A - Indication of process variable
green digits h. 14mm (1000), 10mm (1001), 20mm (1 101)
B - Indication setpoint
green digits h. 14mm (1000), 10mm (1001), 14mm (1 101)
C - Function key
D - Raise key
E - Lower key
FACEPLATE DESCRIPTION
RTD 2/3-wires
for 1001, 1101 instruments
Pt100 -199,9...199,9°C / -199,9...199,9°F
Pt100 -200...400°C / -328...752°F
DC - Linear
0...50mV, 10...50mV
Ri > 1MΩ
To be used only with external shunt on
the controller for 0...10V, 0...20mA,
4...20mA signals.
OUTPUTS
Main output with direct action (heating) or
inverse action (cooling).
Relay
With rating 5A at 250Vac/30Vdc cosϕ =1
(3,5A at cosϕ = 0,4);
Spark suppression on the NO contact.
(Order code R0);
Logic
24V± 10%, Rout = 470Ω
(12Vmin a 20mA).
Protected against inverse polarity and
shortcircuit.
Continuous
0...20mA or 4...20mA dc output on a max.
resistance of 500Ω configurable as
0...10V with 500Ω load.
Rload ≥ 47KΩ.
(order code V and I)
S
ERIAL LINE
Optoisolated 4-wires.
Passive Current Loop (1200 baud) interface or RS485 4-wires
(1200/2400/4800/9600 baud).
Protocol: GEFRAN CENCAL
POWER SUPPLY
Standard: 100...240Vac/dc ± 10%
on request: 11...27Vac/dc ± 10%
50/60Hz; 9VA max.
Protection by internal fuse not serviceable
by the user.
AMBIENT CONDITIONS
Working temperature: 0...50°C
Storage temperature: -20...70°C
Humidity: 20...85%Ur non condensing
CONTROL
On/Off, P, PD, PID either for heating or
cooling, with parameters configurable
from the faceplate:
• Proportional band: 0,0...99,9% f.s.
• Integral time: 0,0...99,9 min
• Derivative time:
0,0...9,99 min (0,0...19,99 min)
• Reset power (proportional band
position): 0...100%.
• Hysteresis (only for On/Of f control):
-199...999 (-999...1999) digit.
• Cycle time: -2...200 sec (0 for On/Of f
control).
• Soft-start (gradual increase of main out-
put power over a predetermined time on
switch on): 0...99,9 min
• Manual reset (correction of the of fset
after setting):
-199...999 (-999...1999) digit.
• Offset (setting a difference between the
actual measurement of the input probe
and the value read by the controller):
-199...300 (-300...300) digit.
- Automatic/Manual function with bum-
pless transfer between manual and automatic.
- Automatic power on and power off to
disactivate the instrument.
ALARMS
• 3 alarms, settable as absolute, deviation
or symmetrical deviation alarm with
respect to the control setpoint with configurable mode (Hi or Lo).
• The alarm point may be set anywhere
within the configured scale.
• AL1 alarm with PD action with configurable parameters.
- Proportional band is set for the hysteresis of AL1 in the range:
-199...999 (-999...1999) digit.
- Derivative time:
0,0...9,99 (0,0...19,99)min.
- Cycle time: 1...200 sec (0 for On/Of f
alarm).
• Alarm (AL3) may be used as opencircuit
load alarm (HB) when used with input
from a current transformer; configurable
current scale: 0...99,9 (0...199,9)
• LBA (Loop Break Alarm) function alarm.
• Intervention time and power output in the
alarm condition are configurable from the
faceplate.
• Hysteresis for the alarm setpoint is confi-
gurable from the faceplate in the range:
-199...999 (-999...1999) digit.
WEIGHT
320g (1000)
400g (1001, 1101)
B
E
GF
D
A
C
B
E
GF
D
A
C
GF
B
ED
A
C
F - Main output indication, green led
G - Alarm LEDs, red led
IP54 faceplate protection (IP65 available)