GFK-2461B Serial Communications Modules
August 2007
IC695CMM002 and IC695CMM004
PACSystems RX3i Serial Communications modules expand the serial communications capabilities of the RX3i system.
MODULE OK
PORT FAULT
Serial Communications module IC695CMM002 provides two independent, isolated serial ports. Serial Communications module IC695CMM004, illustrated at right, provides four independent, isolated serial ports. Up to six Serial Communications modules can be located
P1 P2: P3: P4:
in the main PACSystems RX3i backplane.
Each port can be configured for MODBUS Master, MODBUS Slave, or Serial I/O protocol. In addition, for modules that are version 1.10 or
STATUS
PORT 1
later, each port can be configured for CCM Slave protocol using Proficy Machine Edition 5.6, SIM 6 or later. For modules that are version 1.20 or later, each port can be configured for DNP3 Master or DNP3 Slave protocol using Machine Edition 5.6 SIM 10 or later. If any
STATUS
PORT 2
port is configured for DNP3 Master or Slave, the other ports on the module can only be configured for DNP3 Master or Slave.
Additional module features include:
Port-to-port isolation and port-to-backplane isolation
RS-232, RS-485/422 communication, software-selected
Hardware handshake: RTS/CTS for RS-232
Selectable Baud Rates: 1200, 2400, 4800, 9600, 19.2K, 38.4K,
57.6K, 115.2K
Module fault status reporting (Watchdog, Ram Fail, Flash Fail)
Module identity and status reporting, including LED status
indicators
Meets CE, UL/CUL 508 and 1604, and ATEX requirements
Flash memory for future upgrades
These modules must be located in an RX3i Universal Backplane.
RX3i Serial Communications can be hot-inserted and removed following the instructions in the PACSystems RX3i System Manual, GFK-2314.
STATUS
PORT 3
STATUS
PORT 4
IC695CMM004
Page 3
2 RX3i Serial Communications Modules
GFK-2461B
Release Information
This release is an upgrade of previous version 1.10.
Release History
Release Upgrade Kit Comments
IC695CMM002-AA IC695CMM004-AA
IC695CMM002-AB IC695CMM004-AB
IC695CMM002-AC IC695CMM004-AC
N/A Initial Release
44A753277-G02 44A753278-G02
44A753277-G03 44A753278-G03
Supports CCM Slave Protocol
Supports DNP3 Master and DNP3 Slave Protocol
New for this Release
This release of the RX3i Serial Module adds support for Distributed Network Protocol 3.0 Master and Slave to the other protocols: MODBUS Master/Slave, CCM, and Serial I/O. This module does not operate with COMMREQs but rather uses preconfigured mappings of the I/O reference memory.
MODBUS Master and MODBUS Slave Protocols now support the configuration of 1 stop bit, for compatibility with some GE Fanuc Automation MODBUS Slaves.
Compatibility
Programmer: Proficy® Machine Edition Logic Developer 5.6 with Service Pack 2 SIM 10
RX3i CPU: PACSystems RX3i CPU Version 5.00 or later is required to be able to use the time
synchronization feature on a DNP3 Master port.
Problems Resolved for This Release
When parity is set to none in the port configuration for the Modbus Master or Modbus Slave protocols, the stop bits were forced to 2. This restriction has now been removed and the stop bits can be set to 1 or 2.
Page 4
RX3i Serial Communications Modules 3
GFK-2461B
Restrictions and Open Issues in this Release
1. When multiple group objects (i.e. %I and %AI memory) are read in a single request, the DNP3 port will
ignore all but the first object. Operations of multiple group objects should be split into multiple successive exchanges (i.e. exchange 1 - %I, exchange 2 - %AI).
2. The DNP3 slave port has problems using the link layer to validate frame receipt. The DNP3 organization
encourages users not to do this.
3. These modules do not support GE Fanuc special MODBUS commands for use with a Daniels Flow
Computer.
4. PLC Reference Address and Reference Length Parameters do not support bit length/start. Bit and Non-
Byte Length operations must begin on a byte boundary.
5. When a port is configured for CCM Slave protocol, and:
a new configuration is stored to the PLC using Machine Edition, or
the system is power-cycled, or
the module is hot-inserted,
if the first query received from the CCM Master is a Read Scratchpad request, the module will reject that request. All subsequent Read Scratchpad requests will be successful unless one of the above conditions occurs again.
Operating Notes
The maximum resolution for the MODBUS drop delay is 420us, so the minimum time for a drop delay is 420us.
Installation in Hazardous Locations
EQUIPMENT LABELED WITH REFERENCE TO CLASS I, GROUPS A, B, C & D, DIV. 2 HAZARDOUS LOCATIONS IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D OR NON-HAZARDOUS LOCATIONS ONLY
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES; AND
WARNING - EXPLOSION HAZARD - DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
Page 5
4 RX3i Serial Communications Modules
GFK-2461B
Specifications: IC695CMM002 and IC695CMM004
Refer to the PACSystems RX3i System Manual, GFK-2314, for product standards and general specifications.
Number of Serial Ports IC695CMM002: two independent serial ports
IC695CMM004: four independent serial ports
Connectors RJ-45
Number of Serial Communications Modules per CPU
Backplane power requirements
LEDs Module OK, Port Fault, Port Status (2 or 4)
Port Type RS-232 or RS-485/22. 4-wire (full duplex) or 2-wire (half-duplex)
Flow Control for R-232 Selectable: Hardware (CTS/RTS) or none
Baud rates 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2k
Parity Even, odd, none
Data bits 7, 8
Stop bits 1, 2
Operating Temperature
Input Impedance Zin > 96 kOhm for RS-485/422
Max Overvoltage +/- 25V
Channel-Channel Crosstalk
Six in the main CPU backplane
IC695CMM002 0.7 Amps maximum @ 3.3 VDC
0.115 Amps maximum @ 5.0 VDC
IC695CMM004 0.7 Amps maximum @ 3.3 VDC
0.150 Amps maximum @ 5.0 VDC
operation for RS-485/422
0°C to + 60°C
3 kOhm < Zin < 7 kOhm for RS-232
–55dB minimum
Isolation Port to Backplane and to frame ground: 250 VAC continuous;
In order to meet emission and immunity requirements for the EMC directive (CE mark), shielded cable must be used with this module.
1500 VAC for 1 minute, 2550VDC for one second.
Port to port: 500VDC continuous, 710VDC for one minute.
Page 6
RX3i Serial Communications Modules 5
GFK-2461B
LEDs
MODULE OK
PORT FAULT
P1 P2: P3: P4:
STATUS
PORT 1
STATUS
PORT 2
STATUS
PORT 3
STATUS
PORT 4
The Module OK LED indicates the status of the module. Solid green indicates that the module has been configured. The Module OK LED is off, if the module is not receiving power from the R3i backplane, or if a serious module fault exists.
At powerup, the Module OK LED flashes green/off while the module is executing powerup diagnostics. It then flashes more slowly as the module receives its configuration from the CPU.
If a problem occurs, the Module OK LED flashes amber, The blink code (see below) indicates the cause of the error.
1 = watchdog expired 2 = RAM error 6 = Invalid CPU Master Interface version 7 = CPU heartbeat failure 8 = Failed to get semaphore
The Port Fault LED indicates the status of all ports. The Port Fault LED is green when there are no faults present on any enabled port. If this LED turns amber, there is a fault on at least one port.
A port’s Status LED flashes green when there is activity on the port.
IC695CMM004
The area below the module LEDs can be used to record identifying information about each port.
Serial Ports
Each port is a standard RJ-45 female connector with the following pin assignments. For MODBUS applications, note that these pin assignments are different than the standard MODBUS pin assignments. If the port is configured for MODBUS master or slave operation, custom cables are needed.
RJ-45
Pin
8
1
Note: There is no shield or frame ground pin on the port connector.
RS­232
8 COM GND GND
7 Termination 2
6 CTS R- (RxD0)
5 COM GND GND
4 Termination 1
3 RxD R+ (RxD1)
2 TxD T- / R- (D0) T- (TxD0
1 RTS T+ / R+ (D1) T+ (TxD1)
RS-485/422
Half Duplex
RS-485/422 Full Duplex
Page 7
6 RX3i Serial Communications Modules
r
j
j
j
GFK-2461B
If the Serial Communications module is communicating with a Series 90-30 CPU363 or external PACSystems RX3i CPU, the connections are:
RX3i Serial Module CPU363/RX3i
T+ To RD('B')
T- To RD('A')
R+ To SD('B')
R- To SD('A')
Termination
By default, each port is set for no termination. Termination is needed if the module is the first or last device on an RS-485 network, even if there is only one other device on the network. Termination can be provided using either an external resistor as shown below or the port’s built-in 120-Ohm termination. If line termination other than 120 Ohms is required, an appropriate external resistor must be supplied.
User-Supplied Termination for RS-485
Full Duplex 4-Wire
RS-485
6
3
Terminating
Resisto
Half Duplex 2-Wire
RS-485
2
1
Terminating
Resistor
Built-in Termination for RS-485
Termination using the built-in 120-Ohm resistor can be provided by either setting the appropriate RS-485 termination jumper OR by installing shorting jumpers on the RS-485 cable connector that attaches to the serial port.
Internal 120-Ohm Termination,
Default Jumper Positions
Side of Port Connector
Front of Module with
Faceplate Removed
Jumper for Full Duplex, 4-Wire in Default (Upper) Position
Jumper for Half Duplex, 2-Wire in Default (Upper) Position
Full Duplex
Four-Wire RS-485
Move top
umper down or connect Port pins 7 and 3
Leave bottom
umper in Default Position
Half Duplex
Two-Wire RS-485
Leave top Jumper in Default Position
Move bottom
umper down or connect Port pins 4 and 1
To set 120-Ohm termination internally:
1. Remove the module’s faceplate by pressing in on the side tabs and pulling the faceplate away from the
module.
2. With the module oriented as shown, move either the upper or lower jumper: