RSTI-EP Slice I/O
Module Status
LED
Channel Status
LED
GE provides several RSTi-EP specialty modules, which can be used to meet specific
Digital pulse width modulation modules can control from 0.5A to 2A
Specialty Modules
EP-5111, EP-5112, EP-5212, EP-5261, EP-5311, EP-5422, EP-5442
needs in your system. Each module has a Module Status LED and each channel has
a LED for visual indication of connectivity.
The counter module EP-5111 can read one square-wave signal (1 channel) (for
example, from an incremental encoder) with a maximum input frequency of 100
kHz. The 32-bit counter can count up or down within a predetermined range of
values.
Specialty Module
The digital counter module EP-5112 can read two square-wave signals (2 channels)
(for example, from an incremental encoder) with a maximum input frequency of 100
kHz. Depending on the operating mode, both 32-bit counters can count up or down
independent of each other in a preset range of values. The counters can be
controlled via software by setting the appropriate control word.
The digital counter module EP-5212 can read frequency of one square-wave signal
(1 channel) from one or two external sensors with a maximum input frequency of
100 kHz. Frequencys to be counted are applied to channel CH0 and/or channel CH1,
the measurement will be started via control word 1 and 2 respectively. Measuring
cycles can be defined in μs. The longer the measuring cycle the more exactly the
measurement.
The digital pulse width modulation modules EP-5422 and EP-5442 are used for the
control of small motors with current requirements of 0.5 A up to 2 A which can also
be used for the control of valve flaps. The switching frequencies are adjustable up to
40 kHz and, in addition to this, the push/pull output levels can be used for motor
activation; for example: change of rotation direction. As with all modules of the RSTiEP system, the characteristics are outstanding – from the modular design and the
interchangeable electronics to the removable plug-in terminal strip.
The RSTi-EP station is usually installed on a horizontally positioned DIN rail.
Installation on vertically positioned DIN rails is also possible.
Modules should to be allowed to de-energize for a minimum 10 seconds after
power down, prior to starting any maintenance activity.
Refer to the RSTi-EP Slice I/O User Manual (GFK-2958) for additional information.
Refer to the RSTi-EP Power Supply Reference Guide, a software utility available on
PME V9.00, for detailed power-feed requirements.
Module Features
Spring style technology for ease of wiring
DIN rail mounted
Double-click installation for positive indication of correct installation
Compatible for 2 and 3 wire connection
32-bit counter, 24 V DC
Counting frequency 100 kHz max (A/B channel, 1/2/4- times sampling or pulse
and direction, invertible)
Gate input (hardware gate, HW gate), reset input, digital output controlled by an
internal comparator
Alarm and diagnostic function with μs time stamp
Digitally adjustable input filter to suppress interferences(17 filter frequencies
gradually adjustable between 3 Hz and 187 kHz)
SSI Encoder Interface Serial Communication module
© 2015 - 2016 General Electric Company.
*
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective
owners.
2 RSTi-EP Slice I/O Specialty Modules
Process, parameter, and diagnostic data depend on the network adapter used.
500 V DC between the current paths
Incremental encoders and other input characteristics for
sensor types 1 and 3 are in accordance with EN 61131-2
Max. input current per
channel
Reverse polarity protection
Individual channel
diagnostics
Status, alarm, diagnostics
Reverse polarity protection
Individual channel
diagnosis
GFK-2962B
Ordering Information
Module Description
EP-5111 1 Channel High Speed Counter, AB 100 kHz 1 DO 24VDC, 0.5A
EP-5112 2 Channel High Speed Counter, AB 100 kHz
EP-5212 2 Channel Frequency Measurement, 100 kHz
EP-5422 2 Channels PWM Output, Positive Logic, 24VDC, 2.0 A
EP-5442 2 Channels PWM Output, Positive Logic, 24VDC, 0.5 A
EP-5261
EP-5311 SSI Encoder, BCD or Gray-Code Format, 5/24 VDC
1 Channel Serial Communications, 232, 422, 485
Specifications
Type
Input filter Filter time adjustable from 0,01 to 1 ms
--
and 187 kHz (333 ms and
5 μs)
3.5 mA
Yes Yes No
Mode of operation
Pulse and direction / AB mode
with 1-, 2-, 4-times sampling
Yes -- --
mode with 1-, 2-, 4-times
Pulse rising edge
RSTi-EP Slice I/O Specialty Modules 3
Current consumption from
system current path I
Current consumption from
output current path Iin
35 mA plus output current for
the digital output
35 mA plus sensor supply
current
-20°C to +60°C (-4 °F to +140 °F)
-40°C to +85°C (-40 °F to +185 °F)
Air humidity
(operation/transport)
Process, parameter and diagnostic data depend on the network
RSTi-EP I/O communication bus
RS-232, RS-485, RS-422, parameterizable
300 – 115200 Bps, parameterizable
Current of power supply output
DIN 66020, DIN 66259, EIA-RS232C, CCITT V.24/V.28
Individual channel diagnosis
Current consumption from system current path I
Current consumption from input current path Iin
For additional general data, refer to the section, General Technical Data for I/O Modules.
GFK-2962B
SYS
5% to 95%, noncondensing as per IEC 61131-2
8 mA
35 mA
Adapter used (refer to the table in the section, Order and
Arrangement of the Modules)
SYS
For public disclosure
4 RSTi-EP Slice I/O Specialty Modules
Process, parameter and diagnostic data depend on the network
RSTi-EP I/O communication bus
SSI (Differential RS-422)
500 mA (24 V DC) / 400 mA (5 V DC)
Reverse polarity protection
Individual channel diagnosis
max. 320 m (1049.( ft) at 125 kHz; shielded
Current consumption from system current path
8 mA
Current consumption from input current path Iin
25 mA + sensor supply current
For additional general data, refer to the section, General Technical Data for I/O Modules.
GFK-2962B
Data
Adapter used (refer to the table in the section, Order and Arrangement
of the Modules)
I
,
SYS
RSTi-EP Slice I/O Specialty Modules 5
Process, parameter, and diagnostic data depend on the network adapter used.
25 μs t o 175 ms (40 kHz to 6 Hz)
Resistive load
(min. 47 Ω)
Resistive load
(min. 12 Ω)
2-wire, 3-wire, 3-wire + FE
max. 2 A per plug, total max. 4 A
max. 2 A per plug, total max. 8 A
0–100 % PN-switching or P-switching, adjustable
Response time of the
protective circuit
Individual channel diagnosis
system current path I
SYS
output current path I
OUT
-20°C to +60°C (-4 °F to +140 °F)
-40°C to +85°C (-40 °F to +185 °F)
GFK-2962B
PN output stage
Max. output current
Switching frequency
Current consumption from
Current consumption from
Air humidity
static, 6 Hz to 40 kHz
static, 6 Hz to 40 kHz
< 100 μs
8 mA
40 mA + Load
5% to 95%, noncondensing as per IEC 61131-2
6 Hz to 40 kHz
6 Hz to 40 kHz