GE Digital EP-3164, EP-3264, EP-3124, EP-3368, EP-3468, EP-3704, EP-380 Data sheet
Specifications and Main Features
Frequently Asked Questions
User Manual
RSTI-EP Slice I/O
Module Status
LED
Channel Status
LEDs
Digital Input Connector
Ground
24 V DC
FE
GE provides a range of RSTi-EP analog input modules with 4 or 8 inputs and up
Analog Input Modules
GFK-2960A `EP-3164, EP-3264, EP-3124, EP-3368, EP-3468
December 2015 EP-3704, EP-3804
to 16-bit resolution. The measurement range is defined by parameterization
with an accuracy of 0.1% FSR with the exception of EP3124, which 0.25% FSR.
The parameters for the measurement range can be individually set for each
channel.
The EP-3704 module can detect up to 4 analog resistance temperature
detectors. The resolution is 16 bit per channel.
The EP-3804 module can detect up to 4 analog thermocouple sensors or
voltages between ± 15 mV and ± 2 V.
The wiring connectors on each module are color coded for ease of wiring.
Refer to the section,
Each module features a type plate, which includes identification information,
the key technical specifications, and a block diagram. In addition, a QR code
allows for direct online access to the associated documentation. The software
for reading the QR code must support inverted QR codes.
Markers are available as accessories for labelling equipment. Each I/O module
can be labelled using the markers to ensure clear identification when
replacing individual modules or electronic units.
A green Module Status LED indicates there is communication on the system
bus. In addition, each channel has its own status LED.
Field Wiring for additional information.
The RSTi-EP station is usually installed on a horizontally positioned DIN rail.
Installation on vertically positioned DIN rails is also possible.
Modules should to be allowed to de-energize for a minimum 10 seconds after
power down, prior to starting any maintenance activity.
Refer to the RSTi-EP Slice I/O Module User Manual (GFK-2958) for additional
information.
Refer to the RSTi-EP Power Supply Reference Guide, a software utility available
on PME V9.00, for detailed power-feed requirements.
Module Features
Spring style technology for ease of wiring
DIN rail mounted
Double-click installation for positive indication of correct installation
Up to 8 analog inputs
Supports indirect firmware update through network adapter using Web