RSTI-EP Slice I/O
Module Status
LED
Channel Status
LEDs
Digital Input Connector
Ground
24 V DC
FE
GE provides a range of RSTi-EP digital input modules with 4, 8 or 16 inputs,
Digital Input Modules
EP-1214, EP-1218, EP-1318, EP-125F, EP-1804
Digital Input Module with Time Stamp EP-12F4
which are primarily used to receive binary control signals from sensors,
transmitters, switches or proximity switches. Their flexible design allows them
to meet your demands with reserve potential.
All modules are fully compliant with IEC 61131-2. They can be switched on the
input side with type-1 and type-3 sensors in accordance with IEC 61131-2.
The wiring connectors on each module are color coded for ease of wiring.
Refer to the section, Field Wiring for additional information.
The time stamp module EP-12F4 can detect up to 4 binary control signals and
provide them with a time stamp (resolution 1 μs). Depending on the
configuration of the module, up to 5 or 15 time stamp entries can be
evaluated.
Each module features a type plate, which includes identification information,
the key technical specifications, and a block diagram. In addition, a QR code
allows for direct online access to the associated documentation. The software
for reading the QR code must support inverted QR codes.
Markers are available as accessories for labelling equipment. Each I/O module
can be labelled using the markers to ensure clear identification when
replacing individual modules or electronic units.
A green Module Status LED indicates there is communication on the system
bus. Additionally, there are Yellow LEDs for each input to indicate when it is
active. Refer to the section,
LEDs for additional information.
Digital Input Module
© 2015-2016 General Electric Company. All Rights Reserved.
*
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective
owners.
The RSTi-EP station is usually installed on a horizontally positioned DIN rail.
Installation on vertically positioned DIN rails is also possible.
Modules should to be allowed to de-energize for a minimum 10 seconds after
power down, prior to starting any maintenance activity.
Refer to the RSTi-EP Slice I/O Module User Manual (GFK-2958) for additional
information.
Refer to the RSTi-EP Power Supply Reference Guide, a software utility available
on PME V9.00, for detailed power-feed requirements.
Module Features
Positive Logic
Spring style technology for ease of wiring
DIN rail mounted
Double-click installation for positive indication of correct installation
Up to 16 sensor inputs
Compatible with type-1 and type-3 sensor inputs per IEC 61131-2
Time stamping available
Supports hot insertion and extraction
2 RSTi-EP Slice I/O Digital Input Modules
Process, parameter and diagnostic data depend on the
network adapter used.
Max. input current per
channel
Reverse polarity
protection
Individual channel
diagnosis
Current consumption
from input current path I
IN
-20°C to +60°C (-4 °F to +140 °F)
-40°C to +85°C (-40 °F to +185 °F)
RSTi-EP Slice I/O Digital Input Module with Time Stamp
Ordering Information
Module Description
EP-1214 Digital Input, 4 Points, Positive Logic 24VDC, 2,3, or 4-Wire
EP-1218 Digital Input, 8 Points, Positive Logic, 24VDC 2-Wire
EP-1318 Digital Input, 8 Points, Positive Logic, 24VDC 3-Wire
EP-125F Digital Input, 16 Points, Positive Logic, 24VDC, 1-Wire
EP-1804 Digital Input, 4 Points, 110/230 VAC (65 – 277 VAC), 2 Wire, Isolated
EP-12F4 Digital Input, 4 Points, Positive Logic 24VDC, 2,3, or 4-Wire, Time stamp
Specifications
Data
Sensor types
Input filter Input delay adjustable from 0 to 40 ms
Type 1 and Type 3 sensors as per IEC 61131-2
- - - -
Sensor supply
Sensor connection
max. 2 A per
plug, total
2-wire, 3-
wire, 3-wire +
max. 15 mA
per channel
2-wire
max. 2 A per
plug, total
2-wire, 3-
wire
- -
- - No
from system current path
- -
†
Input delay
3 ms
No Yes No
1-wire
adjustable
from 0 to
†
3 mA
2-wire, 3-
wire, 3-wire +
Yes
8 mA
for Type 3
sensors as per
Input delay
10 ms
-
2-wire
18 mA 30 mA 30 mA 52 mA 18 mA No
RSTi-EP Slice I/O Digital Input Modules 3
Air humidity
(operation/transport)
†
When used with PROFIBUS-DP network adapter it is limited to 20 ms
Current consumption from the system current path
Must be included when calculating the power supply
RSTi-EP Slice I/O Digital Input Module with Time Stamp
- -
87 g (3.07 oz)
85 g (2.99
5% to 95%, noncondensing as per IEC 61131-2
83 g (2.93
87 g (3.07 oz)
89 g (3.07 oz) 87 g (3.07 oz)
Current Demand for Digital Input Modules
SYS
I
Power consumption from input current path
IN
Power consumption from output current path
I
OUT
Current demand of the connected sensors
I
S
Current demand of the connected actuators
I
L