The QS4, hereinafter referred to as the FACP or control panel, when
properly installed, operates as a Local Protected Premises Fire Alarm
System in accordance with the following standards:
•NFPA Standard 72, 1999 Edition
•Underwriters Laboratories Standard 864, 7th Edition
•Underwriters Laboratories of Canada Standard ULC S527
In addition, Auxiliary Fire Alarm System operation requires a Reverse
Polarity Module (RPM). Central Station Fire Alarm System operation
requires a Dialer card (DLD).
Installation in accordance with this manual, applicable codes, and the
instructions of the authority having jurisdiction is mandatory.
Limitation of Liability
Fire Alarm System
Limitations
FCC Compliance Statement
Edwards Systems Technology (EST) shall not under any circumstances
be liable for any incidental or consequential damages arising from loss
of property or other damages or losses owing to the failure of EST
products beyond the cost of repair or replacement of any defective
products. EST reserves the right to make product improvements and
changes to product specifications at any time.
While every precaution was taken during the preparation of this
document to ensure its accuracy, EST assumes no responsibility for
errors or omissions.
Automatic fire alarm systems can not guarantee against property
damage, loss of property, or loss of life. An automatic fire alarm system's
ability to provide early warning of a developing fire may be limited for a
variety of reasons, but mainly due to improper installation or
maintenance.
The best way to minimize system failures is to perform regularly
scheduled preventive maintenance in accordance with national and local
fire codes. All system components and wiring should be tested and
maintained by trained fire alarm system professionals.
This equipment can generate and radiate radio frequency energy. If this
equipment is not installed in accordance with this manual, it may cause
interference to radio communications. This equipment has been tested
and found to comply within the limits for Class A computing devices
pursuant to Subpart B of Part 15 of the FCC Rules. These rules are
designed to provide reasonable protection against such interference
when this equipment is operated in a commercial environment.
Operation of this equipment is likely to cause interference, in which case
the user at his own expense, will be required to take whatever measures
may be required to correct the interference.
About this manual • iii
Related documentation • iv
Document history • vi
Chapter 1Product description • 1.1
System overview • 1.2
Component descriptions • 1.3
Circuit descriptions • 1.5
Controls and indicators • 1.9
Controls and indicators behind the flip-down cover • 1.10
Controls and indicators on the zone annunciator card • 1.11
Interpretation of screen displays • 1.12
Chapter 2Installation • 2.1
Installation do's and don'ts • 2.2
Installation checklist • 2.3
Two ways to install the cabinet: Surface or semi-flush mount • 2.4
How to assemble the panel • 2.6
Wiring mains ac and earth ground • 2.7
System jumper settings • 2.8
System addressing • 2.10
Terminal definitions • 2.14
Connecting a PT–1S printer • 2.22
Installing standby batteries • 2.23
Content
Chapter 3Operating instructions • 3.1
Instructions for the Level 1 operator (public mode access) • 3.2
Instructions for the Level 2 operator (emergency mode access) • 3.5
Instructions for the Level 3 operator (maintenance mode access) • 3.7
Instructions for the Level 4 operator (service mode access) • 3.10
QuickReference list • 3.11
Chapter 4Programming instructions • 4.1
Overview • 4.2
QuickStart setup instructions • 4.4
Customizing the system configuration • 4.13
Setting up an Output Group • 4.21
Setting up a Zone • 4.26
This manual provides information on how to properly install, wire, and
maintain the FACP and related components, and is organized as
follows:
Chapter 1 provides a detailed description of the fire alarm control panel
and its operation.
Chapter 2 provides instructions for installing the fire alarm control
panel.
Chapter 3 provides instructions for operating the control panel.
Chapter 4 provides instructions for programming the fire alarm system
from the front panel.
Chapter 5 provides simplified wiring schematics for standard
applications.
Chapter 6 provides instructions for maintaining the system.
Appendix A provides worksheets for calculating maximum wire lengths
for notification and Signature circuits, and for sizing standby batteries.
Appendix B provides a set of bar codes that you can use to enter text
for location messages.
Appendix C provides information on how to program the SIGA–REL
using the QS–CU (QuickStart Configuration Utility).
Safety information
Important safety admonishments are used throughout this manual to
warn of possible hazards to persons or equipment.
WARNING: Warnings are used to indicate the presence of a hazard
which will or may cause personal injury or death, or loss of service if
safety instructions are not followed or if the hazard is not avoided.
Caution: Cautions are used to indicate the presence of a hazard which
will or may cause damage to the equipment if safety instructions are not
followed or if the hazard is not avoided.
This chapter provides a detailed description of the fire alarm control
panel and its operation.
Content
System overview • 1.2
Component descriptions • 1.3
Circuit descriptions • 1.5
Controls and indicators • 1.9
Controls and indicators behind the flip-down cover • 1.10
Controls and indicators on the zone annunciator card • 1.11
Interpretation of screen displays • 1.12
Hardware capabilities vary depending on cabinet
size and option card configuration, but generally:
•Up to four Class A or Class B Signature
signaling line circuits that support up to 250
single-address Signature devices each
•Up to 40 Class A or 48 Class B initiating device
circuits (IDC). Combination systems can not
exceed 40 IDC circuits total
•Up to 16 Class A or 20 Class B notification
appliance
•Up to two 30-zone displays
•Up to 96 dry-contact relay
•4.5 amps of 24 Vdc power for external
notification appliances
•Battery charger capable of charging batteries
rated up to 40 Ah. Maximum battery size for
ULC applications is 30 Ah
•Up to eight, fully-supervised, mirrored or
customized remote annunciators
Minimum system requirements
A Local Protected Premises Fire Alarm System
requires only the FACP (CPU, PS6, and
enclosure) with at least one SLIC, ZB16–4, or
ZA8–2 card programmed with at least one audible
output circuit and one alarm input circuit.
In addition to the hardware requirements of a
Local system:
•Add a 2–CTM City Tie Module for an Auxiliary
Fire Alarm System
•Add a DLD Dual Line Dialer Card or RPM
Reverse Polarity Module for a Remote
Supervising Station Fire Alarm System
•Add a DLD Dual Line Dialer Card or RPM
Reverse Polarity Module for a Central Station
Fire Alarm System
•Add a SIGA–REL for Releasing Device Service
monitor events. In normal mode, the control panel
monitors the system for any events.
Off-normal operating mode description
The panel operates in off-normal mode any time
there is an event introduced into the system.
When this happens, the CPU:
• Changes the contact positions on the
appropriate common relays
• Activates all common alarm outputs (alarm
events only)
• Turns on the panel buzzer
• Executes the appropriate programmed output
response for the input that signaled the event
• Sends a record of the event to the appropriate
display queue and out the serial port
If there is no operator in attendance, the panel
displays the content of the highest priority display
queue containing a record.
If there is an operator in attendance, the panel
displays the content of the current display queue
regardless of any new events introduced into the
system.
Failsafe operating mode description
The panel operates in failsafe mode when the
CPU loses the ability to communicate with the PS6
and JP1 on the PS6 is in the ON position. When
this happens, the power supply:
• Closes the common trouble relay contacts
• Instructs the dialer to send the default trouble
message
• Monitors the system for any alarm events
If an alarm event occurs, the power supply:
• Changes the contact positions on the common
alarm relay
• Turns on all conventional common alarm
outputs. Signature common alarm outputs are
not affected.
Normal operating mode description
The panel operates in normal mode in the
absence of any alarm, supervisory, trouble, and
• Instructs the dialer to send the default alarm
message
Component descriptions
Product description
123
J5
6A
JP1 CONFIGURATION
PIN 1 & 2 = MODEM PWR
PIN 2 & 3 = RTS
5
6B
J6
J7
J8
JP1
J2
13
784
9
10
1. Cabinet enclosure: Houses the panel
electronics and standby batteries.
2. SL30–1 LED/Switch Card: Provides thirty
circuits for point or zone annunciation. Each
circuit has two LEDs for annunciating alarm,
supervisory, and trouble signals, and a button
numbered from 31 to 60.
3. SL30 LED/Switch Card: Same as SL30–1
except the buttons are numbered 1–30.
system messages, status information, and
programming menus, and executes system
responses based on the panel programming.
5. PS6 Power Supply Card: Provides primary dc
power to the panel electronics and external
circuits. The PS6 also provides common alarm,
supervisory and trouble relays for remote station
supervision.
Product description
6. RS485 (NT–A) Class A Card: The NT–A
comprises the RS485 card and QS–232 UART
module. Together these provide an additional
RS–232 channel to allow Class A communication
between the control panel and other remote
annunciator panels. Control panels require
installation of both cards while remote
annunciator panels only require installation of a
QS–232 card and only then if you want to
connect a printer or service computer.
7. ZA8–2 Class A Conventional Zone Card:
Provides six dedicated Class A initiating device
circuits (IDCs) for connecting two-wire smoke
detectors and dry-contact initiating devices. The
ZA8–2 also provides two circuits that you can
configure as IDCs or as 24 Vdc notification
appliance circuits (NACs).
8. ZB16–4 Class B Conventional Zone Card:
Provides twelve dedicated Class B initiating
device circuits (IDCs) for connecting two-wire
smoke detectors and dry-contact initiating
devices. The ZB16–4 also provides four circuits
that you can configure as IDCs or as Class B 24
Vdc notification appliance circuits (NACs).
10. ZR8 Relay Card: Provides eight dry-contact
relays. You can configure each relay for
normally-open or normally-closed operation.
11. DLD Dual Line Dialer Card: Provides two
telephone line connections for sending system
messages to a compatible Digital Alarm
Communicator Receiver.
12. SLIC Signature Loop Intelligent Controller
Card: Provides one Class A or Class B signaling
line circuit (loop) for connecting Signature series
detectors and modules. The SLIC also provides
two Class A or Class B notification appliance
circuits (NACs) for connecting polarized 24 Vdc
notification appliances (horns, strobes).
13. Standby batteries: Provides dc power to the
panel electronics in the absence of ac power.
14. Transformer: Changes the mains ac supply
voltage for the power supply card.
15. AC wiring block and fuse holder: Provides
connections for mains ac (primary power) and 5A
fuse.
9. QS–Cable12 Expansion Cable: Extends the
CPU data and power bus to circuit cards installed
on the lower DIN rail in the 12-option cabinet.
Style: Form C
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when
connected to a power-limited source
2. Relay 2 (Common Supervisory)
Style: Normally-open
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when
connected to a power-limited source
3. Relay 3 (Common Trouble)
Style: Normally-open, held closed
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when
connected to a power-limited source
Product description
2
534
6
71
4. Relay 4 (Programmable)
Style: Normally-open
Contact rating: 1 A @ 20.4 – 26.4 Vdc (0.6 PF)
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited only when
connected to a power-limited source
5. Smoke/Accessory Power
Output: Continuous or interruptible via jumper
selection
Voltage: 24 Vdc, regulated
Current: 250 mA
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Supervised and power-limited
6. RS485
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Wire type: Twisted pair, six twists per foot
minimum
Circuit capacitance: 0.4 µF
Circuit resistance: 100 Ω
Supervised and power-limited
7. RS232
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Nonsupervised and power-limited
Wire length: 20 ft maximimum
9
8. AUX Power #1, #2, and #3
Voltage: 17.5 – 26.4 Vdc FWR (full wave
rectified)
Current: 1.5 A each
Wire size: 18 to 12 AWG (0.75 to 2.5 mm²)
Power-limited and supervised for short circuit
conditions only
9. Battery Circuit
Charge current: 2 A
Charge capacity: 40 Ah (UL), 30 Ah (ULC)
Supervised and nonpower-limited
Configuration: Class B or Class A
Output voltage: 24 Vdc, nominal
Output current: 2.0 A @ 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
End of line resistor: 10 kΩ, 1/2W
Supervised and power-limited
2. NAC #2
Configuration: Class B or Class A
Output voltage: 24 Vdc, nominal
Output current: 1.0 A @ 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
End of line resistor: 10 kΩ, 1/2W
Supervised and power-limited
3. Signature Loop
Configuration: Class B (Style 4) or Class A (Style 6)
Capacity: 125 Signature detectors, 125 Signature single-address
modules
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
Circuit resistance: 65 Ω
Circuit capacitance: 0.3 µF
Supervised and power-limited
4. NAC Riser In/Out
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
2
)
2
)
2
)
12
43
ZR8 Relay Card circuits
1. Dry-contact relays R1 – R4
Outputs: Normally-open or normally-closed contacts via jumper
selection
Contact rating: 24 Vdc @ 1.0 A
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
Nonsupervised, and power-limited only when connected to a
power-limited source
2. Dry-contact relays R5 – R8
Outputs: Normally-open or normally-closed contacts via jumper
selection
Contact rating: 24 Vdc @ 1.0 A
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
Nonsupervised, and power-limited only when connected to a
power-limited source
Wiring configuration: Class B
Detector voltage: 20.33 – 24.76 Vdc, max ripple 2000 mV
Short circuit current: 75.9 mA, max.
Resistance: 50 Ω, max.
Capacitance: 100 µF, max
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
End of line resistor: 4.7 kΩ, 1/2W
Supervised and power-limited
2. NAC Circuits Z13 – Z16
Wiring configuration: Class B
Output voltage: 24 Vdc, nominal
Output current: 2.0 A @ 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
End of line resistor: 10 kΩ, 1/2W
Supervised and power-limited
IDC specifications apply when programmed as IDC circuit
3. R1
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
4. R2
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
2
)
2
)
2
)
2
)
Product description
1
2
1
3
4
ZA8–2 Class A Conventional Zone Card circuits
1. IDC Circuits Zone 1 – Zone 3, Zone 5 – Zone 7
Wiring configuration: Class A
Detector voltage: 19.90 – 22.46 Vdc, max ripple 2000 mV
Short circuit current: 75.9 mA, max.
Resistance: 50 Ω, max.
Capacitance: 100 µF, max
Wire size: 18 to 12 AWG (0.75 to 2.5 mm2)
End of line resistor: 4.7 kΩ, 1/2W
Supervised and power-limited
2. NAC Circuits Zone 4, Zone 8
Wiring configuration: Class A
Output voltage: 24 Vdc, nominal
Output current: 2.0 A, 24 Vdc
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
End of line resistor: 10 kΩ, 1/2W
Supervised and power-limited
IDC specifications apply when programmed as IDC circuit
3. NAC PWR IN (Zone 4)
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
4. NAC PWR IN (Zone 8)
Voltage: 24 Vdc, nominal
Wire size: 18 to 12 AWG (0.75 to 2.5 mm
Moves the cursor up one line at a time or
to the previous record in the display
queue
Moves the cursor down one line at a time
or to the next record in the display queue
Moves the cursor right one character at a
time or to the next display queue
Moves the cursor left one character at a
time or to the previous display queue
Enters operator input and selects menu
items
2. Alarm LED: Indicates the panel posted an
alarm event record into the corresponding display
queue.
3. Supervisory LED: Indicates the panel posted
a supervisory event record into the corresponding
display queue.
4. Disable/Test LED: Indicates part of the
system is disabled or is currently under test.
Disabled components also signal a system
trouble.
3
8
13
18
23
28
9
14
19
24
29
10
15
20
25
30
8
13
18
23
28
4
9
14
19
24
29
5
10
15
20
25
30
5. Monitor LED: Indicates the panel posted a
monitor event record into the corresponding
display queue.
6. Trouble LED: Indicates the panel posted a
trouble event record into the corresponding
display queue.
7. Ground Fault LED: Indicates a ground fault in
the system wiring. Ground faults also signal a
system trouble.
8. CPU Fail LED: Indicates an unexpected
reboot or failure with the microprocessor. CPU
failures also signal a system trouble.
9. Power LED: Indicates the panel has ac power.
10. Panel Silence/Acknowledge button/LED:
Turns off the panel buzzer and acknowledges all
events. The Panel Silenced LED indicates that all
off normal events have been acknowledged and
the internal buzzer is off.
11. Status button: Displays the Status menu
from which you can identify active or disabled
points in the system.
12. Help button: Provides additional information
for the event record selected on the display.
Controls and indicators behind the flip-down cover
7
9
6
584
1234167890
5
3
1. Enable Controls key switch: Gives priority
access to control functions reserved for operators
with Level 2 access.
2. Barcode scanner jack: Input point for optional
barcode scanner.
3. Numeric keypad: Numbered buttons for
entering data and selecting menu options.
11
6
27
22
17
12
7
2
28
23
18
13
8
3
29
24
19
14
9
4
30
25
20
15
10
5
1
2
11
6
1
12
7
2
13
8
3
14
9
4
15
10
5
26
21
16
26
21
16
27
22
17
28
23
18
29
24
19
30
25
20
6. Drill button: Turns notification appliances on
according to the panel programming but does not
place the panel in alarm. The LED indicates
when the panel is in Drill mode.
7. Menu button: Displays the operator menus.
8. Delete button: Returns to the previous menu
or back spaces the cursor.
4. Reset button: Restores devices or zones in
alarm or trouble to their standby condition. The
LED indicates when the panel is resetting.
5. Alarm Silence button: Turns active
notification appliances off according to the panel
programming. Pressing Alarm Silence a second
time turns them back on. The LED indicates
when the panel is in alarm and operating with
notification appliances turned off.
9. Enter button: Press the Enter button to accept
information from the operator or continue to the
next item.
Controls and indicators on the zone annunciator card
213
1
6
11
16
21
26
2
7
12
17
22
27
3
8
13
18
23
28
4
9
14
19
24
29
5
10
15
20
25
30
Product description
1. Zone display button: Displays an event
record for each device in the corresponding zone
that signaled an alarm.
2. Zone active LED: Indicates a device in the
corresponding zone signaled an alarm condition.
3. Zone trouble LED: Indicates a device or
wiring fault in the corresponding Zone.
Note: ULC requires that every fire panel have the
capability to visually display system status by
means of specific indicators for each zone. All
status changes must clearly indicate that the
information is an Alarm (ALM), Supervisory
(SUP), Trouble (TBL), or Monitor (MON).
This chapter provides instructions for installing the fire alarm control
panel.
Content
Installation do's and don'ts • 2.2
Installation checklist • 2.3
Two ways to install the cabinet: Surface or semi-flush mount • 2.4
How to assemble the panel • 2.6
Wiring mains ac and earth ground • 2.7
System jumper settings • 2.8
System addressing • 2.10
Terminal definitions • 2.14
Connecting a PT–1S printer • 2.22
Installing standby batteries • 2.23
Connecting a service computer • 2.24
When installing cabinets...DO use fasteners that can support the full weight of the
cabinet and standby batteries. Tighten firmly to avoid
vibrations.
DO NOT drill inside the cabinet with circuit cards installed.
Remove all metal filings before installing the circuit cards.
DO NOT recess the cabinet into the wall deeper than 2–11/16
inches (68.2 mm) from the finished wall surface to allow room
for the trim kit.
When installing circuit boards...DO ground yourself with an approved static-protective wrist
strap when handling circuit boards.
DO keep circuit boards in their protective antistatic packaging.
Remove only for inspection or installation.
DO NOT touch component leads and connector pins when
handling circuit boards.
DO disconnect ac power and batteries before installing or
removing circuit boards. Installing or removing circuit boards
while the control panel is energized may damage the
equipment.
When installing circuit wiring...
When installing Signature loops...DO NOT install more than fifteen SIGA–UMs or MABs
When installing standby batteries...DO NOT install standby batteries until after you completely
DO use appropriately sized wire for the application.
DO make sure there are no wire-to-ground shorts or wire-towire shorts before connecting field wires to the panel.
DO NOT over tighten screw terminals. Over tightening may
strip screw terminal threads and cause loose connections.
configured for two-wire smoke detectors on a loop.
DO NOT install more than seven SIGA–UMs or MABs
configured for two-wire smoke detectors on loops with isolator
devices.
DO NOT install more than ten SIGA–RELs on a loop. You
must use the QuickStart configuration utility to program a
SIGA–REL. Refer to the technical manual supplied with the
SIGA–REL and appendix C of this manual for programming
information.
Make sure the installation location is free from construction
dust and debris, and immune to extreme temperature ranges
and humidity.
Allow enough floor and wall space so the panel can be
installed and serviced without obstructions.
Pull and tag all field wiring. See Appendix A for wire length
calculations.
Open the shipping container and carefully unpack the
equipment. Check for any visible signs of damage. If there is
any damage, return the equipment to the place of purchase.
Keep the container and packing material until after completely
installing and testing the equipment. Use the shipping
container to return the equipment to the manufacturer.
Verify the shipping container contains the correct parts. If any
parts are missing or damaged, return the equipment to the
manufacturer.
See Figure 2-1 for cabinet dimensions.
Bring the primary power conductors into the left side
(nonpower-limited area) of the cabinet and wire to the ac
terminal block.
¨ Connect the field wiring
¨ Use the AutoLearn and
AutoLoop utilities to configure
the system
¨ Customize the system
configuration
¨ Install the standby batteries
WARNING: Make sure that the circuit breaker providing ac
power is switched off before connecting wires to the terminal
block.
Bring the field wiring into the power-limited area of the cabinet.
Verify there are no open or shorts then connect the wires to
their respective terminals.
Refer to chapter 4.
Refer to chapter 4.
Do not connect standby batteries to the panel until after
completely testing the panel.
terminal block makes a mechanical connection
to chassis (earth) ground. Do not allow the ac
hot and neutral conductors to make contact with
the middle connector on the ac terminal block.
Wiring instructions
1. Bring the mains ac conductors into the
cabinet through the 3/4–1/2 inch combination
knock-outs on the left side or upper left
corner of the cabinet.
2. Wire the hot (H, L1), neutral (N, L2), and
ground (G, E) conductors to the ac terminal
block as shown.
Notes
Keep power-limited wires in the shaded area
and nonpower-limited wires in the nonshaded
area.
Maintain a 1/4-inch separation between the
mains ac and battery wires (power-limited) and
and all other nonpower-limited wiring at all
times.
3. Insert tabbed end of terminal block cover
(deadfront) into the slot provided on the side
of the cabinet.
JP2 configures the Smoke/Accessory power
output for constant or resettable 24 Vdc.
•Set JP2 to ACC PWR to provide constant
24 Vdc for external equipment.
•Set JP2 to SMK PWR to provide resettable
24 Vdc for four-wire smoke detectors
JP1 configures the panel for failsafe operation.
Failsafe allows the system to generate output
responses even when the CPU loses
communication with the power supply card.
JP1 – JP8 configure which relay contacts are
present on the terminal connections for R1 – R8,
respectively.
The normal operating state of the relay (on or off
when the panel is normal) determines whether
the terminal connections are normally-open or
normally-closed.
The figure to the right shows the relay contact
positions when the relay is turned off.
Installation
R4+R4–
JP4
RS485 (NT–A) Class A Card jumpers
JP1 configures ground fault supervision for
Class A remote annunciators.
•Set a shorting plug across JP1–1 and JP1–2
when the PS6 powers the remote
annunciator and provides ground fault
supervision
•Set a shorting plug across JP1–2 and JP1–3
when an external supply powers the remote
annunciator and provides ground fault
supervision
Each option card installed in the panel is
assigned a unique card address. Only the SLIC,
ZB16–8, ZA8–2, and ZR–8 have card addresses
that you can set. The CPU, DLD and PS6 card
addresses are fixed.
00: Reserved for the CPU
01–07: Used for the SLIC, ZB16–8, ZA8–2, and
ZR–8
08–13: Used for the ZB16–8, ZA8–2, and ZR–8
14: Reserved for the DLD
15: Reserved for the PS6
ON
1234
ON
1234
ON
1234
ON
1234
ON
1234
ON
1234
ON
1234
= 01
= 02
= 03
= 04
= 05
= 06
= 07
ON
= 08
123 4
ON
= 09
123 4
ON
= 10
123 4
ON
= 11
123 4
ON
= 12
123 4
ON
= 13
123 4
Tip: When you install the option cards, set the
card addresses in consecutive order as you
move away from the power supply starting at
address 01.
Table 2-1: PS6 Power Supply card terminal definitions
NO C NC C NO C NO C NO N.C.RTS TX RX COM
118171615141312111098765432
SMOKE
ACC PWRRELAY 1 RELAY 2 RELAY 3 RELAY 4RS485RS232
–
+
–
+
TB1
BATT PWR
AUX1 AUX2 COM AUX3 COM
+
1
15432
–
NC
3
2
AUX POWER
TB2
TB3
Terminal No.NameDescription
TB1–1, –2Relay 1 NO, CNormally-open relay contacts that close automatically when
the panel processes an alarm event. The contacts remain
closed until all active alarm points restore and the panel
resets.
TB1–2, –3Relay 1 C, NCNormally-closed relay contacts that open automatically when
the panel processes an alarm event. The contacts remain
open until all active alarm points restore and the panel
resets.
TB1–4, –5Relay 2 C, NO
Normally-open relay contacts that close automatically when
the panel processes a supervisory event. The contacts
remain closed until the active supervisory point restores.
TB1–6, –7Relay 3 C, NONormally-open relay contacts that close automatically when
the panel energizes. The contacts open when the panel
processes a trouble event or when the panel loses power
and remain open until the trouble condition restores.
TB1–8, –9Relay 4 C, NONormally-open relay contacts that close depending on how
the user programs the panel.
TB1–10N.C.Not used
TB1–11, –12SMK/ACC PWR +, –
Provides regulated 24 Vdc for four-wire smoke detectors or
accessory devices depending on jumper setting.
TB1–13, –14RS485 +, –Connects to the Channel 1 input on a remote annunciator
TB1–1, –2ZONE 1 B+, B–Connects to the IN +/– terminals of the first device on the IDC.
TB1
TB2
TB1–3, –4ZONE 1 A+, A–
Connects to the OUT +/– terminals of the last device on the
IDC.
Note: ZONE 2, 3, 5, 6, and 7 connect the same as described for ZONE 1.
IDC/NAC circuit connections
Terminal No.NameDescription
TB1–13, –14ZONE 4 B+, B–
Connects to the IN +/– terminals of the first device on the NAC.
Polarity markings (+/–) indicate output signal polarity with the
circuit turned off. Polarity reverses with the circuit turned on.
TB1–15, –16ZONE 4 A+, A–Connects to the OUT +/– terminals of the last device on the
NAC.
TB1–17, –18NAC PWR IN+, IN–
Connects to the signal source used to provide 24VDC to ZONE
4.
TB2–13, –14ZONE 8 B+, B–Connects to the IN +/– terminals of the first device on the NAC.
Polarity markings (+/–) indicate output signal polarity with the
circuit turned off. Polarity reverses with the circuit turned on.
TB2–15, –16ZONE 8 A+, A–Connects to the OUT +/– terminals of the last device on the
NAC.
TB2–17, –18NAC PWR IN+, IN–
Connects to the signal source used to provide 24VDC to ZONE
8.
Note: ZONE 4 and ZONE 8 may be programmed as IDC circuits.
TB1–1, –2Z1+, Z1–Connects to the IN +/– terminals of the first device on the IDC.
Note: Z2–Z16 connect the same as described for Z1.
IDC/NAC circuit connections
Terminal No.NameDescription
TB2–7, –8Z13+, Z13–
Connects to the IN +/– terminals of the first device on the NAC.
Polarity markings (+/–) indicate output signal polarity with the
circuit turned off. Polarity reverses with the circuit turned on.
TB2–9, –10Z14+, Z14–same as above
TB2–11, –12Z15+, Z15–same as above
TB2–13, –14Z16+, Z16–same as above
TB2
TB1–15, –16R1+, R1–Connects to the signal source used to provide 24VDC to Z13 and
Z14.
TB1–17, –18R2+, R2–Connects to the signal source used to provide 24VDC to Z15 and
Z16.
Note: Z13, Z14, Z15, and Z16 may be programmed as IDC circuits.
1. Place the batteries in the
bottom of the control panel.
2. Wire the batteries to the
PS6.
Notes
Do not run wires through the
bottom knock-outs when
batteries are installed in the
control panel.
Battery wiring is supervised
and nonpower-limited.
Maintain a 1/4-inch
separation between powerlimited and nonpower-limited
wiring at all times.
Installation
+
For batteries rated greater
than 10 Ah
1. Place the batteries in a
BC-1 Battery Cabinet. The
cabinet must be mounted
within 3 ft of the control
panel, in the same room,
and connected with conduit.
2. Wire the batteries to the
PS6.
Note: Install, maintain, and test
standby batteries in
accordance with NFPA 72.
Connection of a service computer to the
control panel requires programming
cable P/N 260097, ordered separately.
Connection of a service computer to a
remote annunciator requires
programming cable P/N 360136 and a
RJ–11 to DB9 adapter P/N 240507,
both ordered separately.
This chapter provides instructions for programming the fire alarm system
from the front panel. Worksheets are provided at the end of the chapter
to use as programming aids and to document the system programming.
Content
Overview • 4.2
QuickStart setup instructions • 4.4
Customizing the system configuration • 4.13
Setting up an Output Group • 4.21
Setting up a Zone • 4.24
A Zone is a function in the system software that initiates an
active response based on a single alarm event. Firewall
designations, planned evacuation criteria, architectural design,
and other factors all contribute to how the system designer
divides the protected premises into zones.
FACP
ZONE 2
ZONE 1
ZONE 3
J
An Output Group is a function in the system software that
establishes the correlation between input circuits and
responses. When an input changes states, the condition of the
input determines which response the panel runs. For example,
a smoke detector initiates the Active response when it signals
an alarm condition but initiates the Trouble response when
removed from its base.
Exception Event while programming
the system, note the error code, and
then contact EST Technical Services
at 6411 Parkland Drive, Sarasota, FL
34243 or at 1-800-655-4497.
To clear the Exception Event, press
Alarm Silence while the event is
displayed. You may have to reset the
panel to display the event again.
This procedure uses the AutoLearn and AutoLoop utilities to
automatically configure the system. The AutoLearn utility
configures the option cards. The AutoLoop utility configures
the circuits on the Signature loop.
Caution: Running the AutoLearn utility deletes the existing
panel programming. If you have already programmed the
system, running AutoLearn requires you to re-enter everything
again from the beginning.
If you have a dialer installed, the AutoLearn utility requires you
to program the DLD before exiting. Be sure to have the
following:
•Subscriber account numbers, telephone numbers, and
transmission formats obtained from the CMS (Central
Monitoring Station). Appendic C provides a list of Contact ID
event codes.
•A completed copy of the DLD Programming Worksheet
(Figure 4-1).
After you have finished using the AutoLearn and AutoLoop
utilities to configure the system, you can either:
•Customize the system programming
Step 2:
Apply power to the system
•Go to step 11 and Save and Sync.
1. Verify that each circuit card installed in the control panel
has a unique card address.
2. Apply power to the control panel and to all the remote
annunciators.
After applying power, the panel CPU performs a diagnostic
check in the background. You can not begin programming
until this finishes and the AutoLearn option becomes
available.
Run the AutoLoop utility on each loop controller installed in
the control panel.
Caution: When the system reboots, the loop controller
reinitializes the loop. If you attempt to run the AutoLoop utility
during this time, you could corrupt the project database.
1. On the control panel, press Menu.
2. Choose Login then enter the password required for Level 4
access.
3. Choose Program > Configure.
If the loop is still initializing, do not proceed until loop
initialization has finished.
4. Choose Cards > Edit, then enter the card number for the
loop controller.
5. On the Edit Cards menu, choose AutoLoop.
6. If the number of detector and module addresses on the
display match the number installed on the loop, press
Enter to accept, then wait while the database is updated.
If not, press Del to cancel. You must correct the problem
before continuing with this loop.
Step 11:
Saving the project database
Tip: Only Save and Sync after you
have finished programming the control
panel and you want to update the
project databases in the remote
annunciators.
7. On the SLIC menu, choose Exit.
8. For each additional loop controller, repeat steps 4–7.
9. Choose Exit.
At this point, you have configured the project database for a
general alarm system. Refer to Table 4-2, Table 4-3 and
Table 4-4 for initial system settings.
If you want to accept the general alarm system configuration,
choose Save and Sync.
If you want to make changes to the system configuration,
choose Save, and then make your changes. See Customizingthe system configuration. After making all of your changes:
1. Press Menu.
2. Choose Login then enter the password required for Level 4
access.
3. Choose Program > Configure > Exit.
4. Choose Save and Sync.
Note: If the local AHJ requires a hard copy of your site
programming, use the QuickStart Configuration Utility to
retrieve the database from the panel and print the required
information.
Table 4-4: AutoLoop initial settings for SIGA devices
SIGA DevicePersonalityDescriptionDevice TypeEdit?
SIGA–IPHS, –PHS,
–PS, –IS
SIGA–HFS, HRS,
–IM
Single-stage pull
stations
Dual-stage pull
stations
SIGA–APS03Class B Active Non-LatchingMonitorFPP/CU
SIGA–(M)CC1(S)05Riser selectorCommon Alarm
SIGA–(M)CC207Dual riser selectorCommon Alarm
SIGA–(M)CR(R)08Dry contactNonsupervised
SIGA–(M)CT101Class B Alarm LatchingAlarmFPP/CU
SIGA–(M)CT201Class B Alarm LatchingAlarmFPP/CU
SIGA–DTS01Class B Alarm LatchingAlarmFPP/CU
SIGA–IO31Monitor Input/Output N.O.MonitorFPP/CU
SIGA–MAB00Class A Signal OutputMonitorFPP/CU
SIGA–UM00Class A Signal OutputMonitorFPP/CU
SIGA–MM103Class B Active Non-LatchingMonitorFPP/CU
SIGA–WTM02Class B Active Latching - DelayedAlarmFPP/CU
SIGA–(M)RM123Riser monitor - 24 VdcMonitorFPP/CU
noneSmoke detector settings as follows:
Sensitivity: Least
Verification: None
Prealarm: None
noneHeat detector settings not programmableAlarmFPP/CU
01Class B Alarm LatchingPullFPP/CU
01Class B Alarm LatchingMonitorFPP/CU
01Class B Alarm LatchingPullFPP/CU
03Class B Active Non-LatchingMonitorFPP/CU
01Class B Alarm LatchingAlarmFPP/CU
00not used
00not used
04Class B Active Latching.SupervisoryFPP/CU
AlarmFPP/CU
FPP/CU
Output
FPP/CU
Output
FPP/CU
Output
Note: If you use Signature devices from another system, the AutoLoop utility uses the attributes programmed from
the previous system as the initial settings for a general alarm system.
You can customize the system configuration, if
your requirements exceed that of the general
alarm system created using the AutoLearn and
AutoLoop utilities.
Before you can make any changes to the system
programming, you must log onto the system to
start an editing session.
The control panel has a watchdog timer that kicks
you out of an editing session after a period of
inactivity. If this happens, you will have to log in
again to continue.
After you finish customizing the system
configuration, save your changes, and then test
the system. After everything checks out then Save
and Sync to copy the database to the remote
annunciators.
What is it you want to doThis is how you do it
Make information about the installer available
on the CPU/Display
AutoLearn default: No text
WARNING: Entering Edit mode (choosing
Configure on the Program menu) disables the
control panel and leaves the premises unprotected
until you exit Edit mode.
To start an editing session:
1. Press Menu.
2. Choose Login then enter the password required
for Level 4 access.
3. Choose Program > Configure.
1. On the Configure menu, choose System > User
Labels.
2. Choose Facility Name, scan in the name of the
project, and then press Enter.
Set how long notification circuits must stay on
before pressing Alarm Silence can turn them
off or pressing Reset can reset the panel
AutoLearn default: None (no delay)
Set how long the panel must wait before
signaling an ac power failure
AutoLearn default: 0 (no delay)
3. Choose Inst Company, scan in the name of the
installing company, and then press Enter.
4. Choose Phone Number, scan in the telephone
number to call for service-related issues, and
then press Enter.
5. Choose Programmer, scan in the name of the
person that programmed the system, and then
press Enter.
6. Choose Exit.
1. On the Configure menu, choose System >
ALM/RST Inhib.
2. Select a time delay from the pick list then press
Enter.
1. On the Configure menu, choose System > AC
Power Dly.
2. Select a time delay from the pick list then press
Enter.
Enter location message text for a circuit on a
ZB16–4 or ZA8–2 card
Change the device type of a circuit on a ZB16–
4 or ZA8–2 card
Change the device type of the NAC circuits on
the SLIC
AutoLearn defaults: NAC1 device type is Visible;
NAC 2 device type is Common Alarm Output
Common Alarm Output circuits turn on
automatically when an input signals an alarm
event. Visible and Audible output circuits must be
placed in an Output Group in order to turn them
on. The AutoLearn utility automatically places
Visible circuits in an Output Group
1. On the Configure menu, choose Card, and then
enter the card address number.
2. Choose Text Message, scan in the text, and
then press Enter.
3. Choose Exit.
WARNING: Changing the device type of an input
circuit to a device type for an output circuit
removes the circuit from all input logic groups.
Changing the device type of an output circuit to a
device type for an input circuit removes the output
circuit from all output groups.
1. On the Configure menu, choose Card, and then
enter the card address number.
2. Choose Device Type, select the device type
from the pick list, and then press Enter.
3. Choose Exit.
WARNING: Changing an output circuit from a
Common Alarm Output device type to an Audible
device type does not automatically place the
Audible circuit in an Output Group. You must add
the Audible Circuit to the Output Group manually
or the Audible circuit will not turn on.
1. On the Configure menu, choose Cards > Edit
then enter the card address number.
3. Choose NAC 1 then choose the device type for
NAC 1.
4. Choose NAC 2 then choose the device type for
NAC 2.
5. Choose Exit > Save Edits, then wait while the
database is updated.
What is it you want to doThis is how you do it
Programming instructions
Change the performance class of the Signature
loop wiring
AutoLearn default: Wiring is Class B.
Enter location message text for an automatic
detector
Change the Alarm Sensitivity setting of a
smoke detector
1. On the Configure menu, choose Cards > Edit
then enter the card address number.
2. Choose Config Card.
3. Choose Wiring Class then choose how the loop
is wired to the SLIC.
4. Choose Exit > Save Edits, then wait while the
database is updated.
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the detector's serial
number.
3. Choose Message then scan in the text that you
want sent when the detector signals an event.
4. Choose Exit > Save Edits.
WARNING: Selection of the appropriate detector
technology and sensitivity settings should result
from a careful analysis of the hazard,
environmental conditions, and expected results.
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Detect > Edit > Enter Serial #
and then scan or enter the detector's serial
number.
3. Choose Sensitivity then choose the alarm
sensitivity setting you want the detector to use.
Refer to Table 4-5 and Table 4-6.
Enter location message text for a circuit on a
SIGA module
Change the device type for a circuit on a SIGA
module
Note: The device types shown in the pick lists vary
depending on the SIGA module. The device types
shown in the pick lists for the second address of a
dual-address module also vary depending on the
device type chosen for the first address.
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Module > Edit > Enter Serial #
and then scan or enter the serial number of the
module.
3. For a single-address module or the first
address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address
module, choose Device 2.
4.Choose Message, scan in the text, and then
press Enter.
5.Choose Exit.
1. On the Configure menu, choose Cards > Edit
and then enter the card address number of the
loop controller.
2. Choose Config Module > Edit > Enter Serial #
and then scan or enter the serial number of the
module.
3. For a single-address module or the first
address of a dual-address module, choose
Device 1.
— or —
For the second address of a dual-address
module, choose Device 2.
4. Choose Type, select a device type from the
pick list, and then press Enter.
AlarmDevice type assigned to IDC circuits that connect to automatic or a combination of automatic
and manual alarm-signal initiating devices. Alarm circuits signal Alarm Active events.
Alarm OutputDevice type assigned to IDC/NAC circuits that connect to notification appliances that you want
turned on automatically when the panel processes an alarm signal. Alarm Output circuits turn
off when you press Alarm Silence and turn on when you press Drill.
Audible
HeatDevice type assigned to IDC circuits that connect to automatic alarm-signal initiating devices
MonitorDevice type assigned to IDC circuits that connect to monitor-signal initiating devices that
OutputDevice type assigned to IDC/NAC circuits that supervise their output wiring for opens and
PullDevice type assigned to IDC circuits that connect to manually operated alarm-signal initiating
Supervisory
TamperDevice type assigned to IDC circuits that connect to supervisory-signal initiating devices that
Verified SmokeDevice type assigned to IDC circuits that connect to automatic alarm-signal initiating devices
Visible
Water Flow
Device type assigned to IDC/NAC circuits that connect to audible notification appliances
(horns). Audible circuits turn off when you press Alarm Silence and turn on when you press
Drill.
that detect a rise in the surrounding temperature. Heat circuits signal Heat Alarm events.
monitor the operation of ancillary system functions. Monitor circuits signal Monitor events.
shorts. Output circuits do not turn off when you press Alarm Silence or turn on when you press
Drill.
devices. Pull circuits signal Pull Station events.
Device type assigned to IDC circuits that connect to supervisory-signal initiating devices that
detect abnormal conditions that could make the sprinkler system inoperative or ineffective.
Supervisory circuits signal Supervisory events.
detect when someone tampers with a component of the sprinkler system. Tamper circuits signal
Tamper events.
that use alarm verification. Verified Smoke circuits signal Alarm Verify events when the fire
condition is first detected then Alarm Active events after verifying the fire condition exists.
Device type assigned to IDC/NAC circuits that connect to visual notification appliances
(strobes). Visible circuits do not turn off when you press Alarm Silence or turn on when you
press Drill unless programmed to do so.
Device type assigned to IDC circuits that connect to alarm-signal initiating devices that detect
water flowing through the sprinkler system. Water Flow circuits signal Waterflow events.
Before you begin, you should complete a Zone Programming
Worksheet (Figure 4-9) for each Zone. Keep a copy for your
records. You will also need to refer to the Output Group
programming worksheets.
To set up a Zone:
1. On the control panel, press Menu.
2. Choose Login then enter the password required for Level 4
access.
3. Choose Program > Configure > Zone.
4. To program a new Zone, choose Add, and then choose a
zone type (Alarm, Supervisory, or Monitor).
— or —
Choose Edit, select an existing zone from the pick list, and
then press Enter.
1. Choose Message, scan in the message text, and then
press Enter.
2. Choose Members, then for each device that comprises the
Zone:
Choose Device Address, then enter the member's device
number from the worksheet
— or —
Choose Enter Serial#, scan in or enter the member's serial
number.
3. Choose Review to verify which devices you added to the
Zone. If you added any devices in error, delete them.
4. Choose Output Group > Add, then select the Output group
from the pick list that contains the responses you want
activated, and then press Enter.
Repeat for each Output group you want to add.
5. Choose Review to verify which Output groups you added to
the Zone. If you added any Output groups in error, remove
them.
6 For coded systems, choose Coding, and then enter the