GE Digital EP-2214, EP-2614, EP-2634, EP-2218, EP-225F Data sheet

RSTI-EP Slice I/O
Module Status
Channel Status
LEDs
Digital Input Connector
Ground
24 V DC
FE
GE provides a range of RSTi-EP digital output modules with 4, 8 or 16 outputs, which
GFK-2959B Digital Output Modules December 2015 EP-2214, EP-2614, EP-2634, EP-2218, EP-225F
Relay Output Module EP-2714
Solid-state Relay Output Module EP-2814
are primarily used for the incorporation of decentralized actuators.
All outputs are designed for DC-13 discrete outputs according to DIN EN 60947-5-1 and IEC 61131-2 specifications. Frequencies of up to 1 kHz are possible except for relay and SSR output modules. Protection of the outputs ensures maximum system safety (Relay and SSR modules do not support short circuit protection). This consists of an automatic restart following a short-circuit.
The digital relay output module EP-2714 can control up to 4 discrete outputs, each with a maximum of 6 A. Each connector features a potential-free changeover contact. The relay coils are supplied with power from the output current path (I
The solid-state relay output module EP-2814 uses four semiconductor switches to control up to 4 discrete outputs, each with a maximum of 0.5 A at 255 V AC. The switching characteristics of the semiconductor switch have it as being closed when the voltage crosses zero and open when the current crosses zero. Each connector features a potential-free NO (Normally Open) contact.
The wiring connectors on each module are color coded for ease of wiring. Refer to the section, Field Wiring for additional information.
Each module features a type plate, which includes identification information, the key technical specifications, and a block diagram. In addition, a QR code allows for direct online access to the associated documentation. The software for reading the QR code must support inverted QR codes.
Markers are available as accessories for labelling equipment. Each I/O module can be labelled using the markers to ensure clear identification when replacing individual modules or electronic units.
A green Module Status LED indicates there is communication on the system bus. Additionally, there are Yellow LEDs for each input to indicate when it is active. Refer to the section, LEDs for additional information.
The RSTi-EP station is usually installed on a horizontally positioned DIN rail. Installation on vertically positioned DIN rails is also possible.
Modules should to be allowed to de-energize for a minimum 10 seconds after power down, prior to starting any maintenance activity.
Refer to the RSTi-EP Slice I/O Module User Manual (GFK-2958) for additional information.
OUT
).
Digital Output Module
© 2015 General Electric Company. All Rights Reserved.
*
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective
owners.
Refer to the RSTi-EP Power Supply Reference Guide, a software utility available on PME V9.00, for detailed power-feed requirements.

Module Features

Positive Logic EP-2634 also supports Negative Logic Spring style technology for ease of wiring DIN rail mounted Double-click installation for positive indication of correct installation Up to 16 outputs Compatible with type-1 and type-3 sensor inputs Supports hot insertion and extraction
2 RSTi-EP Slice I/O Digital Output Modules
EP-2214
Digital Output, 4 Points, Positive Logic 24VDC, 0.5A, 2,3, or 4 Wire
EP-2218
Digital Output, 8 Points, Positive Logic, 24VDC, 0.5A, 2 Wire
EP-2614
Digital Output, 4 Points, Positive Logic 24VDC, 2.0A, 2,3, or 4 Wire
EP-225F
Digital Output, 16 Points, Positive Logic, 24VDC, 0.5A, 1 Wire
EP-2634
Digital Output, 4 Points, Positive/Negative Logic 24VDC, 2.0A, 2,3, or 4 Wire
EP-2714
Digital Relay Output, 4 Points, Positive Logic, 24 - 220 VDC/VAC, 6A, 2 Wire
EP-2814
Digital Output, 4 Points, Positive Logic, 230 VAC, 1A
EP-2214
EP-2614
EP-2634
EP-2218
EP-225F
System Data
Data
Process, parameter and diagnostic data depend on the network adapter used.
Interface
RSTi-EP system bus
System bus transfer rate
48 Mbps
Outputs
Number
4 4 4 8 16
P- or N-Logic
Type of load
ohmic, inductive, lamp load
Response time
low » high max. 100 μs; high » low max. 250 μs
Max. output current
per channel
0.5 A
2 A
2 A
0.5 A
0.5 A
per module
2 A
8 A
8 A
4 A
8 A
(inductive)
Switching frequency
Resistive load (min. 47 Ω)
1 kHz
1 kHz with suitable free-wheeling diode
Lamp load (12 W)
1 kHz
Actuator connection
2-wire, 3-wire, 3-wire + FE
2-wire
1-wire
Actuator supply
max. 2 A per plug, total max. 8 A
--
--
Short-circuit-proof
Yes
Protective circuit
Constant current with thermal switch-off and automatic restart
current limiting circuit
Module diagnostics
Yes
diagnostics
Yes
Yes
GFK-2959B

Ordering Information

Module Description

Specifications

Type
Breaking energy
Inductive load (DC 13)
Response time of the
Individual channel
P-Logic Switchable
150 mJ per channel
0.2 Hz without free-wheeling diode
< 100 μs
No
P-Logic
Reactionless
Can be used with EP-19xx
-- Yes Yes Yes
Yes Yes -- --
RSTi-EP Slice I/O Digital output Modules 3
EP-2214
EP-2614
EP-2634
EP-2218
EP-225F
Supply
20.4V – 28.8V
system current path I
SYS
output current path I
OUT
General data
Operating temperature
-20°C to +60°C (-4 °F to +140 °F)
Storage temperature
-40°C to +85°C (-40 °F to +185 °F)
(operation/transport)
Width
Depth
Height
Weight
EP-2714
EP-2814
System Data
Data
Interface
System bus transfer rate
48 Mbps
Outputs
Number
Type
Material for power and data contacts
Switching characteristic
Opening when the current crosses zero
Response time
Minimum switching current
Maximum switching current
--
1 A per channel
--
4 A per module
Max. output current
5 A at 60°C (140 °F) /
6 A at 55°C (131 °F) per channel
20 A at 60°C (140 °F) /
24 A at 55°C (131 °F) per module
--
25 mA
Switching frequency
max. 5 Hz
up to 20 Hz
Short-circuit-proof
No
external fuse
Protective circuit
External fusing with 6 A prescribed
--
switching current
255 V AC, UL: 277 V AC,
DC corresponding to the derating curve
Reactionless
Yes
GFK-2959B
Supply voltage
Current consumption from
8 mA
Current consumption from
Air humidity
20 mA + load 25 mA + load 20 mA + load 35 mA + load 25 mA + load
5% to 95%, noncondensing as per IEC 61131-2
11.5 mm (0.45 in)
76 mm (2.99 in)
120 mm (4.72 in)
86 g (3.03 oz) 86 g (3.03 oz) 86 g (3.03 oz) 86 g (3.03 oz) 83 g (2.93 oz)
Process, parameter, and diagnostic data depend on the network adapter used.
RSTi-EP system bus
4
Relay from - C SSR / triac
Ni-Au, 3 μm --
--
Closing when the voltage crosses zero,
Holding current
Defined trip behaviour of the prescribed
Service life with AC-15 load and 1-A
Max. switching voltage
20 ms 10 ms
-- 50 mA per channel
--
--
-- 1 A super quick-acting
> 300.000 switching cycles --
255 V AC, UL: 277 AC
4 RSTi-EP Slice I/O Digital Output Modules
EP-2714
EP-2814
Diagnosis
Yes
No
Supply
20.4V – 28.8V
current path I
SYS
current path I
General data Operating temperature
-20°C to +60°C (-4 °F to +140 °F)
Storage temperature
-40°C to +85°C (-40 °F to +185 °F)
Air humidity (operation/transport)
5% to 95%, noncondensing as per IEC 61131-2
11.5 mm (0.45 in)
76 mm (2.99 in)
Height
120 mm (4.72 in)
Weight
83 g (2.93 oz)
Product
I
IIN
I
IS
IL
EP-2214
8 mA
--
20 mA
--
x
EP-2614
8 mA
--
25 mA
--
x
EP-2714
8 mA
--
20 mA
--
--
EP-2814
11 mA
--
--
--
--
EP-2634
8 mA
--
20 mA
--
x
EP-2218
8 mA
--
35 mA
--
--
EP-225F
8 mA
--
25 mA x --
I
x
Current consumption from the system current path
Must be included when calculating the power supply
GFK-2959B
Module diagnosis
Individual channel diagnostics
Supply voltage
Current consumption from system
8 mA 11 mA
Current consumption from output
OUT
Width Depth
SYS
SYS
I
Power consumption from input current path
IN
Power consumption from output current path
I
OUT
Current demand of the connected sensors
I
S
Current demand of the connected actuators
I
L
20 mA --
Current Demand for Digital Output Modules
OUT
Loading...