GE Digital ST-1124, ST-1114, ST-1214, ST-1224, ST-1314 Specifications

...
RSTi Slice I/O
Process Automation Control Systems
RSTi discrete input modules are available for a wide range of applications requiring DC voltages (5 VDC, 24 VDC, 48 VDC) and AC voltages (110 VAC, 220 VAC). The input modules are available in 4, 8 or 16 point density to optimize panel space.
ST-1124 ST-1114 ST-1214 ST-1224 ST-1314
Product Name
Lifecycle Status Active Active Active Active Active
Module Type Discrete Input Discrete Input Discrete Input Discrete Input Discrete Input
Input Voltage Range
Number of Points 4 4 4 4 4
Points per Common 4 4 4 4 4
Input Impedance ~1.3K ohms ~1.3K ohms ~5.1K ohms ~5.1K ohms ~12K ohms
Input Signal Delay < 0.5msec < 0.5msec 3.0msec 3.0msec 3.0msec
Filtering Time
Trigger Voltage
Maximum On State Current
Connector Type
Internal Power Used (5 VDC loading)
Dimensions (H x W x D) in mm 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70
5 VDC Input,
4 points Negative Logic
5 VDC
(4.5 VDC to 5.5 VDC)
Typical 1.5 msec.
(software filtering)
On State: 2.4 VDC to
5.5 VDC
OFF State: 0.8 VDC
4.5 mA per point at 5.5 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
5 VDC Input,
4 points Positive Logic
5 VDC
(4.5 VDC to 5.5 VDC)
Typical 1.5 msec.
(software filtering)
On State: 2.4 VDC to
5.5 VDC
OFF State: 0.8 VDC
4.5 mA per point at 5.5 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input,
4 points Positive Logic
24 VDC
(11 VDC to 28.8 VDC)
Typical 1.5 msec. Typical 1.5 msec.
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input,
4 points Negative Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
48 VDC Input,
4 points Positive Logic
48 VDC
(34 VDC to 60 VDC)
ON State: 48 VDC
(34 VDC to 60 VDC)
OFF State: 10 VDC
4 mA per point
at 48 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
Automation & Control Systems
1.86
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
RSTi discrete input modules are available for a wide range of applications requiring DC voltages (5 VDC, 24 VDC, 48 VDC) and AC voltages (110 VAC, 220 VAC). The input modules are available in 4, 8 or 16 point density to optimize panel space.
ST-1324 ST-131F ST-1218 ST-1228 ST-121F
Product Name
Lifecycle Status Active Active Active Active Active
Module Type Discrete Input Discrete Input Discrete Input Discrete Input Discrete Input
Input Voltage Range
Number of Points 4 16 8 8 16
Points per Common 4 16 8 8 16
Input Impedance ~12K ohms ~12K ohms ~5.1K ohms ~5.1K ohms ~5.1K ohms
Input Signal Delay 3.0msec 3.0msec 3.0msec 3.0msec 3.0msec
Filtering Time Typical 1.5 msec. Typical 1.5 msec. Typical 1.5 msec. Typical 1.5 msec.
Trigger Voltage
Maximum On State Current
Connector Type
Internal Power Used (5 VDC loading)
Dimensions (H x W x D) in mm 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70
48 VDC Input, 4 points
Negative Logic
48 VDC
(34 VDC to 60 VDC)
ON State: 48 VDC
(34 VDC to 60 VDC)
OFF State: 10 VDC
4 mA per point
at 48 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
48 VDC Input, 16 points
Positive Logic
48 VDC
(34 VDC to 60 VDC)
ON State: 48 VDC
(34 VDC to 60 VDC)
OFF State: 10 VDC
2.5 mA per point
at 60 VDC
Connector Type Hirose,
HIF3BA-20D-2.54DSA
45 mA @ 5.0 VDC
Maximum
12/24 VDC Input, 8
points Positive Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input, 8
points Negative Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
12/24 VDC Input,
16 points Positive Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Connector Type Hirose,
HIF3BA-20D-2.54DSA
45 mA @ 5.0 VDC
Maximum
www.geautomation.com
Automation & Control Systems
1.87
RSTi Slice I/O
Process Automation Control Systems
RSTi discrete input modules are available for a wide range of applications requiring DC voltages (5 VDC, 24 VDC, 48 VDC) and AC voltages (110 VAC, 220 VAC). The input modules are available in 4, 8 or 16 point density to optimize panel space.
ST-122F ST-1804 ST-1904
Product Name
Lifecycle Status Active Active Active
Module Type Discrete Input Discrete Input Discrete Input
Input Voltage Range
Number of Points 16 4 4
Points per Common 16 4 4
Input Impedance ~5.1K ohms ~11K ohms ~22K ohms
Input Signal Delay 3.0msec 10.0msec 10.0msec
Filtering Time Typical 1.5 msec.
Trigger Voltage
Maximum On State Current
Connector Type
Internal Power Used (5 VDC loading)
Dimensions (H x W x D) in mm 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70
12/24 VDC Input,
16 points Negative Logic
24 VDC
(10.2 VDC to 28.8 VDC)
ON State: 10.2 to
28.8 VDC
OFF State: 5 VDC
6 mA per point
at 28.8 VDC
Connector Type Hirose,
HIF3BA-20D-2.54DSA
45 mA @ 5.0 VDC
Maximum
110 VAC Input,
4 points (47 to 63Hz)
120 VAC
(85 VAC to 132 VAC)
ON State: 85 VAC to
132 VAC
OFF State: 60 VAC
8 mA per point
at 132 VAC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
240 VAC Input,
4 points (47 to 63Hz)
240 VAC
(170 VAC to 264 VAC)
ON State: 170 VAC to
264 VAC
OFF State: 130 VAC
12 mA per point
at 264 VAC
Spring Clamp
Terminal Block
35 mA @ 5.0 VDC
Maximum
Automation & Control Systems
1.88
www.geautomation.com
Process Automation Control Systems
RSTi Slice I/O
Analog I/O Modules (Input)
RSTi analog input modules are available in a wide range of voltage and current signals. Analog input modules are available in 12 bit or 14 bit resolution.
ST-3114 ST-3118 ST-3134 ST-3214 ST-3218
Analog 0 to 20 mA,
Product Name
Lifecycle Status Active Active Active Active Active
Module Type Analog Input Analog Input Analog Input Analog Input Analog Input
Range 0 to 20 mA Range 0 to 20 mA Range 0 to 20 mA Range 4 to 20 mA Range 4 to 20 mA Range
Number of Points 4 8 4 4 8
Points per Common 4 8 4 4 8
Diagnostic Supported Open Wire if < 3 mA
Update Rate 4msec/All channels 4msec/All channels 4msec/All channels 4msec/All channels 4msec/All channels
Resolution
Accuracy
Input Impedance 120 ohms 120 ohms 120 ohms 120 ohms 120 ohms
Internal Power Used (5 VDC loading)
Connector Type
Dimensions (H x W x D) in mm 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70
12bit Input, 4 channels
12 bits:
4.88 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 20 mA,
12bit Input, 8 channels
12 bits:
4.88 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
60 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 20 mA,
14bit Input, 4 channels
14 bits:
1.22 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 4 to 20 mA,
12bit Input, 4 channels
12 bits:
3.9 microAmp/bit
±0.1% Full Scale @ 25°C ±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 4 to 20 mA,
12bit Input, 8 channels
12 bits:
3.9 microAmp/bit
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
60 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
www.geautomation.com
Automation & Control Systems
1.89
RSTi Slice I/O
Process Automation Control Systems
Analog I/O Modules (Input)
RSTi analog input modules are available in a wide range of voltage and current signals. Analog input modules are available in 12 bit or 14 bit resolution.
ST-3234 ST-3274 ST-3424 ST-3428 ST-3444
Analog 4 to 20 mA,
Product Name
Lifecycle Status Active Active Active Active Active
Module Type Analog Input Analog Input Analog Input Analog Input Analog Input
Range 4 to 20 mA Range 4 to 20 mA Range 0 to 10 VDC 0 to 10 VDC 0 to 10 VDC
Number of Points 4 4 4 8 4
Points per Common 4 4 4 8 4
Diagnostic Supported Open Wire if < 3 mA Open Wire if < 3 mA
Update Rate 4msec/All channels 4msec/All channels 4msec/All channels 4msec/All channels 4msec/All channels
Resolution 14 bits: 0.9 microAmp/bit 12 bits: 3.9 microAmp/bit 12 bits: 2.44 mV/bit 12 bits: 2.44 mV/bit 14 bits: 0.6 mV/bit
Accuracy
Input Impedance 120 ohms 120 ohms 500K ohms 500K ohms 500K ohms
Internal Power Used (5 VDC loading)
Connector Type
Dimensions (H x W x D) in mm 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70 99 x 12 x 70
14bit Input, 4 channels
±0.1% Full Scale @ 25°C ±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 4 to 20 mA,
12bit Input, 4 channels
(connector type)
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Requires Sensor Connect
3M Mini-Clamp Plug,
37104 Series
Analog 0 to 10 VDC,
12bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
165 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 10 VDC,
12bit Input, 8 channels
±0.1% Full Scale @ 25°C ±0.3% Full Scale @ 0°C,
60°C
60 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Analog 0 to 10 VDC,
14bit Input, 4 channels
±0.1% Full Scale @ 25°C
±0.3% Full Scale @ 0°C,
60°C
170 mA @ 5.0 VDC
Maximum
Spring Clamp
Terminal Block
Automation & Control Systems