RSTi discrete input modules are available for a wide range of applications requiring DC voltages (5
VDC, 24 VDC, 48 VDC) and AC voltages (110 VAC, 220 VAC). The input modules are available in 4, 8
or 16 point density to optimize panel space.
Input Signal Delay< 0.5msec< 0.5msec3.0msec3.0msec3.0msec
Filtering Time
Trigger Voltage
Maximum On State Current
Connector Type
Internal Power Used
(5 VDC loading)
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
5 VDC Input,
4 points Negative Logic
5 VDC
(4.5 VDC to 5.5 VDC)
Typical 1.5 msec.
(software filtering)
On State: 2.4 VDC to
5.5 VDC
OFF State: 0.8 VDC
4.5 mA per point
at 5.5 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
5 VDC Input,
4 points Positive Logic
5 VDC
(4.5 VDC to 5.5 VDC)
Typical 1.5 msec.
(software filtering)
On State: 2.4 VDC to
5.5 VDC
OFF State: 0.8 VDC
4.5 mA per point
at 5.5 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input,
4 points Positive Logic
24 VDC
(11 VDC to 28.8 VDC)
Typical 1.5 msec. Typical 1.5 msec.
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input,
4 points Negative Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
48 VDC Input,
4 points Positive Logic
48 VDC
(34 VDC to 60 VDC)
ON State: 48 VDC
(34 VDC to 60 VDC)
OFF State: 10 VDC
4 mA per point
at 48 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
Automation & Control Systems
1.86
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
Discrete I/O Modules (Input)
RSTi discrete input modules are available for a wide range of applications requiring DC voltages (5
VDC, 24 VDC, 48 VDC) and AC voltages (110 VAC, 220 VAC). The input modules are available in 4, 8
or 16 point density to optimize panel space.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
48 VDC Input, 4 points
Negative Logic
48 VDC
(34 VDC to 60 VDC)
ON State: 48 VDC
(34 VDC to 60 VDC)
OFF State: 10 VDC
4 mA per point
at 48 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
48 VDC Input, 16 points
Positive Logic
48 VDC
(34 VDC to 60 VDC)
ON State: 48 VDC
(34 VDC to 60 VDC)
OFF State: 10 VDC
2.5 mA per point
at 60 VDC
Connector Type Hirose,
HIF3BA-20D-2.54DSA
45 mA @ 5.0 VDC
Maximum
12/24 VDC Input, 8
points Positive Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input, 8
points Negative Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input,
16 points Positive Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Connector Type Hirose,
HIF3BA-20D-2.54DSA
45 mA @ 5.0 VDC
Maximum
www.geautomation.com
Automation & Control Systems
1.87
RSTi Slice I/O
Process Automation Control Systems
Discrete I/O Modules (Input)
RSTi discrete input modules are available for a wide range of applications requiring DC voltages (5
VDC, 24 VDC, 48 VDC) and AC voltages (110 VAC, 220 VAC). The input modules are available in 4, 8
or 16 point density to optimize panel space.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 70
12/24 VDC Input,
16 points Negative Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Connector Type Hirose,
HIF3BA-20D-2.54DSA
45 mA @ 5.0 VDC
Maximum
110 VAC Input,
4 points (47 to 63Hz)
120 VAC
(85 VAC to 132 VAC)
ON State: 85 VAC to
132 VAC
OFF State: 60 VAC
8 mA per point
at 132 VAC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
240 VAC Input,
4 points (47 to 63Hz)
240 VAC
(170 VAC to 264 VAC)
ON State: 170 VAC to
264 VAC
OFF State: 130 VAC
12 mA per point
at 264 VAC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
Automation & Control Systems
1.88
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
Analog I/O Modules (Input)
RSTi analog input modules are available in a wide range of voltage and current signals. Analog input
modules are available in 12 bit or 14 bit resolution.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
12bit Input, 4 channels
12 bits:
4.88 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 20 mA,
12bit Input, 8 channels
12 bits:
4.88 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
60 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 20 mA,
14bit Input, 4 channels
14 bits:
1.22 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 4 to 20 mA,
12bit Input, 4 channels
12 bits:
3.9 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 4 to 20 mA,
12bit Input, 8 channels
12 bits:
3.9 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
60 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
www.geautomation.com
Automation & Control Systems
1.89
RSTi Slice I/O
Process Automation Control Systems
Analog I/O Modules (Input)
RSTi analog input modules are available in a wide range of voltage and current signals.
Analog input modules are available in 12 bit or 14 bit resolution.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
14bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 4 to 20 mA,
12bit Input, 4 channels
(connector type)
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Requires Sensor Connect
3M Mini-Clamp Plug,
37104 Series
Analog 0 to 10 VDC,
12bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 10 VDC,
12bit Input, 8 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
60 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 10 VDC,
14bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
170 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Automation & Control Systems
1.90
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
Analog I/O Modules (Input)
RSTi analog input modules are available in a wide range of voltage and current signals.
Analog input modules are available in 12 bit or 14 bit resolution.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
Analog -10 to 10 VDC,
12bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
170 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog -10 to 10 VDC,
14bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
170 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 5 VDC,
12bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
170 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 5 VDC,
14bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
170 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
www.geautomation.com
Automation & Control Systems
1.91
RSTi Slice I/O
Process Automation Control Systems
Discrete I/O Modules (Output)
RSTi discrete output modules are available for a wide range of applications requiring
DC voltages (5 VDC, 24 VDC, 48 VDC) and AC voltages (12 VAC, 125 VAC). The modules are
available in 4, 8 or 16 point density to optimize panel space. Relay output modules are also
available. The ST-2792 has an added feature of manual/automatic override.
Field Power Requirement5 VDC (4.5 VDC to 5.5 VDC) 5 VDC (4.5 VDC to 5.5 VDC) 24 VDC (11 VDC to 28.8 VDC)24 VDC (11 VDC to 28.8 VDC)
Power Dissipation5 mA @ 28.8 VDC Per Channel5 mA @ 28.8 VDC Per Channel
Connector Type
Internal Power Used
(5 VDC loading)
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
40 mA For 10ms, Repeatable
Every 1 Sec.
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
50 mA @ 5.0 VDC
Maximum
40 mA For 10ms, Repeatable
Every 1 Sec.
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
50 mA @ 5.0 VDC
Maximum
OFF to ON : Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
45 mA @ 5.0 VDC
Maximum
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
45 mA @ 5.0 VDC
Maximum
Automation & Control Systems
1.92
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
Discrete I/O Modules (Output)
RSTi discrete output modules are available for a wide range of applications requiring
DC voltages (5 VDC, 24 VDC, 48 VDC) and AC voltages (12 VAC, 125 VAC). The modules are
available in 4, 8 or 16 point density to optimize panel space. Relay output modules are also
available. The ST-2792 has an added feature of manual/automatic override.
Field Power Requirement24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)24 VDC (11 VDC to 28.8 VDC)24 VDC (11 VDC to 28.8 VDC)
Power Dissipation5 mA @ 28.8 VDC Per Channel5 mA @ 28.8 VDC Per Channel5 mA @ 28.8 VDC Per Channel5 mA @ 28.8 VDC Per Channel
Connector Type
Internal Power Used
(5 VDC loading)
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
45 mA @ 5.0 VDC
Maximum
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
45 mA @ 5.0 VDC
Maximum
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
45 mA @ 5.0 VDC
Maximum
OFF to ON : Max. 0.3ms
ON to OFF: Max. 0.3ms
Spring Clamp
Terminal Block
45 mA @ 5.0 VDC
Maximum
www.geautomation.com
Automation & Control Systems
1.93
RSTi Slice I/O
Process Automation Control Systems
Discrete I/O Modules (Output)
RSTi discrete output modules are available for a wide range of applications requiring
DC voltages (5 VDC, 24 VDC, 48 VDC) and AC voltages (12 VAC, 125 VAC). The modules are
available in 4, 8 or 16 point density to optimize panel space. Relay output modules are also
available. The ST-2792 has an added feature of manual/automatic override.
Power Dissipation5 mA @ 28.8 VDC Per Channel5 mA @ 28.8 VDC Per Channel3 mA @ 28.8 VDC Per Channel3 mA @ 28.8 VDC Per Channel
Connector Type
Internal Power Used
(5 VDC loading)
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
24 VDC (11 VDC to 28.8 VDC) 24 VDC (11 VDC to 28.8 VDC)24 VDC (11 VDC to 28.8 VDC)24 VDC (11 VDC to 28.8 VDC)
Spring Clamp Terminal BlockSpring Clamp Terminal BlockConnector Type Hirose,
60 mA @ 5.0 VDC
Maximum
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
45 mA @ 5.0 VDC
Maximum
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
HIF3BA-20D-2.54DSA
80 mA @ 5.0 VDC
Maximum
OFF to ON: Max. 0.3ms
ON to OFF: Max. 0.3ms
Connector Type Hirose,
HIF3BA-20D-2.54DSA
80 mA @ 5.0 VDC
Maximum
Automation & Control Systems
1.94
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
Discrete I/O Modules (Output)
RSTi discrete output modules are available for a wide range of applications requiring
DC voltages (5 VDC, 24 VDC, 48 VDC) and AC voltages (12 VAC, 125 VAC). The modules are
available in 4, 8 or 16 point density to optimize panel space. Relay output modules are also
available. The ST-2792 has an added feature of manual/automatic override.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 24 x 7099 x 12 x 70
0.8A @ 48 VDC
0.5A @ 110 VDC
2A @ 250 VAC
OFF to ON : Max. 10ms
ON to OFF: Max. 10ms
24 VDC, 240 VACNo Connection with Field Power
Spring Clamp
Terminal Block
65 mA @ 5.0 VDC
Maximum
2A @ 5~28.8 VDC
0.8A @ 48 VDC
0.5A @ 110 VDC
2A @ 250 VAC
OFF to ON: Max. 10ms
ON to OFF: Max. 10ms
Field Power passes though to
the next module
Spring Clamp
Terminal Block
130 mA @ 5.0 VDC
Maximum
2A @ 5~28.8 VDC
0.8A @ 48 VDC
0.5A @ 110 VDC
2A @ 250 VAC
OFF to ON: Max. 10ms
ON to OFF: Max. 10ms
No Connection with Field Power
Field Power passes though to
the next module
Spring Clamp
Terminal Block
150 mA @ 5.0 VDC
Maximum
0.5 Amp
40 Amp for 16 mSec. or
4 Amp for 30 Sec.
OFF to ON: Max. 3ms
ON to OFF: Max. 1/2 Cycle plus 3ms
120 VAC nominal Voltage Range:
12~125 VAC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
www.geautomation.com
Automation & Control Systems
1.95
RSTi Slice I/O
Process Automation Control Systems
Analog I/O Modules (Output)
RSTi analog output modules are available in a wide range of voltage and current signals. Specialty
analog modules are also available for manual over-ride and 0 to 1 Amp analog out.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
60 mA @ 5.0 VDC
Maximum
60 mA @ 5.0 VDC
Maximum
60 mA @ 5.0 VDC
Maximum
60 mA @ 5.0 VDC
Maximum
Automation & Control Systems
1.96
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
Analog I/O Modules (Output)
RSTi analog output modules are available in a wide range of voltage and current signals. Specialty
analog modules are also available for manual over-ride and 0 to 1 Amp analog out.
Dimensions (H x W x D) in mm99 x 12 x 7099 x 12 x 7099 x 12 x 7099 x 12 x 70
Mini-Clamp Plug, 37104 Series
AWG#20~22 available
40 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
155 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
60 mA @ 5.0 VDC
Maximum
Requires Sensor Connect 3M
Mini-Clamp Plug, 37104 Series
AWG#20~22 available
60 mA @ 5.0 VDC
Maximum
www.geautomation.com
Automation & Control Systems
1.97
RSTi Slice I/O
Process Automation Control Systems
Analog I/O Modules (Output)
RSTi analog output modules are available in a wide range of voltage and current signals. Specialty
analog modules are also available for manual over-ride and 0 to 1 Amp analog out.