Process Automation Control Systems
PACSystems RX3i Controller
Analog I/O Modules (Input)
GE offers easy-to-use analog modules and HART analog modules for control processes such as
flow, temperature and pressure.
IC694ALG232 IC694ALG233 IC695ALG600
PACSystems RX3i
Analog Input, Voltage, High Density
(16 Channel) 16 Bit with
Product Name
Lifecycle Status Active Active Active
Module Type
Backplane Support No Backplane Restrictions No Backplane Restrictions Universal Backplane Only. Uses PCI Bus.
Number of Slots Module
Occupies on Backplane
Range
HART Support
advanced diagnostics
Analog Input Analog Input Universal Analog Input
1 1 1
-10 V to +10 V, 0 to 10 V 0-20 mA, 4-20 mA,
N/A N/A N/A
PACSystemsRX3i
Analog Input, Current, High Density
(16 Channel) 16 Bit with
advanced diagnostics
4-20 mA Enhanced
PACSystems RX3i Analog Input.
Configurable per channel for Current,
Voltage, RTD, Thermocouple and
Resistive. High Density (8 Channel)
Requires High Density Terminal Block
(IC694TBB032 or IC694TBS032). Cold
Junction Compensation are available
for Thermocouple configurations
(IC695ACC600 contains 2 CJCs)
Voltage: +50 mV, +150 mV, 0–5 V, 1–5 V,
0–10 V, +10 V; Current: 0–20 mA, 4–20 mA,
+20 mA; Thermocouple Inputs: B, C, E, J, K, N, R,
S, T; RTD Inputs: PT 385 / 3916, N 618 / 672, NiFe
518, CU 426: Resistance Inputs: 0 to 250 / 500 /
1000 / 2000 / 3000 / 4000 Ohms
Channel-to-Channel
Isolation
Number of Channels 16 Single Ended, 8 Differential 16 8
Single Ended: 5 ms for all channels
Update Rate
Resolution
Accuracy
Input Impedance
Input Filter Response
Notch Filter N/A N/A Yes
Diagnostics
Internal Power Used
External Power Requirement
Connector Type
Differential: 3 ms all channels
16 bit; ±10 V, 0.3125 mV, 1 LSB;
0-10 V, 0.3125 mV, 1 LSB
500K Ohms (single-ended mode)
1 MegaOhms (differential mode)
23 Hz (single-ended mode)
38 Hz (differential mode)
Under Range/Over Range,
Positive/Negative Rate of Change, High,
High-High, Low, Low-Low
112 mA (maximum) @ +5 VDC 120 mA @ +5 VDC 400 mA @ 5 V; 350 mA @ 3.3 V
110 mA (maximum) +24 VDC supply
connected to TB1 on IC695CHSxxx
Terminal Block (20 screws),
No No Two Groups of Four
6 ms all channels 10ms per Channel; 4 Channels = 40ms (1KHz
16 bit; 0-20 mA, 0.625 µA/bit;
4-20 mA, 0.5 µA/bit; 4-20 mA
Enhanced, 0.5 µA/bit
0.25% at 25ºC (77ºF) 0.25% at 25ºC (77ºF) Calibrated Accuracy at 25°C.
250 ohms Current 249 ohms ±1%
23 Hz Configurable: 8Hz, 12Hz, 16Hz,
Under Range/Over Range, Open Wire,
Positive/Negative Rate of Change, High,
High-High, Low, Low-Low
65 mA @ 24 VDC N/A
included with module.
Terminal Block (20 screws),
included with module.
filter) 127ms per Channel 4 Channels = 508ms
(8Hz filter) Channels that are disabled
are not scanned, shortening scan time.
11 to 16 bits, depending on configured
range and A/D filter frequency
Better than 0.1% of range (except
10 ohm CU RTD) Accuracy depends
on A/D filter, data format, input noise,
and ambient temperature.
40Hz, 200Hz, 1000Hz
Open Wire, Short Circuit,
Positive/Negative Rate of Change,
High, High-High, Low, Low-Low
IC694TBBx32 or IC694TBSx32.
Sold Separately.
www.geautomation.com
Automation & Control Systems
1.15
PACSystems RX3i Controller
Process Automation Control Systems
Analog I/O Modules (Input)
GE offers easy-to-use analog modules and HART analog modules for control processes such as
flow, temperature and pressure.
IC695ALG608 IC695ALG616 IC695ALG628
PACSystems RX3i Analog Input.
Configurable per channel for Current
or Voltage. High Density (8 Channel)
Product Name
Lifecycle Status Active Active Active
Module Type
Backplane Support Universal Backplane Only. Uses PCI Bus. Universal Backplane Only. Uses PCI Bus. Universal Backplane Only. Uses PCI Bus.
Number of Slots Module
Occupies on Backplane
Range
Requires High Density Terminal Block
(IC694TBB032 or IC694TBS032).
Analog Input Analog Input Analog Input with HART Communications
1 1 1
Current: 0 to 20 mA, 4 to 20 mA, ±20 mA;
Voltage: ±10 V, 0 to 10 V, ±5 V, 0 to 5 V, 1 to 5 V
PACSystems RX3i Analog Input.
Configurable per channel for Current
or Voltage. High Density (16 Channel)
Requires High Density Terminal Block
(IC694TBB032 or IC694TBS032).
Current: 0 to 20 mA, 4 to 20 mA, ±20 mA;
Voltage: ±10 V, 0 to 10 V, ±5 V, 0 to 5 V, 1 to 5 V
PACSystems RX3i Analog Input
with HART Communications.
Configurable per channel for Current
or Voltage. High Density (8 Channel)
Requires High Density Terminal Block
(IC694TBB032 or IC694TBS032).
Current: 0 to 20 mA, 4 to 20 mA, ±20 mA;
Voltage: ±10 V, 0 to 10 V, ±5 V, 0 to 5 V, 1 to 5 V
HART Support
Channel-to-Channel
Isolation
Number of Channels 8 16 8
All 8 Channels at 5 msec @ 500Hz.
Update Rate
Resolution
Accuracy
Input Impedance
Input Filter Response
Notch Filter Yes Yes Yes
Diagnostics
Internal Power Used
External Power Requirement
Connector Type
Performance is dependent on filtering.
32-bit IEEE floating point or 16-bit integer
(in 32-bit field) input data format
Calibrated Accuracy @ 13°C – 33°C with
8 Hz, 12 Hz and 16 Hz filter; 0 to 10 V,
±10 V input types: 10 mV0 to 5 V, 1 to 5 V,
±5 V input types: 5 mV0 to 20 mA,
4 to 20 mA, ±20 mA input types: 20 µA
Configurable: 8Hz, 12Hz, 16Hz,
Open wire, short circuit, positive/negative rate
of change, High, High-High, Low, Low-Low
450 mA @ 5 V; 600 mA @ 3.3 V 450 mA @ 5 V; 600 mA @ 3.3 V 450 mA @ 5 V; 600 mA @ 3.3 V
IC694TBBx32, IC694TBSx32 or IC694TBC032
N/A N/A Get HART Device Information (Function 1)
One Group of Eight One Group of Sixteen One Group of Eight
All 16 Channels at 9 msec @ 500Hz.
Performance is dependent on filtering.
32-bit IEEE floating point or 16-bit integer
(in 32-bit field) input data format
Calibrated Accuracy @ 13°C – 33°C with
8 Hz, 12 Hz and 16 Hz filter; 0 to 10 V,
±10 V input types: 10 mV0 to 5 V, 1 to 5 V,
±5 V input types: 5 mV0 to 20 mA,
4 to 20 mA, ±20 mA input types: 20 µA
Current 249 ohms ±1% Current 249 ohms ±1% Current 249 ohms ±1%
40Hz, 200Hz, 500Hz
N/A N/A N/A
Sold Separately.
Configurable: 8Hz, 12Hz, 16Hz,
40Hz, 200Hz, 500Hz
Open wire, short circuit, positive/negative rate
of change, High, High-High, Low, Low-Low
IC694TBBx32, IC694TBSx32 or IC694TBC032
Sold Separately.
Simplified HART Pass-Thru Command (Function 2)
Enterprise HART Pass-Thru Command (Function 3)
All 8 Channels at 5 msec @ 500Hz.
Performance is dependent on filtering
and HART enabled channels could add
6 to 8 seconds.
Selectable per channel
Calibrated Accuracy @ 13°C – 33°C
with 8 Hz, 12 Hz and 16 Hz filter;
0 to 10 V, ±10 V input types: 10 mV0 to
5 V, 1 to 5 V, ±5 V input types: 5 mV0 to 20 mA,
4 to 20 mA, ±20 mA input types: 20 µA
Configurable: 8Hz, 12Hz, 16Hz,
40Hz, 200Hz, 500Hz
Open wire, short circuit, positive/negative rate
of change, High, High-High, Low, Low-Low
IC694TBBx32 or IC694TBSx32.
Sold Separately.
Automation & Control Systems
1.16