GE Digital EPXMBE001 Data sheet

RSTI-EP Slice I/O
Ethernet Ports
Power
Supply
LED
PWR, SF, BF, MT, L/A X1,
and L/A X2 LEDs
Door for Micro USB Port
Modbus Network Adapter
The EPXMBE001 network adapter is a Modbus TCP participant developed according to IEC 61158. The network adapter is the head module for the RSTi-EP communication bus, to which up to 64 active RSTi-EP modules can be connected. The Modbus TCP network adapter has two Ethernet ports and an integrated switch.
The network adapter can be accessed with a system-independent web server application via the USB service interface or the Ethernet. Thus, all information, such as diagnostics, status values and parameters, can be read and all connected modules can be simulated or forced.
The station's main power supply is integrated in the network adapter. Power is supplied via two 4-pole connectors, separated into the input and output current paths.
Caution, the RSTi-EP station is usually installed on a horizontally positioned DIN rail. Installation on vertically positioned DIN rails is also possible. However, the heat dissipation is reduced such that the derating values change (refer to the section, Thermal Derating.
Modules should to be allowed to de-energize for a minimum 10 seconds after power down, prior to starting any maintenance activity. The network adapter cannot be hot-swapped.
Refer to the RSTi-EP Slice I/O User Manual (GFK-2958) for additional information.
Refer to the RSTi-EP Power Supply Reference Guide, a software utility available on PME V9.00, for detailed power-feed requirements.
Module Features
Supports up to 64 active RSTi-EP modules Spring-style technology for ease of wiring DIN rail mounted Double-click installation for positive indication of correct installation Built-in Web Server for diagnostic information and firmware update
through Ethernet and micro USB port
Option of fixed or DHCP IP address configuration Support for daisy-chain/line, star topologies
GFK-2966B Modbus September 2016
®
Network Adapter Module EPXMBE001
© 2015 General Electric Company. All Rights Reserved.
*
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective
2 RSTi-EP Slice I/O Modbus Network Adapter
Module
Description
EPXMBS001
RSTi-EP Slice I/O Modbus TCP Network Adapter
EPXMBE001
System data
Connection
2 x RJ-45
Fieldbus protocol
Modbus TCP
Process image
Input data width
max. 8 kBytes
Parameter data
max. 1024 kBytes
Diagnostic data
max. 1024 kBytes
Number of modules
max. 64 active
Configuration interface
Micro USB 2.0
Transfer rate
Fieldbus
10 Mbps/100 Mbps
RTSi-EP system bus
Max. 48 Mbps
Supply
Supply voltage for system and inputs
20.4V – 28.8V
Supply voltage for outputs
20.4V – 28.8V
Max. feed-in current for input modules
10 A
Max. feed-in current for output modules
10 A
Current consumption from system current path I
SYS
112 mA
Connection data
Type of connection
Spring style
Conductor cross-section
Single-wired, fine-wired
0.14 – 1.5 mm2 (AWG 26 – 16)
General data
Operating temperature
-20°C to +60°C (-4 °F to +140 °F)
Storage temperature
-40°C to +85°C (-40 °F to +185 °F)
Air humidity (operation/transport)
5% to 95%, noncondensing as per IEC 61131-2
Width
52 mm (2.05 in)
Depth
76 mm (2.99 in)
Height
120 mm (4.72 in)
Weight
223 g (7.87 oz)
GFK-2966B
Ordering Information
Specifications
RSTi-EP Slice I/O Modbus Network Adapter 3
LED
Indication
LED State/Description
PWR
Power LED
Green: Supply voltage connected
SF
System Fault
Red: Configuration error, or error in the network adapter, or error in a module, or there is a new diagnostic report
Red flashing: Station in Force mode
BF
Bus fault
Red: No connection to the fieldbus Red flashing: Configuration error, no connection to the control unit, or error in
the parameter set
MT
Maintenance Required
Yellow: Error on the system bus or fieldbus
L/A X1
Connection/Active
Green / Yellow†: Connection established between port 1 of the network adapter and another field device
Green flashing / Yellow flashing†: Data being exchanged on port 1
L/A X2
Connection/Active
Green: Connection established between port 2 of the network adapter and another field device Green flashing: Data being exchanged on port 2
Green: Transfer rate 100 MBit/s
Yellow: Transfer rate 10 MBit/s
LED
EPXMBE001
Power
Supply
Green: Supply voltage > 18 V DC Red: At least one current path < 18 V
3.1
Green: Input current path supply voltage > 18 V DC
3.2
Red: Input current path supply voltage < 18 V DC
3.3 3.4
Red: Internal fuse defective
4.1
Green: Output current path supply voltage > 18 V DC
4.2
Red: Output current path supply voltage < 18 V DC
4.3 4.4
Red: Internal fuse defective
GFK-2966B
LEDs
LED Status Indicators
LED Indicators