW) (d.302)