Gefran 1000, 1001, 1101 Data Sheet

1000 / 1001 / 1101
CONFIGURABLE CONTROLLERS
Main applications
• Plastics extrusion lines and injection moulding machines
• Polymerisation plant for synthetic fibre production
• Climatic chambers and test benches
• Chemical and pharmaceutical industries
• Food processing plant
• Packaging machinery
• Wood working machinery
• Polyurethane machinery
• Cooling systems
• Industrial ovens and furnaces
• Rubber moulding machinery
Main features
• Inputs for thermocouples and resistance thermometers completely configurable from the faceplate
• Offset function on the input signal
• Relay, mA or logic main output
• Between 1 and 3 configurable alarms
• Auxiliary input for C.T.
• Alarm for opencircuit load or shortcircuit probe
• PD alarm output configurable for cooling
• Self-tuning/Auto-tuning, Soft-start, bumpless Man/Auto transfer
• Serial line: optoisolated 4-wires
GENERAL
Microprocessor controller, 48x96 (1/8 DIN) format for model 1000 and 96x96 (1/4 DIN) format for models 1001 and 1101 manufactured using SMT. The 1000 family of controllers provide a complete operator interface, with a Lexan membrane faceplate to give IP54 frontal protection that has 3 keys, two green LED displays with 3 (1000) or 4 (1001 and 1101) digits, and red LED indicators for the 3 alarm relay outputs and a green LED for the main control output. The main input for the control variable is universal and provides the possibility of connecting different types of signal: ï Thermocouples of types J, K, N, S, R, T ï Resistance thermometer Pt100 (3-wire) ï Linear inputs: 0-50mV, 10-50mV keyboard definable 2-10V, 0-10V, 0-20mA, 4-20mA with an external shunt. An auxiliary analogue input is available for a current transformer input. The instrument has a double control out­put that is both relay (5A a 250Vac /30Vdc cos
ϕ
= 1) and static (24Vdc ± 10%, 12Vmin a 20mA) and up to a maxi­mum of 3 alarm relay outputs (5A, 250Vac/30Vdc cos
ϕ
= 1). Alternatively, the control output can be analogue (0-20mA, 4-20mA or 0-10V, 2-10V).
The optional communications port can be Current Loop or RS485 with GEFRAN (Cencal) protocol with a maximum speed of 9600 baud (RS485). The programming of the instrument is simplified by the grouping of the parame­ters into function blocks. Access to the configuration parameters is protected by a hardware jumper and a protection code can be used to restrict the number of parameters that can be displayed and modified by the user. A PC programming kit is available for even simpler configuration, composed of a cable and a guided program for Windows environment (see data sheet code WINSTRUM).
TECHNICAL DATA
I
NPUTS
Accuracy 0,5% f.s. ± 1 digit Sampling time 120msec
TC- Thermocouple
for 1000 instrument J
(Fe-CuNi) 0...800°C / 32...999°F
K (NiCr-Ni)
0...999°C / 32...999°F
N
(NiCr-Si-NiSi)
0...999°C / 32...999°F
S
(Pt10Rh-Pt) 0...999°C / 32...999°F
R (Pt13Rh-Pt) 0...999°C / 32...999°F T (Cu-CuNi) -100...400°C / -148...752°F for 1001, 1101 instruments J
(Fe-CuNi) 0...800°C / 32...999°F
K (NiCr-Ni) 0...1300°C / 32...1999°F N (NiCr-Si-NiSi) 0...1300°C / 32...1999°F S
(Pt10Rh-Pt)
0...1600°C / 32...1999°F
R
(Pt13Rh-Pt) 0...1600°C / 32...1999°F
T (Cu-CuNi) -100...400°C / -148...752°F
Configured from the faceplate. The error on the ambient temperature compensation is 0,05°C for every 1°C variation. Over and under range, erro­neous connection and opencircuit probe messages.
RTD 2/3-wires
for 1000 instrument Pt100 -19,9...99,9°C / -19,9...99,9°F Pt100 -199...400°C / -199...752°F
A - Indication of process variable
green digits h. 14mm (1000), 10mm (1001), 20mm (1 101)
B - Indication setpoint
green digits h. 14mm (1000), 10mm (1001), 14mm (1 101)
C - Function key D - Raise key E - Lower key
FACEPLATE DESCRIPTION
RTD 2/3-wires
for 1001, 1101 instruments Pt100 -199,9...199,9°C / -199,9...199,9°F Pt100 -200...400°C / -328...752°F
DC - Linear
0...50mV, 10...50mV Ri > 1M To be used only with external shunt on the controller for 0...10V, 0...20mA,
4...20mA signals.
OUTPUTS
Main output with direct action (heating) or inverse action (cooling).
Relay
With rating 5A at 250Vac/30Vdc cosϕ =1 (3,5A at cosϕ = 0,4); Spark suppression on the NO contact. (Order code R0);
Logic
24V± 10%, Rout = 470 (12Vmin a 20mA). Protected against inverse polarity and shortcircuit.
Continuous
0...20mA or 4...20mA dc output on a max. resistance of 500configurable as
0...10V with 500load. Rload 47KΩ. (order code V and I)
S
ERIAL LINE
Optoisolated 4-wires. Passive Current Loop (1200 baud) inter­face or RS485 4-wires (1200/2400/4800/9600 baud). Protocol: GEFRAN CENCAL
POWER SUPPLY
Standard: 100...240Vac/dc ± 10% on request: 11...27Vac/dc ± 10%
50/60Hz; 9VA max. Protection by internal fuse not serviceable by the user.
AMBIENT CONDITIONS
Working temperature: 0...50°C Storage temperature: -20...70°C Humidity: 20...85%Ur non condensing
CONTROL
On/Off, P, PD, PID either for heating or cooling, with parameters configurable from the faceplate:
• Proportional band: 0,0...99,9% f.s.
• Integral time: 0,0...99,9 min
• Derivative time: 0,0...9,99 min (0,0...19,99 min)
• Reset power (proportional band
position): 0...100%.
• Hysteresis (only for On/Of f control):
-199...999 (-999...1999) digit.
• Cycle time: -2...200 sec (0 for On/Of f
control).
• Soft-start (gradual increase of main out-
put power over a predetermined time on switch on): 0...99,9 min
• Manual reset (correction of the of fset
after setting):
-199...999 (-999...1999) digit.
• Offset (setting a difference between the
actual measurement of the input probe and the value read by the controller):
-199...300 (-300...300) digit.
- Automatic/Manual function with bum-
pless transfer between manual and auto­matic.
- Automatic power on and power off to
disactivate the instrument.
ALARMS
• 3 alarms, settable as absolute, deviation
or symmetrical deviation alarm with respect to the control setpoint with confi­gurable mode (Hi or Lo).
• The alarm point may be set anywhere within the configured scale.
• AL1 alarm with PD action with configu­rable parameters.
- Proportional band is set for the hystere­sis of AL1 in the range:
-199...999 (-999...1999) digit.
- Derivative time: 0,0...9,99 (0,0...19,99)min.
- Cycle time: 1...200 sec (0 for On/Of f
alarm).
• Alarm (AL3) may be used as opencircuit
load alarm (HB) when used with input from a current transformer; configurable current scale: 0...99,9 (0...199,9)
• LBA (Loop Break Alarm) function alarm.
• Intervention time and power output in the
alarm condition are configurable from the faceplate.
• Hysteresis for the alarm setpoint is confi-
gurable from the faceplate in the range:
-199...999 (-999...1999) digit.
WEIGHT
320g (1000) 400g (1001, 1101)
B
E
GF
D
A
C
B
E
GF
D
A
C
GF
B
ED
A
C
F - Main output indication, green led G - Alarm LEDs, red led
IP54 faceplate protection (IP65 available)