PAC8000 Railbus Isolator
The PAC8000 Railbus Isolator is required when using any 2/1 modules in a node. The unit provides
galvanic isolation between those modules interfacing to Intrinsic Safe field wiring on the 2/1 side
of the isolator and those with conventional wiring on the 2/2 side. The unit mounts on its dedicated
Railbus Isolator Carrier 8725-CA-RB.
Note: System Power is not passed from one side of the Railbus Isolator to the other, so System
Power on the 2/1 side must be supplied by IS System Power Supplies.
8922-RB-IS
Product Name Railbus Isolator
Lifecycle Status Active
Module Addressing 1-32 or 1-64
Railbus Connectors
System Power (12 V)*
Weight (g) 345
Mounting
Dimensions (W x D x H) in mm 42 x 160 x 110
Common PAC8000 Specifications See Section xx for System Specifications
*Note: DC power for the Railbus Isolator is required from both 2/2 and 2/1 sides of the node.
Female In
Male Out
2/2 side 50 mA max.
2/1 side 60 mA max.
DIN-rail (T): 7.5 x 35 mm
DIN-rail (T): 15 x 35 mm
DIN-rail (G)
Flat Panel
Safety and Distributed Control
Automation & Control Systems
5.72
www.geautomation.com