GE Digital 8515-BI-PN, 8516-BI-PN, 8502-BI-DP, 8505-BI-MB, 8507-BI-DP Specifications

...
Safety and Distributed Control
PAC8000 PROFINET Bus Interface Modules
Newly Released PAC8000 PROFINET BIMs allow connection of PAC8000 I/O to remote hosts via PROFINET.
8515-BI-PN 8516-BI-PN
Lifecycle Status Active* Active*
Number of I/O Modules 14 14
Protocol Supported PROFINET PROFINET
BIM Redundancy No (Yes from 2013) No (Yes from 2013)
Baud Rate 10-100Mbaud 10-100Mbaud
LAN Redundancy Ring Ring
LAN Connector Type RJ45 Fiber Optic
Maximum Bus Length 2 – 2,000 m (Full Duplex) 2 – 2,000 m (Full Duplex)
Data Frame Size (bytes) N/A N/A
Input Data (max.) N/A N/A
Output Data (max.) N/A N/A
Message Response Time
LED Indicators 11 11
Address Setting One (1) IP and Three (3) MAC One (1) IP and Three (3) MAC
Configuration Tool Machine Edition V7.5 Machine Edition V7.5
HART Data
Bus Isolation
System Power (12 V) 4.5 Watts (5.5 Wats Max) 6.0 Watts (7.2 Watts Max)
Dimensions (L x W x H) 160.3mm (6.3”) x 128.3mm (5.1”) x 47.8mm (1.9”) 160.3mm (6.3”) x 128.3mm (5.1”) x 47.8mm (1.9”)
Module Weight (g)
BIM Carrier 8752-CA-NS 8752-CA-NS
Common PAC8000 Specifications See Section xx for System Specifications See Section xx for System Specifications
Process Variables and Status
(released in 2013)
*PROFINET BIMs will only support a select and growing number of I/O Modules. Please contact GE before quoting.
Process Variables and Status
(released in 2013)
Currently supports modules:
8103-AI-TX 8117-DO-DC 8116-DO-AC
8104-AO-IP 8111-DI-AC 8118-DO-AC
8109-DI-DC 8112-DI-AC 8119-VI-05
8115-DO-DC 8113-DI-AC
8110-DI-DC 8114-DI-AC
Automation & Control Systems
5.62
www.geautomation.com
Safety and Distributed Control
PAC8000 SafetyNet
PAC8000 Traditional Bus Interface Modules
When used as remote I/O, PAC8000 nodes use a Bus Interface Module (BIM) to communicate with the host controller via a local area network (LAN). Different BIMs can be chosen to operate with specific LAN protocols. BIMs are supplied in a number of different package styles according to their function, and each mounts on a dedicated BIM Carrier.
8502-BI-DP 8505-BI-MB 8507-BI-DP 8521-EB-MT
Product Name PROFIBUS DP BIM Modbus BIM PROFIBUS DP BIM Ethernet BIM
Lifecycle Status Active Active Active Active
Number of I/O Modules 24 32 24 64
Protocol Supported
BIM Redundancy No No Yes Yes
Baud Rate 9.6kb to 6 Mbaud 1.2 to 115.2 kbaud 9.6kb to 12 Mbaud 10- 100 Mbaud
LAN Redundancy No Yes No Yes
LAN Connector Type RS-485 RS485/422 RS-485 RJ45
Maximum Bus Length
Data Frame Size (bytes) Config. up to 244 N/A Config. up to 480 N/A
Input Data (max.) 244 bytes N/A 240 bytes N/A
Output Data (max.) 244 bytes N/A 480 bytes N/A
Message Response Time <4 ms
LED Indicators
Address Setting
Configuration Tool
HART Data Process Variables and Status Process Variables and Status
Bus Isolation 500 V 500 V 500 V 1500 V
System Power (12 V)
Module Width (mm) 63 63 42 69
Module Weight (g) 350 320 500 1350
BIM Carrier
Common PAC8000 Specifications
PROFIBUS-DP V1
(EN 50170)
100 meters to 1.2Km
depending on baud rate
Power
Fault Comm LAN A Config
Railbus
Software (by I/O Configurator)
Switch (by 8510-NS–MO)
GSD File or I/O Configurator
8455–SW-CF
420 mA typ.
520 mA max.
8715-CA-BI
8718-CA-NS
See Section 14 for
System Specifications
Note: If a PROFIBUS BIM is configured over the PROFIBUS using the GSD file, a reduced set of configuration parameters is available. If the 8455-SW-CF is
used, more comprehensive options are available. The instruction manual for the BIM explains the configuration options. Modbus and PROFIBUS-DP BIMs do not support the following modules: 8129-IO-DC, 8132-AI-UN, 8133-HI-TX, 8139-SH-DC, 8140-DO-AC, and
8142-DO-DC.
Modbus RTU
(Revision G)
15 meters
Power
Fault
LAN A and LAN B
Config
Railbus
Software (by I/O Configurator)
Switch (by 8510-NS–MO)
I/O Configurator
8455–SW-CF
260 mA typ.
300 mA max.
8715-CA-BI
8718-CA-NS
See Section 14 for
System Specifications
PROFIBUS-DP V1
(EN 50170)
100 meters to 1.2Km
depending on baud rate
Power
Master
Healthy
Fault
Failsafe
Red Comm
Railbus
Link LAN
PROFIBUS
Hardware setting on carrier Software (eBIM Workbench)
GSD File or I/O Configurator
8455–SW-CF
Process Variables and Status
(from Q4 2012)
420 mA typ.
520 mA max.
8701-CA-BI 8750-CA-NS
See Section 14 for
System Specifications
Modbus TCP/IP
Power
Master
Healthy
Fault
Failsafe
LAN A
LAN B COM 1 COM 2
Safe Mode
I/O Com
Workbench
8459-EB-MT
Process Variables and Status
15 mA (12 V Controller Power
400 mA typ. 500 mA max.)
See Section 14 for
System Specifications
www.geautomation.com
Automation & Control Systems
5.63