GE Appliances RAK148F2, RAK164F2 User Manual

Page 1
OWNER’S MANUAL &
INSTALLATION INSTRUCTIONS
RAK148F2 RAK164F2
SAFETY INFORMATION .............................. 2
OVERVIEW............................................................... 3
INSTALLATION ............................................. 4–7
CONFIGURATION MODE ........................ 8, 9
OPERATING FUNCTIONS ....................... 10
TESTING THERMOSTAT ...................11–12
TROUBLESHOOTING ................................... 13
WARRANTY ......................................................... 16
Digital Non-Programmable
LIA319 9-7757 05-16 GEA
Page 2
IMPORTANT SAFETY INFORMATION
READ ALL INSTRUCTIONS BEFORE USING
WARNING
FIRE AND SHOCK HAZARD
• Always turn off power at the main power supply before installing, cleaning or removing the thermostat. Failure to do so could result in electrical shock hazard.
• Do not use on voltages over 30 VAC. Higher voltages will damage the thermostat and could cause shock or fire hazard.
NOTICE
• All wiring must conform to local and national electrical and building codes.
• Use this thermostat only as described in this manual.
Specifications.
Electrical rating: • 24 VAC (18–30 VAC)
1 amp maximum per terminal
4 amp maximum total load
Operating temperature range: 40°F–99°F (4°C–37°C) Temperature set range: 60°F–85°F (15°C–29°C) Accuracy: ± 1°F (± 0.5°C) System configurations:
RAK148F2: 2-stage heat (heat pump/resistance heat), 1-stage cool, 2-speed fan
RAK164F2: 1-stage heat (resistance heat), 1-stage cool, 2-speed fan
Terminations: R, C, W, Y, GH, GL, B (RAK148F2);
Wiring:
2
R, C, W, Y, GH, GL (RAK164F2)
Maximum wiring length is 66ft (20 meters) for
AWG18 Maximum wiring length is 60ft (18 meters) for AWG20
Page 3
INTRODUCTION OVERVIEW
THERMOSTAT CONTROL
Display Up/Down Buttons
Cool Off
Heat
Function Switch
Fan Auto/On Switch
PARTS DIAGRAM
Display
Mounting
Hole
Configuration
Buttons
COOL OFF
Function
Switch
RESETRIGHTLEFT
HEAT
Auto
On
Up/Down Buttons
B GH GL Y W C
R
AUTO ON
Fan Auto/On
Switch
Low High
Fan Speed Switch
LOW
HIGH
Fan Speed
High/Low
Wiring
Channel
Mounting
Hole
3
Page 4
INSTALLATION INSTRUCTIONS
WARNING
ELECTRICAL SHOCK HAZARD—Turn off power by unplugging the unit or by removing the fuse or switching the appropriate circuit breaker to the OFF position before removing the existing thermostat. Failure to do so could result in risk of electric shock.
PACKAGE CONTENTS/ TOOLS REQUIRED
Package includes: Thermostat on base, thermostat
cover, wiring labels, screws and wall anchors.
Tools needed: 'ULOOZLWKƎELWKDPPHUVFUHZGULYHU
and putty.
4
Page 5
INSTALLATION INSTRUCTIONS
TO REMOVE EXISTING THERMOSTAT
1. Turn off power to heating and cooling system by
removing the f use or switching off the appropriate circuit breaker.
2. Remove cover of old thermostat. This should expose the wires.
3. Label the existing wires with the enclosed wire labels before removing wires.
4. After labeling wires, remove wires from wire terminals.
5. Remove existing thermostat base from wall.
6. Refer to the following section for instructions on how
to install this thermostat.
5
Page 6
INSTALLATION INSTRUCTIONS
TO INSTALL THERMOSTAT
IMPORTANT: Thermostat installation must
conform to local and national building and electrical codes and ordinances.
Note: Mount the thermostat about five feet above the
floor. Do not mount the thermostat on an outside wall, in direct sunlight, behind a door or in an area affected by a vent or duct.
1. Turn off power to the heating and cooling system
by removing the fuse or switching off the appropriate circuit breaker.
2. Move the Function switch on the thermostat to Off.
3. Remove the cover by inserting and twisting a coin or
screwdriver in the slots on the top of the thermostat.
4. Put thermostat base against the wall where you plan
to mount it. Make sure wires will feed through the wire opening in the base of the thermostat.
5. With the base level, mark the placement of the
mounting holes.
6. Set thermostat base and cover away from working
area.
7.8VLQJDƎGULOOELWGULOOKROHVLQWKHORFDWLRQV\RX
have marked for mounting.
8. Use a hammer to tap supplied anchors in mounting
holes.
9. Align thermostat base with mounting holes and feed
the control wires through the wire opening.
6
Page 7
INSTALLATION INSTRUCTIONS
TO INSTALL THERMOSTAT (cont.)
10. Seal hole for wires behind thermostat with non-
flammable insulation or putty, or use a wall plate obtainable from a local hardware or home building store.
11. Use supplied screws to mount thermostat base to wall.
12. Insert stripped, labeled wires in matching wire terminals by pressing on the corresponding terminal contact. See the “Wiring Diagrams” section of this manual.
NOTICE
Make sure exposed portion of wires does not touch other wires.
13. Gently tug wire to be sure of proper connection. Double check that each wire is connected to the proper terminal.
14. Replace cover on thermostat by snapping it in place.
15. Plug the unit in or turn on power to the system at the main service panel.
16. Test thermostat operation as described in the “Testing the Thermostat” section.
7
Page 8
WIRING DIAGRAMS
Table 1: Terminals for six wires 1-stage heat/1­stage cool system (RAK164F2 only)
GL GH Y W C R
-HIGH
-LOW
8
Page 9
WIRING DIAGRAMS
Table 2: Terminals for seven wires 2-stage heat/1-stage cool system (RAK148F2 only)
B GH Y W C RGL
-HIGH
-LOW
9
Page 10
CONFIGURATION MODE
The configuration mode is used to set the RAK148F2 and RAK164F2 to match the heating/cooling system. These thermostats function wi th u p t o 2- s tage heat pump systems (RAK148F2 only).
To configure the RAK148F2 and RAK164F2, perform the following steps:
Note: Operation being set will blink in the display.
1. Slide the Function switch to the OFF position.
2. Remove the thermostat’s front cover.
3. To enter the configuration mode, simultaneously hold
the LEFT and RIGHT buttons in for 6 seconds while the thermostat is in OFF mode. (See diagram on page 3.)
4. Once in the configuration mode, press the button to change settings within each screen.
- Press the RIGHT button to advance to the next screen.
- Press the LEFT button to return to the previous screen.
NOTE: To exit configuration mode at any time, slide the
Function switch to Heat or Cool.
Configuration Mode Settings
The setup screens for Configuration Mode are as follows:
1. Temperature Scale (F or C)—Choose Fahrenheit or Celsius.
<
Press the
to select.
Press the RIGHT button to advance to
the next screen.
NOTE: Default factory setting is Fahrenheit.
2. Temperature Differential—Stage 1— (1–9°F) (1–5°C)
Set the number of degrees between the “setpoint” temperature and the “turn on” temperature for first stage.
Press the Press the RIGHT button to advance to the next screen. Note: Default factory setting is 2°F/1°C for each stage.
or > button
<
or > button to set differential value.
10
<
or >
Page 11
3. Temperature Differential—Stage 2 (1–9°F/1–5°C) RAK148F2 only
Set the number of degrees between when stage 1 turns on and stage 2 turns on.
Press the Press the RIGHT button to advance to the next screen. Note: Default factory setting is 2°F/1°C for each stage.
4. Minimum Cool Setpoint (60, 64, 66, 68, 70, 72, 74, 76°F) (15, 17, 19, 20, 21, 22, 23, 24°C)
Adjust to control the minimum Cool set
temperature allowed.
Press the Press the RIGHT button to advance to the next screen. Note: Default factory setting is 60°F/15° C.
5. Maximum Heat Setpoint (65, 70, 72, 74, 76, 78, 80, 85°F) (18, 21, 22, 23, 24, 26, 27, 29°C)
Adjust to control the maximum Heat set
temperature allowed.
Press the Press the RIGHT button to advance to the next screen.
Note: Default factory setting is 85°F/29°C.
6. Room temperature offset (+9°F to –9°F) (+5°C to –5°C)
Adjust to calibrate displayed room
temperature to match actual room temperature.
Press the Press the RIGHT button to advance to the next screen. Note: Default factory setting is 0°F/0°C.
<
or > button to set differential value.
<
or > button to select.
<
or > button to select.
<
or > button to select.
11
Page 12
OPERATING FUNCTIONS
Off
• In this mode, the thermostat will not turn on the heating or
cooling devices (manual fan can operate).
Off is also used to access Configuration mode.
Cool
• In this mode, the thermostat
controls the cooling system.
• Press the
set the desired temperature.
Heat
• In this mode, the thermostat
controls the heating system.
• Press the
to set the desired temperature.
<
or > button to
<
or > button
12
Page 13
TESTING THE THERMOSTAT
Once the thermostat is installed, it should be thoroughly tested.
NOTICE
Do not use air conditioning beyond the simple test when the outdoor temperature is below 50 degrees. This can damage the air conditioning system.
Note: Before testing the thermostat, move the Fan Auto/On switch to the
Auto position. Fan Test
1. With Function switch set to Off, slide Fan Speed switch to High, and slide Fan Auto/On switch to On position.
2. Indoor fan turns on in high
speed.
3. Slide Fan Speed switch to Low.
4. Indoor fan slows to low speed.
5. Slide Fan Auto/On switch to Auto position.
6. Indoor fan turns off.
Cool Test
1. Slide Function switch to Cool position. Cool mode screen is displayed.
2. Adjust set temperature so it is 5 degrees below room temperature.
3. Air conditioning should come on within a few seconds.
4. Adjust the set temperature so it is 2 degrees above the
room temperature and the A/C should turn off. Note: There is a 3 minute time delay and a 3 minute minimum run time for the compressor when it turns on/off. (On some models, the fan may also have a minimum run time/ off time delay).
Low High
13
Page 14
TESTING THE THERMOSTAT
Heat Test
1. Slide Function switch to Heat position. Heat mode screen is displayed.
2. Adjust set temperature so it is 5 degrees above room temperature.
3. Heat should come on within a few seconds.
4. Adjust the set temperature so it is 2 degrees below the
room temperature and the heat should turn off. Note: There is a 3 minute time delay and a 3 minute minimum run time for the compressor when it turns on/off. (On some models, the fan may also have a minimum run time/ off time delay).
14
Page 15
TROUBLESHOOTING TIPS
Problem Solution
No Display Check for 24 VAC; display is blank
System fan does not come on properly
All thermostat but­tons are inoperative
Thermostat turns on and off too fre­quently
Fan runs continu­ously
Room temperature is not correct
Compressor doesn’t run or turn off im­mediately when changing function or setting
Fan doesn’t run or turn off immedi­ately when changing function or setting
Problem not listed above
when 24 VAC is not present Verify that wiring is correct.
Verify that 24 VAC is present; unit will not operate when 24 VAC is not present.
Adjust temperature differential
VHH&RQ¿JXUDWLRQ0RGH6HWWLQJ
Temperature Differential, Stage 1 and Stage 2 section).
Check Fan Auto/On switch. If set to ON position, fan will run.
Verify that wall hole is plugged with
SXWW\RULQVXODWLRQWRSUHYHQWDLUÀRZ
from the wall cavity. Adjust Tempera-
WXUH2IIVHWVHH&RQ¿JXUDWLRQ0RGH
- Room temperature offset section). There is a 3 minute time delay and
a 3 minute minimum run time for the compressor when it turns on/off.
This is normal. On some models, the fan may have a minimum run time/off time delay.
Press the Reset button once to reset the thermostat and restore all factory settings.
15
Page 16
THERMOSTAT WARRANTY
Staple your receipt here.
Proof of the original purchase date is
needed to validate the warranty.
For The Period Of: GE Appliances Will Replace:
One Year Full Replacement of the thermostat which fails
From the date of the due to a defect in materials or workmanship. original purchase
What GE Appliances Will Not Cover:
Ŷ Service trips to your location. Ŷ Improper installation. If you have an installation problem, contact
your installer. You are responsible for providing adequate electrical connections to the product.
Ŷ Failure of the product resulting from modifications to the product or
due to unreasonable use, including failure to provide reasonable and necessary maintenance.
Ŷ In commercial locations, labor necessary to move the unit, after it has
been initially installed, to a location where it is accessible for service by an individual technician; or, if th e instructions included in this manual have been disregarded.
Ŷ Replacement of location fuses or the resetting of circuit breakers. Ŷ Damage to the product caused by improper power supply voltage,
accident, fire, floods or acts of God.
Ŷ Incidental or consequential damage caused by possible defects with
this thermostat.
EXCLUSION OF IMPLIED WARRANTIES—Your sole and exclusive remedy is product exchange as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.
This warranty is extended to the original purchaser and any succeeding owner for products purchased for use within the USA and Canada. In Alaska, the warranty excludes the cost of shipping or service calls to your site.
Some states or provinces do not allow the exclusion or limitation of incidental or consequential damages. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province. To know what your legal rights are, consult your local, state or provincial consumer affairs office or your state’s Attorney General.
16
Warrantor: GE Appliances, Louisville, KY 40225
Loading...