VersaMax Control
Process Automation Control Systems
Power Supplies
VersaMax Power Supply modules snap onto any VersaMax CPU or Network Interface Unit or onto a
power supply booster carrier. Each power supply can be used as the main power source for
modules in the I/O station, or as a source of supplemental power for larger I/O applications.
IC200PWR102 IC200PWR201 IC200PWR202 IC200PWB001
120/240 VAC Power Supply
with Expanded 3.3 VDC
Product Name
Lifecycle Status Active Active Active Active
Input Voltage 120/240 VAC 9.6-15 VDC, 12 VDC nominal 9.6-15 VDC, 12 VDC nominal N/A
Output Voltage 5 VDC, 3.3 VDC 5 VDC, 3.3 VDC 5 VDC, 3.3 VDC N/A
Extended Power Yes No Yes N/A
Input Power 27 VA 11 W 11 W N/A
Isolated Power N/A No No N/A
Holdup Time 20 ms 10 ms 10 ms N/A
Inrush Current N/A 25 A at 12 VDC; 30 A at 15 VDC 25 A at 12 VDC; 30 A at 15 VDC N/A
Protection
Total Output Current 1.5 A maximum 1.5 A maximum 1.5 A maximum N/A
3.3V Output Current 1.0 A maximum 0.25 A maximum 1.0 A maximum N/A
5V Output Current
Dimensions (W x H x D)
Short circuit, overload Short circuit, overload,
1.5 A minus the 3.3 V
current used, maximum
49 mm (1.93 in) x
133.4 mm (5.25 in) x
39 mm (1.54 in),
not including the
height of the carrier
or the DIN-rail
12 VDC Power Supply 12 VDC Power Supply
with Expanded 3.3 VDC
Short circuit, overload,
reverse polarity
1.5 A minus the 3.3 V
current used, maximum
49 mm (1.93 in) x
133.4 mm (5.25 in) x
39 mm (1.54 in),
not including the
height of the carrier
or the DIN-rail
reverse polarity
1.5 A minus the 3.3 V
current used, maximum
49 mm (1.93 in) x
133.4 mm (5.25 in) x
39 mm (1.54 in),
not including the
height of the carrier
or the DIN-rail
VersaMax Power Supply
Booster Carrier.
Supplies power to all
modules to the right
of booster. Requires
power supply.
N/A
N/A
66.8 mm (2.63 in) x
133.4 mm (5.25 in) x
70 mm (2.75 in),
not including the
height of DIN-rail
Automation & Control Systems
1.122