gefran 1600, 1800 Installation And Operation Manual

CE MARKING: EMC conformity (electromagnetic compatibility) with EEC Directive
89/336/CEE with reference to the generic Standard EN61000-6-2 (immunity in industrial environments) and EN50081-1 (emission in residential environments). BT (low voltage) conformity respecting the Directive 73/23/CEE modified by the Directive 93/68. Limitations: model 1800 conforms to Standard EN55011 for emissions radiated in industrial environment. MAINTENANCE: Repairs must be done only by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case. SERVICE: GEFRAN has a service department. The warranty excludes defects caused by any use not conforming to these instructions.
1600 / 1800
CONTROLLER
SOFTWARE VERSION 3.2x code 80080D / Edition 13 - 03/08
INSTALLATION AND OPERATION MANUAL
RTD type (scale configurable within indicated range, with or without decimal point)
PTC type (on request)
DIN 43760 (Pt100, JPT100) 990, 25°C
Max line resistance for RTD 20 Safety
detection of short-circuit or opening of probes, LBA alarm, HB alarm
°C / °F selection configurable from faceplate
Linear scale ranges
-1999 to 9999 with configurable decimal point position
Thermocouples IEC 584-1 (J, K, R, S, T, B, E, N, Ni-Ni18Mo, L NiCr-CuNi) Cold junction error 0,1° / °C
Controls PID, Self-tuning, on-off pb / dt / di 0.0 ... 999.9% / 0.00 ... 99.99min / 0.00 ... 99.99min Action Heat / Cool Control outputs on / off, pwm, Open / Close Cycle time 0.1 ... 200 sec Main output type Relay, Logic, Continuous (optional) Softstart 0.0 ... 500.0 min Maximum power limit heat / cool
0.0 ... 100.0 %
Fault power setting -100.0 ... 100.0 % Automatic blanking
Optional exclusion, displays PV value
Configurable alarms
3 configurable alarms type: max, min, symmetrical, absolute or relative, LBA, HB
Alarm masking
- exclusion during warm up
- latching reset from faceplate or external contact
Type of relay contact
NO (NC), 5A, 250V, cosϕ = 1
Faceplate protection
IP65
Working / Storage temperature range 0...50°C / -20...70°C Relative humidity
20 ... 85% non-condensing
Installation Panel, plug-in from front Weight 400g (1600V), 600g (1800V) for the complete version
Main input
TC, RTD (Pt100 - JPT100), PTC, 50mV, Ri 1M; 10V, Ri 10K; 20mA, Ri = 50
CT scale range configurable from 0, ... , 100.0A Transmitter power supply
(optional)
filtered 10 / 24Vdc, max 30mA short-circuit protection, isolation 1500V
Analogue retransmission signal (opt) 10V / 20mA, isolation 1500V Logic inputs (optional)
24V NPN, 4.5mA; 24V PNP, 3.6mA isolation 1500V
Serial interface (optional) CL; RS422/485; RS232; isolation 1500V Baud rate
1200 ... 19200
Protocol GEFRAN / MODBUS
Logic output for static relays 11Vdc, Rout = 220(6V/20mA) (option) remote Setpoint
or Amperometric input Feedback input Potentiometer valve position
0 ... 10V, 2 ... 10V, Ri 1M 0 ... 20mA, 4 ... 20mA, Ri = 5 Potentiometer > 500Ω, TA 50mAac, 50/60Hz, Ri = 1,5Ω, isolation 1500V
Power supply (switching type)
(std) 100 ... 240Vac/dc ±10%; 50/60Hz, 12VA max (opt.) 20...27Vac/dc ±10%; 50/60Hz, 12VA max
Display
2 x 4 digits, green, height: 10 and 7 mm (1600V); 20 and 13 mm (1800V)
Keys
5 mechanical keys (,Man/Aut, INC, DEC, F)
Accuracy 0.2% full scale at 25°C room temperature
1 • INSTALLATION
Dimensions and cut-out; panel mounting
2 TECHNICAL SPECIFICATIONS
FUNCTION CABLE TYPE LENGTH
Power supply cable 1 mm
2
1 m
Relay output cable 1 mm
2
3,5 m
Digital communication wires 0,35 mm
2
3,5 m
C.T. connection cable 1,5 mm
2
3,5 m TC input 0,8 mm2compensated 5 m Pt100 input 1 mm
2
3 m
EMC conformity has been tested with the following connections
96
115
108
96
113
10
92
92
115
48
70
115
44,5
92
113
10
108
96
For correct and safe installation, follow the instructions and observe the warnings contained in this manual.
Panel mounting:
To fix the unit, insert the brackets provided into the seats on either side of the case. To mount two or more units side by side, respect the cut-out dimensions shown in the drawing. To obtain IP65 faceplate protection level, remove the device from the box, apply the gasket (supplied) with adhesive to the front edge of the box, and then reinsert the device.
!
Environmental conditions of use for internal use only, altitude up to 2000m
1
80080D_MHW_1600-1800_0308_ENG
1
2
3
4
5
6
7
8
9
10
11
24
25
26
27
28
29
30
31
32
33
22
21
20
19
18
17
16
15
14
13
12
Configurable serial
line isolated to 1500V RS422/485 or RS232
Passive current loop
(max. 1200 baud)
(optional
R60 special)
Serial line
27 26 25 24
-
+
-
+
Tx
Rx
A (Data +)
B (Data -)
RS485 2-wires
GND
RS232
Tx
Rx
Linear (V)
3 DESCRIPTION OF FACEPLATE
User configurable
generic output
- 5A/250Vac relay, cosϕ=1
- 11Vdc logic, Rout=220(6V/20mA)
Standard:
100...240Vac/Vdc ±10% Optional:
20...27Vac/Vdc ±10% 50/60Hz
Digital inputs isolated
1500V
- NPN 24V, 4,5mA
- PNP 24V, 3,6mA (12V, 1,2mA)
Digital inputs
4 CONNECTIONS
Outputs
+
-
User configurable generic
output
- 5A/250Vac relay, cos
ϕ=1
- 11Vdc logic, Rout=220 (6V/20mA)
Available thermocouples:
J, K, R, S, T, B, E, N,
Ni-Ni18Mo, L NiCr-CuNi
- Observe polarities
- For extensions, use the correct compensating cable for the type of TC used
Inputs
TC
2
1
Linear input in dc voltage
0...50mV, 10...50mV,
0...10V, 2...10V
2
1
+
-
8
5
7
14
16
15
17
Out3 (AL1)
IN1
IN2
COM
Power Supply
12
13
~
~
Auxiliary input isolated
1500V
Current transformer
50mAac; 1,5; 50/60Hz
Remote setpoint
0...20mA, 4...20mA, 5Ω,
0...1V, 0...10V,> 1M
Potentiometer > 500
Auxiliary input
6
5
~
~
Outputs
User configurable
generic output
- analogue output isolated to 1500V (0 ... 10V, 0 ... 20mA, 4 ... 20mA)
11
10
+
-
Out4
(AL2 / HB)
33
31
0V
+W2
Transmitter supply isolated
1500V
10/24Vdc, max. 30mA short-circuit protection
9
5
+
-
18
20
19
21 22
Out2 (Close) Out1 (Open)
C
32
+W1
Transmitter supply
GND
+ Vt
1800 1600
(-) NC
(-) NC
(-) NC
(+) NO
(+) NO
(+) NO
C
C
!
PWR
Pt100 2 wires o PTC
Use wires of adequate
diameter (min. 1mm
2
)
PT100, JPT100, PTC
Pt100 3 wires
3
1
2
3
1
2
TT
Linear input in dc
current
0...20mA, 4...20mA
Linear (I)
4
1
2
-
+
9
Pot
+10V+Vt
GND
PV Display: Indication of process variable
Error Indication: LO, HI, Sbr, Err
LO= the value of process variable is < di LO_S
HI= the value of process variable is > di HI_S
Sbr= faulty sensor or input values higher than max.
limits
Err= PT100 third wire opened for PT100, PTC or
input values lower than min. limits
(i.e.: TC wrong connection)
Automatic/Manual adjustment selection
Active only when PV display visualises the process
variable
Function key
Gives access to the various configuration phases •• Confirms change of set parameters and browses next or previous parameter (if Auto/Man key is pressed)
Function indicators
Indicates modes of operation MAN = OFF (Automatic control) MAN = ON (Manual control) AUX = OFF (IN1 = OFF - local Setpoint 1) AUX = ON (IN1 = ON - local Setpoint 2) REM = OFF (local Setpoint) REM = ON (remote Setpoint)
SV display: Indication of setpoint
Indication of output states
OUT 1 (Open); OUT 2 (Close);
OUT 3 (AL 1); OUT 4 (HB)
Raise and Lower key
Press to increment (decrement) any numerical parameter •• Increment (decrement) speed is proportional to time key stays pressed •• The operation is not cyclic: once the maximum (minimum) value of a field is reached, the value will not change even if the key remains pressed.
2
80080D_MHW_1600-1800_0308_ENG
sp.i
ts
inp.2
al.1
al.2
al.3
al.xb
0vt.p
212
5 PROGRAMMING and CONFIGURATION
F
If Inc, Dec, F keys are not pressed within 30 sec, display returns automatically to PV/SV value. All INFO and dAtA data on config menu remain displayed and are not timed.
INFO
P.V. / S.V.
Process variable (PV display) Work Setpoint (SV display) or control output value with regulator in manual
Amperometric input value
or remote Setpoint
(with auxiliary input enabled)
Alarm point 1 (scale points)
Alarm point 2 (scale points)
Alarm point 3 (scale points)
Heater break alarm point
(scale points of ammeter input)
Control output value
(+Heat / -Cool)
Press for
approx.
2 sec
Control parameters
dAtA
CFG
SEr
InP
Out
PASS = 99
Prot
Lin
CuSt
Serial communications
Input settings
Output settings
Hardware configuration
Input linearization
dAtA menu setting
_CAL
Select calibration menu [ 0...12 ]
YES
NO
Keep the F key
pressed to scroll
the menus
Release the F key
to select the
displayed menu
Press the F key to
access the
parameters
Keep the F key
pressed to exit any
menu
Keep F + Auto/Man
keys pressed for 2
sec. on any menu to go immediately
to level 1 display
(*)
(*)
S3 = ON
Local Setpoint
LEVEL 1 MENU
PASS
NO
YES
Hrd
U.CAL
S4 = ON
YES
NO
Custom menu
Password
User calibration
Protection code
(*) The automatic return PV/SV display is disabled for these displays
1
2
3
4
5
6
7
Information display
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Limit value of timer
0...9999 sec
N.B.: Once a particular configuration is entered, all unnecessary parameters are no longer displayed
213
214
215
217
Device structure: identification of boards
SP
-
-
­sp.2
­sp.3
­sp.4
-
-
-
-
-
-
DISPLAY
BOARD
POWER BOARD
CPU BOARD
SERIAL / W BOARD
DISPLAY BOARD
POWER BOARD
CPU
BOARD
SERIAL / W BOARD
3
80080D_MHW_1600-1800_0308_ENG
rst
p.rst
a.rst
ffd
soft
xys.i
xys.2
xys.3
xb t
lba.t
lba.p
Fa(.p
gr.sp
s.tvn
h pb
hit
h dt
h.p.xi
h.p.lo
(.med
c.sp.o
c pb
cit
c dt
c.p.xi
c.p.lo
(ODE
updt
er.nr
prot
InFo Display
CFG
Enabling self-
tuning,
autotuning,
softstart
CFG
Control parameters
Proportional band for
heating or hysteresis on
ON-OFF action
Integral time
for heating
Derivative time
for heating
Maximum power limit
for heating
Setpoint for cooling
relative to heating
setpoint
Proportional band for
cooling or hysteresis for
ON/OFF control
Integral time for cooling
Derivative time
for cooling
Maximum power limit
for cooling
Manual reset
Alarm 2 hysteresis
Alarm 3 hysteresis
Waiting time for HB alarm
intervention
Waiting time for LBA alarm intervention
(Set to “0” to disable LBA alarm)
Power limit for LBA
alarm condition
Power output in fault condition
(when probe is faulty)
(*)
(*)
15
16
17
18
19
20
21
22
23
24
25
31
33
34
35
36
S.tun Continuous Self-tuning Softstart
autotuning 0NONONO 1 YES NO NO 2 NO YES NO 3 YES YES NO 4NONOYES 5 YES NO YES 6--­7--­8 WAIT NO NO 9GO NO NO
10 WAIT YES NO 11 GO YES NO 12 WAIT NO YES 13 GO NO YES
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
-999 999 scale points
0.0 999.9% full scale
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
± 25.0% f.s.
0.0 999.9% full scale
± 999
scale points
± 999
scale points
0 ... 999 seconds
0.0 ... 500.0 min
-100.0 ... 100.0% ON / OFF
-100.0 ... 100.0% ON / OFF
Set gradient
(see applicable note)
0.0...999.9 digit/min.
(digit / sec see SP.ty)
Antireset
Feedforward
27
28
0 ... 9999
scale points
-100.0 ... 100.0%
Reset power
26
-100.0 ... 100.0%
(*)LBA alarm may be reset by simultaneously pressing + keys when OutP is displayed or by
switching to Manual.
216
INFO
Serial
communication
code
Software
version
Software
protection code
Self
diagnostic
error code
8
9
10
11
12
Information
display
0 No Error 1Lo 2Hi 3 ERR 4 SBR
Alarm 1 hysteresis
30
± 999
scale points
Softstart time
29
0.0 ... 500.0 min
(Value has to be higher than cycle time value of output to which HB alarm is assigned)
Minimum power limit for
heating (not available for
double heat/cool action)
254
0.0 ... 100.0%
Cooling medium
97
0 ... 2
Minimum power limit for
cooling (not available for
heating/cooling double
action)
255
0.0 ... 100.0%
C.MEd Relative gain (Rg)
(see applicable note) 0 Air 1 1 Oil 0,8 2 Water 0,4
Note:
h_Pb, h_it, h_dt, h.P.Hi, hPLo, c_Pb, c_it, c_dt, c.P.Hi, c.P.Lo parameters are read only if the optioncontrol parameter groups has been selected (showing current values)
c_Pb, c_it, c_dt parameters are read only if the option relative gain heat/cool control (Ctrl = 14) has been selected.
-
-
-
-
-
-
-
-
-
-
4
80080D_MHW_1600-1800_0308_ENG
(ode
ser.p
bavd
sp.ty
type
Ser
Ser
Unit identification code for serial
communication (if enabled)
[see hrd.1 in Hrd]
Serial communications
Serial interface
protocol CENCAL,
MODBUS
Select Baudrate
38
39
40
0 ... 9999
SEr.P Serial protocol
0 CENCAL GEFRAN 1 MODBUS RTU
bAud Baudrate CENCAL Interface MODBUS Interface
0 1200 485 / 232 485 1 2400 485 / 232 485 2 4800 485 / 232 485 3 9600 485 / 232 485 4 19200 485 / 232 485
Parity selection
101
PAr Parity
0 No parity 1 Odd 2 Even
Setpoint type: LOC/REM,
Select type of remote
setpoint
[0...7]
Probe type, signal, enable custom linearization,
and main input scale
tYPE Probe type Scale Scale range max. Scale range max.
(C/F) without decimal point with decimal point 0 J (Fe-CuNi) C 0 / 1000 0.0 / 999.9 1 J (Fe-CuNi) F 32 / 1832 32.0 / 999.9 2 K (NiCr-Ni) C 0 / 1300 0.0 / 999.9 3 K (NiCr-Ni) F 32 / 2372 32.0 / 999.9 4 R (Pt13Rh - Pt) C 0 / 1750 not available 5 R (Pt13Rh - Pt) F 32 / 3182 not available 6 S (Pt10Rh - Pt) C 0 / 1750 not available 7 S (Pt10Rh - Pt) F 32 / 3182 not available 8 T (Cu-CuNi) C -200 / 400 -199.9 / 400.0 9 T (Cu-CuNi) F -328 / 752 -199.9 / 752.0 10 B (Pt30Rh - Pt6Rh) C 44 / 1800 not available 11 B (Pt30Rh - Pt6Rh) F 111 / 3272 not available 12 E (NiCr-CuNi) C -100 / 750 -100.0 / 750.0 13 E (NiCr-CuNi) F -148 / 1382 -148.0 / 999.9 14 N (NiCrSi-NiSi) C 0 / 1300 0.0 / 999.9 15 N (NiCrSi-NiSi) F 32 / 2372 32.0 / 999.9 16 (Ni - Ni18Mo) C 0 / 1100 0.0 / 999.9 17 (Ni - Ni18Mo) F 32 / 2012 32.0 / 999.9 18 L - GOST (NiCr-CuNi) C 0 / 600 0.0 / 600.0 19 L - GOST (NiCr-CuNi) F 32 / 1112 32.0 / 999.9 20 TC C custom scale (*) 21 TC F custom scale (*)
tYPE Probe type Scale Scale range max. Scale range max.
(C/F) without decimal point with decimal point 0 PT100 C -200 / 850 -199.9 / 850.0 1 PT100 F -328 / 1562 -199.9 / 999.9 2 JPT100 (JIS C 1609/81) C -200 / 600 -199.9 / 600.0 3 JPT100 (JIS C 1609/81) F -328 / 1112 -199.9 / 999.9 4 RTD C custom scale (*) 5 RTD F custom scale (*)
(*) Linearization and scale limit settings (with or without decimal point) are selectable from PC via serial line
PROBE: RTD 3 wires (SEnS=1)
PROBE: PTC (SEnS=2) on request, instead of RTD 3 wires
InP
InP
Input settings
44
45
SP.tY Type of remote Absolute
setpoint Relative 0 analogue (InP.2) absolute 1 analogue (InP.2) relative to
local setpoint
2 digital absolute
(from serial line)
3 digital relative to
(from serial line) local setpoint
PROBE:TC (SEnS=0)
+4 set gradient in digit / sec
tYPE Probe type Scale Scale range max. Scale range max.
(C/F) without decimal point with decimal point 0 PTC 990 C -55 ... 120 -55.0 ... 120.0 1 PTC 990 F -67 ... 248 -67.0 ... 248.0 2 PTC 990 C custom scale (*) 3 PTC 990 F custom scale (*)
tYPE Signal type Scale Scale range max. 0 0...50mV linear -1999 / 9999 1 0...50mV custom linear see table 32 values in Lin 2 10...50mV linear -1999 / 9999 3 10...50mV custom linear see table 32 values in Lin
PROBE: VOLTAGE 50mV (SEnS=3)
tYPE Signal type Scale Scale range max. 0 0...20mA linear -1999 / 9999 1 0...20mA custom linear see table 32 values in Lin 2 4...20mA linear -1999 / 9999 3 4...20mA lineare custom see table 32 values in Lin
PROBE: CURRENT 20mA or TRANSMITTER (SEnS=4)
tYPE Signal type Scale Scale range max. 0 0...10V linear -1999 / 9999 1 0...10V custom linear see table 32 values in Lin 2 2...10V linear -1999 / 9999 3 2...10V custom linear see table 32 values in Lin
PROBE: VOLTAGE 10V or TRANSMITTER (SEnS=5)
tYPE Signal type Scale Scale range max. 0 Custom 0...10V linear -1999 / 9999
1 Custom 0...10V custom linear see table 32 values
in Lin
PROBE: CUSTOM 10V (SEnS=6)
tYPE Signal type Scale Scale range max. 0 Custom lineare -1999 / 9999 1 Custom custom linear see table 32 values
in Lin
PROBE: CUSTOM 50mV, 20mA (SEnS=7)
par
-
5
80080D_MHW_1600-1800_0308_ENG
xi l
lo l
of.52
xi.52
lo.52
flt.2
filt
fild
dp s
lo s
xi s
ofst
typ.2
Digital filter
on main input
Digital filter on display
process variable: acts as
hysteresis
Decimal point position for
main input scale, alarm
and remote setpoint
(*) not available for TC,
RTD and PTC scales
Minimum limit of main
input scale
Maximum limit of main
input scale
Offset correction
of main input
Digital filter on aux input
(if enabled)
[see hrd.1 on Hrd]
Aux analogue input function (if enabled) [see hrd.1 on Hrd]
and enable custom
limitation
Minimum range for aux
input (if enabled)
[see hrd.1 on Hrd]
Maximum range for aux
input (if enabled)
[see hrd.1 on Hrd]
Offset correction of aux
input (if enabled)
[see hrd.1 on Hrd]
Lower limit for local
setpoint and absolute
alarms
Upper limit for local
setpoint and absolute
alarms
+ 8 to select custom linearization (see table 32 values in Lin)
46
47
48
49
50
51
52
53
54
55
56
57
58
0.0 ... 20.0 sec
0 ... 9.9
scale points
dP_S Format
0 xxxx 1 xxx.x 2xx.xx (*) 3x.xxx (*)
min...max input range
selected in tyPE
min...max input range
selected in tyPE
-999 ... 999 scale points
tYP.2 Auxiliary input function
0 None 1 Remote setpoint 2 Analogue remote manual 3 Analogue power reset 4 Current transformer
input for HB
0.0 ... 20.0 sec
Minmax input range
selected in tyP.2
Minmax input range
selected in tyP.2
-999 ... 999 scale points
Lo.S ... Hi.S
Lo.S ... Hi.S
Out
61
Out
Output settings
Select reference signal for
alarm 1
AL.1.r, AL.2.r, AL.3.r
Select reference signal for
alarm 2
Select reference signal for
alarm 3
60
62
AL.x.r Variable to compare Alarm setpoint
0 PV (Process variable) AL 1 InP.2 (aux input) AL 2 SSP (active setpoint) AL (only absolute) 3 PV (Process variable) InP.2
(aux input)
+ 4 only for relative alarms, they refer to SP1 (available if multiset function enabled)
64
63
Alarm type 1
Alarm type 2
Alarm type 3
+ 8 to disable on power up until first interception + 16 to latch alarm
65
AL.x.t Direct (high limit) Absolute or Normal
Inverse (low limit) Relative Symmetrical
to active setpoint (window) 0 direct absolute normal 1 inverse absolute normal 2 direct relative normal 3 inverse relative normal 4 direct absolute
symmetrical
5 inverse absolute
symmetrical
6 direct relative
symmetrical
7 inverse relative
symmetrical
AL.1.t, AL.2.t, AL.3.t
HB alarm
function
66
Hb_F Function description
0 Relay, logic output: alarm active on
load current level lower than setpoint during the ON time of the control output
1 Relay, logic output: alarm active on
load current level higher than setpoint during the OFF time of the control output
2 Alarm active if one of functions 0 and 1 is
true (OR logic between 0 and 1) (*) 3 For continuous heating output 7 For continuous cooling output
+ 0 assigned to output Out1 (only for Hb_F= 0, 1, 2) + 4 assigned to output Out2 (only for Hb_F= 0, 1, 2) + 8 assigned to output Out3 (only for Hb_F= 0, 1, 2) + 12 assigned to output Out4 (only for Hb_F= 0, 1, 2) + 16 inverse HB alarm
(*) minimum setting is fixed at 12% of amperometric full scale