GE Digital 8751-CA-NS Specifications

Safety and Distributed Control
PAC8000 SafetyNet
ELFD Controller Carrier
The ELFD Controller Carrier provides a mounting platform for up to two SafetyNet Controllers (8851-LC-MT). It can also accommodate a Power Supply Monitor module (8410-NS-PS) which can monitor the health of up to two 8913-PS-AC, four 8914-PS-AC power supplies and the 12V supply to Intrinsically Safe Modules (when these are used). For each Controller there is a serial port connector and a manually operated ““Change State” button. The Carrier also provides terminals that are used when earth leakage fault detection is required.
8751-CA-NS
Product Name ELFD Controller Carrier - Terminals for earth leakage fault detection
Lifecycle Status Active
SafetyNet Controller (x2) 8851-LC-MT
Power Supply Monitor Module 8410-NS-PS
Electrical Connections
Railbus Connector male out
Serial Port Connectors 9-pin, D-type (female) (x2)
Power Fail Connections screw terminals (x7 pairs)
Ground Connection M4 screw terminal (x1)
BFP0V Connection M4 screw terminal (x1)
Earth Leakage Fault Detection Connections
System Power connections (Note: this does not provide power to the SafetyNet Controllers)
Dimensions (W x D) mm 200 x 253 (footprint)
Height (mm) 28 (top of circuit board) 55 (overall)
Weight (kg) 1.43 (approx.)
Mounting Methods flat panel (4 fixings)
Two “change state” buttons, one for each SafetyNet Controller, are
User Controls
Master Change to standby if current standby is healthy
Standby Change to offline state
Backup Re-synchronize and return to standby
provided on the carrier. The state change depends upon the controller
state before the button is pressed. See below for effects.
screw terminals (1 pair)
6-Pin (male)
www.geautomation.com
Automation & Control Systems
5.65