No part of this publication may be copied or published by means of printing, photocopying, microfilm
or otherwise without prior written consent of
•
GEA Refrigeration North America, Inc.
herein after called manufacturer. This restriction
also applies to the corresponding drawings and diagrams.
LEGAL NOTICE
This product information is a part of the documentation for the GEA Omni™ scope of delivery and
serves as product presentation and customer advisory service. It contains important information and
technical data regarding the product.
The product information makes the technical, product related and commercial information available to
the customer in detail before the sale of the product.
This product information serves as a support and
technical advisory service for our partners and customers as well as for the marketing team. Apart from
serving as the medium for transfer of product knowhow, it also forms the basis for product demonstrations, the organization and conduction of technical
seminars as well as the technical support at trade
fairs.
This product information should be supplemented
with the information about the industrial safety and
health related regulations at the site of installation of
the product. The regulations vary form place to place
as a result of the statutory regulations applicable at
the site of installation of the product and are therefore have not been considered in this product information.
In addition to this product information and the accident prevention regulations applicable for the
respective country and area where the product is
used, the accepted technical regulations for safe and
professional work must also be observed.
This product information has been written in good
faith. However, the manufacturer cannot be held
responsible for any errors that this document may
contain or for their consequences.
Instruction Manual | GEA Omni™
Control panel
The manufacturer reserves the right to make technical changes during the course of further development of the GEA Omni™ shown in this product information.
Illustrations and drawings in this product information
are simplified representations. As a result of the
improvements and changes, it is possible that the
illustrations do not exactly match the current development status. The technical data and dimensions
are subject to change and claims can be made on
the basis of them.
2GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
SYMBOLS USED IN THIS MANUAL
Danger!
Stands for an immediate danger which
leads to heavy physical injuries or to
the death.
Warning!
Stands for a possibly dangerous situation which leads to heavy physical
injuries or to the death.
Caution!
Stands for a possibly dangerous situation which could lead to light physical
injuries or to damages to property.
Hint!
Stands for an important tip whose
attention is important for the designated use and function of the device.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.20163
Instruction Manual | GEA Omni™
Control panel
4GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
TABLE OF CONTENTS
1SAFETY AND CONFORMITY 13
1.1Safety Instructions 13
1.2Safety note concerning the connection of the GEA Omni™ with the starter panel 14
1.3Conformity - CE marking (Europe) 15
1.4Conformity - UL marking (USA, Canada) 15
2USER INTERFACE 16
2.1Menu Navigation 17
2.2Status Bar 19
2.2.1Logging In 19
2.2.2Current State 21
2.2.3Notifications, Warnings and Shutdowns 22
2.3General Navigation 23
2.3.1Tile Navigation 23
2.3.2Grid and Chart Navigation 23
2.3.3User Adjustable Fields 23
2.3.4Keyboard 24
2.3.5Keypad 25
2.3.6User Non-Adjustable Fields 25
2.3.7Drop Down Boxes and Text Edit 25
2.4OmniView 26
2.4.1Main Viewing Application
2.5Compressor 29
2.5.1Main Tab 31
2.5.2Classic Tab 33
2.5.3Vibration tab 33
2.5.4Starter tab 36
2.6Condenser 37
2.6.1Overview tab (Condenser sequencer) 38
2.6.2Main tab (Condenser sequencer) 39
2.6.3Schedule tab 42
2.6.4Main tab (Condenser water cooled) 46
2.7Evaporator 46
2.7.1Overview tab 47
2.7.2Main tab 48
2.7.3Evaporator for chiller 50
2.8Sequencer 50
2.8.1Overview tab 51
2.8.2Main tab 53
2.8.3Schedule Tab 55
2.9OmniNet 58
2.9.1OmniLink™ Tab 59
2.9.2Modbus TCP Tab 60
2.10 History 61
2.10.1Bottom Menu Navigation 61
2.10.2RT-Trend Tab 64
2.10.3Chart Tab 65
2.10.4Annunciations Tab 66
2.10.5Analysis Tab 68
2.10.6Reporting Tab 69
2.11 Documentation 70
2.11.1Documents Tab 70
2.11.2Videos Tab 72
2.12 Service 73
2.12.1I/O Status Tab 73
2.12.2Maintenance Tab 76
27
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.20165
Instruction Manual | GEA Omni™
Control panel
2.12.3Activity Log Tab 80
2.12.4Touch Panel Tab 82
2.12.5Logic Tab 83
2.13 File Manager 84
2.13.1Support Files 84
2.13.2Documents Tab 87
2.13.3Program Tab 89
2.13.4System Tab 92
2.13.5Apps Tab 94
2.14 Configuration 95
2.14.1System Tab 95
2.14.2Sensors Tab 96
2.15 Panel Settings 97
2.15.1Localization Tab 97
2.15.2Users Tab 98
2.15.3Network Tab 100
2.15.4Email Tab 102
2.16 Panel Info 103
3CONTROL 104
3.1Compressor Control Parameters 104
3.1.1Capacity Control 104
3.1.2Control 109
3.1.3Variable Vi 113
3.1.4Motor 114
3.1.5Motor Power 115
3.1.6Motor Current 116
3.1.7Motor Interlock 118
3.1.8Motor Speed 118
3.1.9Motor Temperature 120
3.1.10Oil Pump 122
3.1.11Oil Pump Interlock 126
3.1.12Oil Differential Pressure 126
3.1.13Oil Filter Pressure 130
3.1.14Oil Separator 132
3.1.15Oil Temperature 134
3.1.16Suction Pressure 135
3.1.17Discharge Pressure 139
3.1.18Discharge Temperature 142
3.1.19Oil Cooling 143
3.1.20Inlet Temperature 145
3.1.21Outlet Temperature 145
3.1.22Loss of Remote Start Signal 147
3.1.23Power Failure Restart 147
3.1.24Superheat 148
3.1.25Economizer 150
3.1.26Pump Down 151
3.1.27Capacity Outputs 153
3.1.28VTrac 154
3.1.29Compressor Service 154
3.2Oil Still Control Parameters 155
3.2.1Oil Still 155
3.3Condenser Sequencer Control Parameters 157
3.3.1Schedule 157
3.3.2Wet Bulb Control 158
3.3.3Discharge Pressure 159
3.3.4Condenser Control 160
3.3.5Water Pump Lockout 161
3.4Condenser Device Control Parameters 163
6GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
3.4.1Control 163
3.4.2Variable Speed Fan/Variable Speed Pump 164
3.4.3Water cooled condenser 164
3.5Evaporator Control Parameters 165
3.5.1Cooling 165
3.5.2Fan Cycling 167
3.5.3Defrost 167
3.5.4Suction Valve Settings 170
3.5.5Invert Solenoid Output 170
3.5.6Evaporator for Chiller 171
3.6Refrigerant Sensor Control Parameters 174
3.6.1Refrigerant Sensor 174
3.7Compressor Operating Data 176
3.7.1Analog Inputs/ Outputs 177
3.7.2Standard Calculated Values 178
3.7.3Digital Inputs/ Outputs 179
3.8Configuration 183
3.8.1Panel Configuration 183
3.8.2Compressor Configuration 187
3.9Normal Operating States 197
3.9.1Stopped Description 197
3.9.2Starting Description 197
3.9.3Running Description 198
3.9.4Stopping Description 198
3.10 Additional Operating States 198
3.11 Screw Compressor Capacity Control 199
3.11.1Forward and Reverse 199
3.12 Variable Vi 201
3.12.1Operating Modes 201
3.12.2Types of Vi Control Systems 202
3.12.3Combined Vi Partial Load Control 202
3.13 Lubrication System 205
3.13.1Full Time 205
3.13.2Full Time with No Prelube 205
3.13.3Startup 205
3.13.4No Pump 206
3.14 IntelliSOC 206
4ANNUNCIATIONS 207
4.1Shutdowns 207
4.1.1List and Description of Compressor Shutdowns 207
4.1.2List and Description of Condenser Shutdowns 212
4.1.3List and Description of Evaporator Shutdowns 213
4.1.4List and Description of VTrac Shutdowns 213
4.1.5List and Description of Refrigerant Sensor Shutdowns 213
4.1.6List and Description of Drum Sequencer Shutdowns 213
4.1.7List and Description of Other Shutdowns 214
4.2Warnings 214
4.2.1List and Description of Compressor Warnings 215
4.2.2List and Description of Limitation Warnings 218
4.2.3List and Description of Condenser Warnings 220
4.2.4List and Description of Evaporator Warnings 220
4.2.5List and Description of Profibus Gateway Warnings 221
4.2.6List and Description of GEA BluAstrum Condenser Warnings 221
4.2.7List and Description of VTrac Warnings 221
4.2.8List and Description of Refrigerant Sensor Warnings 222
4.2.9List and Description of Oil Still Warnings 222
4.2.10List and Description of Other Warnings 222
4.3Notifications 223
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.20167
Instruction Manual | GEA Omni™
Control panel
4.3.1List and Description of Compressor Notifications 223
4.3.2List and Description of Condenser Notifications 223
4.3.3List and Description of Other Notifications 224
5SENSOR CALIBRATION 225
5.1Pressure Transducer Calibration 225
5.2ICTD Temperature Transducer Calibration 226
5.3Capacity Slide Position Calibration 227
5.3.1Compressor Capacity Slide Input Calibration with External Oil Pump 228
5.3.2Compressor Capacity Slide Input Calibration without External Oil Pump 228
5.3.3Calibration for Capacity Slide for Step Variable Vi Compressors 230
5.4Volume Slide Position Calibration 231
5.5Compressor Motor Current Calibration 232
5.6Capacity Slide Sensor Calibration 232
5.6.1Capacity Slide Calibration with External Oil Pump 232
5.6.2Capacity Slide Calibration without External Oil Pump 233
6LIST OF ABBREVIATIONS 235
8GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
10GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig. 114Reverse acting capacity control 201
fig. 115Pressure Sensor Calibration Pad 225
fig. 116Temperature Probe Calibration Pad 226
fig. 117Capacity Slide Calibration Pad 227
fig. 118Capacity Slide Calibration Pad (Step Variable Vi) 230
fig. 119Volume Slide Calibration Pad 231
fig. 120Motor Current Calibration Pad 232
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201611
Instruction Manual | GEA Omni™
Control panel
12GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
1SAFETY AND CONFORMITY
1.1Safety Instructions
The GEA Omni™ is reliable in operation if used as specified.
Hint!
Read the safety instructions in the GEA Omni™ operating manual before startup.
The intended use includes the observance and compliance of
•
all notices regarding hazard to persons and damage to property in the operating instructions,
•
the country-specific standards and safety regulations,
•
the instruction for installation, operation and maintenance,
•
the details of certificates,
•
the requirements for personnel,
Safety and Conformity
Safety Instructions
•
the obligation to exercise due care.
Only compliance with all provisions and guidelines will enable optimum protection of the personnel as well as
dangers to the environment and the safe and smooth operation of the GEA Omni™.
Warning!
GEA Omni™ can cause hazard in case of improper or unintended use. A malfunction indication on the touch screen cannot be ignored.
A personal injury or damage to the machine or plant can be the result.
For precautions to prevent danger see safety instructions in the operating manual.
Warning of electric shock!
Danger of electric shock exists.
More than one switch-disconnect may be necessary to isolate all electrical components.
Before maintenance work on the control panel, make sure that all electrical components are
switched off.
Danger!
It should be ensured at any time that all are necessary processes for compressor cooling and
lubrication in operation as long as the compressor is in operation.
This applies esprecially for the case where the compressor is unintentionally in operation. The
unintentionally compressor operation can be determined by observation of the compressor
motor feedback, the motor current or the motor speed.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201613
Safety and Conformity
Safety note concerning the connection of the GEA Omni™ with the starter panel
Instruction Manual | GEA Omni™
Control panel
Hint!
To minimize the possibility of interference from electromagnetic signals in the operation of the
ICTD temperature converters, the following wiring guidelines must be observed:
•
The signal cables should be two conductor shielded cable. Twisted pair cable is preferable.
•
The signal cables should be run in conduits which do not contain any AC wiring.
•
The signal cables should not be run in parallel or in close proximity to VFD power cables.
•
All VFD equipment in the facility must be solidly grounded.
•
If the ICTD sensors are not mounted on the skid or compressor package, the convertor should be
mounted at the probe location.
•
Operation of some high-powered radio or microwave communications equipment in close proximity to the ICTD temperature converters, ICTD sensors, or interconnecting wiring may result in
inaccurate readings for the associated temperature(s).
1.2Safety note concerning the connection of the GEA Omni™ with the starter panel
Hint!
It is not permitted to add an external controller between the GEA Omni™ and the power panel;
this would compromise the safety interlocks designed for protecting personnel and equipment. All control signals between the GEA Omni™ and the starter panel must be processed
directly and must not flow indirectly via an external controller. GEA Refrigeration North America, Inc. cannot otherwise guarantee the safe operation of the system.
14GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
Conformity - CE marking (Europe)
Safety and Conformity
1.3Conformity - CE marking (Europe)
The CE marking of the GEA Omni™ takes place according to the Low Voltage Directive 73/23/EEC and the
EMC Directive 89/336/EEC.
By affixing the CE mark, the manufacturer confirms the conformity of the product with the applicable EC Directives and compliance with the principle requirements stipulated within them.
The CE mark is affixed in the cabinet.
fig.1:CE mark
1.4Conformity - UL marking (USA, Canada)
The UL marking of the GEA Omni™ takes place according to the UL certification process and confirms the compliance with national standards in the United States and Canada.
With affixing the UL marking, the manufacturer confirms the GEA Omni™ is built to the guidelines of UL.
The UL mark is affixed in the cabinet.
fig.2:UL mark
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201615
User interface
Instruction Manual | GEA Omni™
Control panel
2USER INTERFACE
The screen shown below will appear when the GEA Omni™ panel is powered on.
The central portion of the screen will change depending on the current display of the panel.
The menu bar on the left displays options used for navigation between displays or interfaces. The status bar at
the bottom displays important information regarding the status of the panel and its devices. Both the menu bar
and the status bar will remain visible at all times.
fig.3:Initial Screen
16GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.1Menu Navigation
User interface
Menu Navigation
fig.4:Main menu bar
The menu bar is used to navigate through the various user interfaces available on the GEA Omni™ panel. Each
option will display a new screen on the panel. For full information on a given option, see the associated section
of the document.
The options and their corresponding sections are shown in the list below.
OmniView
Compressor
Condenser
Evaporator
Sequencer
OmniNet
History
Documentation
Section 2.4, Page 26
Section 2.5, Page 29
Section 2.6, Page 37
Section 2.7, Page 46
Section 2.8, Page 50
Section 2.9, Page 58
Section 2.10, Page 61
Section 2.11, Page 70
Service
File Manager
Configuration
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201617
Section 2.12, Page 73
Section 2.13, Page 84
Section 2.14, Page 95
User interface
Menu Navigation
Instruction Manual | GEA Omni™
Control panel
Panel Settings
Panel Info
Section 2.15, Page 97
Section 2.16, Page 103
18GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
Status Bar
2.2Status Bar
fig.5:Default status bar
The status bar is displayed along the bottom of the panel display and will be visible regardless of which screen is
currently open on the panel. It displays the current user, the status of certain devices controlled by the panel, any
notifications, warnings or shutdowns that have been annunciated and the current date and time.
fig.6:Expanded status bar
Touching anywhere on the status bar will bring up the sub-screen displayed above. The expanded status bar
may be used to make changes to the user level, view detailed status information regarding controlled devices, or
acknowledge and clear annunciations.
2.2.1Logging In
fig.7:Default users
The bottom left corner of the panel displays the user who is currently logged in. The icon is also color coded to
indicate the permissions each user has access to. When no user is logged in, this section will display LoggedOut and the user icon will be red. Once a user has logged in, the name of the user will be displayed and the icon
will change to green if the user’s access level is Operator or Service, or yellow if the user’s access level is
Admin.
Hint!
Admin level is only for use by GEA certified technicians.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201619
User interface
Status Bar
fig.8:Remote Icon
Instruction Manual | GEA Omni™
Control panel
Additionally, if the panel is currently being viewed remotely through OmniLink, the bottom left hand corner of the
display will blink back and forth between the icon for the current user and the remote icon shown above. The
remote icon is always colored blue and displays how many remote devices are currently viewing the panel display.
fig.9:User panel
The section shown to the far left of the sub-screen when the status bar is clicked displays a list of all users currently associated with the panel. For more information on adding or deleting users, refer to Instruction Manual
Section 2.15.2, Page 98.
If the user selected in the list is the one that is currently logged in, the Logout button will be enabled, which will
cause the panel to display the Logged Out message until another user is logged in. The Login button will be
enabled whenever a user account other than the one that is currently logged in is selected.
When a user not currently signed in is selected, the Login button will be enabled. Touching it will bring up a
numeric keypad which will allow the user to enter their password. If the correct password is entered, the selected
user will be signed in on the panel. If another user is already logged in, logging in as a different user will result in
them being signed out.
The default passwords for the Operator, Service and Admin access levels are displayed in the table shown to
the below. It is advisable to change these passwords once startup is completed.
Access levelDefault password
Operator1
Service123654
Admin1236547890
20GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
Hint!
The Admin account will only be accessible on new panels if a USB containing the Admin
Access Key file is plugged into the panel. In this case, the Admin password does not need to
be entered.
The Admin account will also be accessible for Retrofit panels and panels sold without a package or skid. In this case, the user will need to enter the Admin password displayed above. The
account will remain enabled until the panel is commissioned.
2.2.2Current State
User interface
Status Bar
fig.10:Status panel
The bottom center portion of the panel display shows the status of the compressor controlled by the panel. If
multiple devices are controlled from a single panel, the display will cycle between them periodically.
The section shown in the middle of the sub-screen when the status bar is clicked displays a list of all devices
controlled by the panel, such as compressors and evaporators and their current status.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201621
User interface
Status Bar
Instruction Manual | GEA Omni™
Control panel
2.2.3Notifications, Warnings and Shutdowns
fig.11:Annunciation icons
The bottom right portion of the status bar directly to the left of the date and time block will be clear during normal
operation of the panel. If the panel ever annunciates a notification, warning or shutdown, the corresponding portion of the bar will flash with the number and type of the annunciation.
fig.12:Annunciations panel
The section shown to the far right of the sub-screen when the status bar is clicked displays detailed information
about each annunciation. Along with an icon detailing the type of the annunciation, the display includes the name
of the annunciation, along with the date and time that it was triggered.
The buttons on the right of the display are used to acknowledge and clear annunciations. An annunciation with
the acknowledge button, abbreviated ACK on the display, will not be removed from the list, even if the issue that
caused the annunciation in the first place is resolved, until the button has been pressed. Other annunciations
may be cleared using the Clear button, which will immediately remove the annunciation.
However, if the condition that caused the annunciation in the first place has not been resolved, the annunciation
will reappear in the list. Any annunciation that is tracked by the Omni Historian Section 2.10, Page 61 will also
appear with a History button, which may be pressed to automatically open the historical table.
22GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
General Navigation
2.3General Navigation
The user interface (UI) for the GEA Omni™ makes use of a number of different navigation methods. The following is a brief description of each of these methods.
2.3.1Tile Navigation
fig.13:Sample Tile display
(Documentation Screen)
Certain screens, such as the Documentation and Configuration screens, display information divided across multiple tiles. Each tile corresponds to a specific element, such as a compressor or other device in the configuration
screen or a specific document in the documentation screen. Touching a tile will display the information connected to the tile.
For specific information regarding specific tiles see the appropriate section below. To return to the tile display,
the Close button in the bottom right corner of the display must be clicked.
2.3.2Grid and Chart Navigation
Grid and chart displays, such as those displayed in the Main compressor screen and the History screen, contain
detailed information divided into columns. For detailed information on specific tables, please see the appropriate
section below.
A table or grid may be navigated by using touch functionality to scroll through the data, or by touching a row and
using the arrow buttons.
2.3.3User Adjustable Fields
Fields that may be modified by the user are indicated by a white background. These fields are used for data that
may need to be modified while the panel is in operation.
Exception: List of Control Parameters. Fields that may be modified by the user are indicated by a white or light
blue background.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201623
User interface
General Navigation
Instruction Manual | GEA Omni™
Control panel
2.3.4Keyboard
When a field is selected that allows a text string to be entered by the user, the keyboard shown below will appear
in the lower half of the screen.
fig.14:Keyboard display (Letters)
The letter keys may be used in the same manner as a normal keyboard. The &123 button changes the display of
the keyboard to the one shown below, which is used to add numbers or frequently used symbols to the string.
fig.15:Keyboard Display (Numbers and symbols)
24GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
General Navigation
2.3.5Keypad
When a field is selected that allows only numeric value to be entered by the user, the keypad shown below will
appear in the lower half of the screen. The number keys may be used to enter a new value for the field, and the
+/- key is used to change the sign of the value.
fig.16:Keypad display
2.3.6User Non-Adjustable Fields
Fields that may not be modified by the user are indicated by a dark gray background. These fields are used for
information that is intended to be displayed only.
2.3.7Drop Down Boxes and Text Edit
Various fields that allow user input are in the form of text boxes and drop down lists.
A text box appears as a blank white box and may be used to enter any text string the user desires.
Drop down lists are differentiated from text boxes by a downward pointing arrow on the far right. These fields
have a predetermined list of possible values which appear in a vertical list when the arrow is clicked, from which
the user may select the desired value.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201625
User interface
OmniView
2.4OmniView
Instruction Manual | GEA Omni™
Control panel
fig.17:Main OmniView screen
26GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
OmniView
2.4.1Main Viewing Application
The main OmniView screen will display tiles corresponding to each device controlled by the panel. Each tile displays the name and pertinent information for the associated device.
Standard Devices
1.Compressor
Tiles corresponding to compressors display the
name, set point, status and current values associated with the compressor. While the capacity of the
compressor is being increased, an upward facing
arrow will be displayed in the lower right hand corner of the tile. Similarly, a downward facing arrow
will be displayed in the bottom left hand corner of
the tile if the compressor capacity is being
decreased. The color of the tile is determined by
the current status of the compressor. If the compressor is not connected, the tile will be colored
gray. The other colors, in order of precedence, are:
•
fig.18:Compressor tile
Red/ light green flash: Illegally Started
•
Red: Shutdown
•
Light green: Running
•
Yellow: Warning
•
Dark green: Stopped
Touching any tile will open the compressor screen for the selected compressor. Refer to Section 2.5,
Page 29 for full details on compressor operation.
2.Condenser Sequencer
The tile corresponding to the condenser sequencer
displays important information relating to the control of condenser devices. The information displayed, from top to bottom, includes:
•
Control value
•
Set point
•
Status
•
Current step
•
Fans running
•
Pumps running
fig.19:Condenser sequencer tile
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201627
User interface
OmniView
Touching the condenser sequencing tile will open the overview screen for the condenser. Refer to Section 2.6, Page 37 for full details on condenser control.
3.Evaporator
fig.20:Evaporator Tiles
Instruction Manual | GEA Omni™
Control panel
These tiles each correspond to an evaporator zone.
Each tile displays the name of the evaporator, the
current zone temperature. Depending on the current status of the zone, the tile will also display
either the time remaining on the defrost cycle or the
temperature set point the zone is in the process of
cooling to. The zone status is indicated by the color
of the tile. The colors are:
•
Light Blue: Tiles of this color indicate that the
associated zone is in cooling mode.
•
Dark Red: Tiles of this color indicate that the
associated zone is currently in defrost mode.
Touching any tile will open the evaporator screen for the selected zone. Refer to Section 2.7, Page 46
for full details on evaporator operation.
4.Control Level (for compressor sequencing)
These tiles each correspond to a control level for
use in compressor sequencing. The information
displayed on each tile, from top to bottom, includes:
•
Control value
•
Set point
•
Status
•
Current step
•
Compressors running
•
Compressors available
fig.21:Control level tile
Touching any control level tile will open the overview screen for the sequencer. Refer to Instruction Man-ual Section 2.8, Page 50 for full details on compressor sequencing.
28GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
Compressor
2.5Compressor
The Compressor menu is used to control each compressor from the panel. There are multiple tabs which are
detailed below. The bottom of the screen contains the eight standard buttons used to control the compressor.
Active buttons are illuminated with black text and a white outline while inactive buttons are darkened with white
text.
fig.22:Standard compressor buttons
The buttons are:
1.STOP
This button is illuminated whenever the compressor is in the stopped state, whether through a normal
stoppage or through a shutdown condition. Touching this button will initiate the stopping procedure. For
more information, refer to Section 3.9.4, Page 198. While the compressor is in the stopping process, this
button will flash. Touching the button a second time will cause the compressor to stop without unloading.
2.START
This button is illuminated whenever the compressor is running in local mode. Touching this button will
attempt to start the compressor. If the compressor is in the process of starting, this button will flash.
Once the compressor has started, the button will be illuminated continuously. If the compressor is in
Automatic Start/Stop mode, this button will display an A in its upper left hand corner and will resume
flashing if it has been automatically stopped to allow pressure to build.
3.REMOTE
This button is illuminated whenever the compressor is set to receive instructions from an external
source, such as a sequencer. Touching this button will switch the compressor from local to remote control.
4.AUTO
This button is illuminated whenever the compressor is set to control its capacity automatically based on
the control signal. Touching the button will switch the compressor to Automatic mode.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201629
User interface
Compressor
5.HOLD
This button is illuminated when the compressor is set to maintain its current capacity and will not load or
unload for any other reason. Touching and holding the button will display a block of additional buttons
based on the type of the compressor.
Alternatively, simply touching the button will cause the compressor to hold at its current capacity slide
position.
The example shown below displays the options for a screw compressor, and may be used to select the
capacity slide position at which the compressor should hold.
fig.23:Hold position options
Instruction Manual | GEA Omni™
Control panel
6.LOAD
The gray bar on the right of this button represents an LED. Whenever the Load Solenoid of the compressor is energized, the LED will be illuminated green. Touching and holding the button while the compressor is running in Local mode will force the compressor to increase capacity unless a limitation for
capacity increase is active. This will also force the compressor into Hold mode.
7.UNLOAD
The gray bar on the right of this button represents an LED. Whenever the Unload Solenoid of the compressor is energized, the LED will be illuminated green. Touching and holding the button while the compressor is running in Local mode will force the compressor to decrease capacity unless a limitation for
capacity decrease is active. This will also force the compressor into Hold mode.
8.EXTERNAL
Touching the button will force the compressor’s capacity mode into External mode. This button will be
illuminated when the capacity of the compressor is being controlled remotely from an external device.
30GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.5.1Main Tab
User interface
Compressor
fig.24:Main tab display
This screen contains all of the operational data for the compressor. For panels configured to control a single
compressor, this screen will be the default display. If multiple compressors are controlled from the panel, this tab
will display information pertaining to the compressor most recently selected in the tile display of the OverviewTab detailed in section "Overview Tab" (not yet available at the moment). If no tile has been selected in the overview screen, this screen will display the first compressor. The display is divided into three parts:
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201631
User interface
Compressor
1.Main Compressor Display
This portion of the screen displays the current status of the compressor. The color of the display is
dependent on the status of the compressor. The colors, in order of precedance, are:
•
Red/ light green flash: Illegally Started
•
Red: Shutdown
•
Light green: Running
•
Yellow: Warning
•
Dark green: Stopped
2.Operating Data
This table contains the current values associated with the compressor.
The information in the table is divided into three columns. The left column contains the slice location of
the value, if applicable. If the row in question does not correspond to a slice location, this column will be
blank. The middle column contains the name of the variable. The right column contains the current value
and units of the variable, if applicable.
The Edit Grid button in the upper right corner of the table will display a fourth column containing check
boxes which allows the user to toggle which rows are displayed. A checked row is displayed, while an
unchecked row is hidden. While the check boxes are displayed, the text of the Edit Grid button will
change to Save Grid. Touching the button a second time will hide the fourth column and display only
selected rows.
Each user may customize the values displayed in this table separately.
For details on individual elements of the Operating Data display, refer to Section 3.7, Page 176.
Instruction Manual | GEA Omni™
Control panel
3.Control Parameters
This table contains the name and current values of the parameters used to control the compressor.
Each parameter may be edited by touching the row and either selecting an option from a list of possibilities,or entering a new value using the keypad or keyboard. The color of the text indicates whether the
value may be edited; blue values may be modified, gray values may not. For normal operation, only the
parameters that may be edited by the user are displayed.
Touching the Advanced View button will instead display all parameter data. This will also change the text
of the button to Basic View, which may be clicked a second time to only display the editable parameter
data. For details on individual control parameters, refer to Section 3.1, Page 104.
32GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.5.2Classic Tab
User interface
Compressor
fig.25:Classic tab display
This screen displays the most important operating data for the compressor.
The gauges shown in the upper portion of the screen display the suction, oil differential and discharge readings,
the indicator shown in the bottom left corner displays the current capacity slide valve reading, and the values
displayed in the bottom right show the run time, current and rpm of the motor. The rpm reading will only be displayed if the motor has a variable speed drive.
2.5.3Vibration tab
This screen displays information pertaining to the VTrac vibration sensor. It will only be displayed if VTrac is enabled in the configuration of the panel. The data may be displayed in two different formats. The format currently
displayed may be switched by touching the button which is displayed to the left of the options button in the bottom right hand corner of the screen.
The text of the view button is dependent on the view format currently displayed. The text will read SpectrumView while the damage view format is displayed, and the will instead read Damage View while the spectrum
view format is displayed.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201633
User interface
Compressor
fig.26:VTrac Damage view
Instruction Manual | GEA Omni™
Control panel
Damage view, as shown above, displays the currently measured vibration of any of the available VTrac sensors
in the form of a horizontal bar graph. Each row corresponds to a different measurement point on a sensor. Certain sensors contain multiple points of measurement. The text located along the right edge of the screen displays
the name of each measured point, with the sensor channel the point is associated with displayed in parentheses.
The numbers along the vertical axis of the graph display the current value measured at the associated point, and
the horizontal axis denotes the vibration level.
Each bar is color coded as detailed below:
•
Blue: This portion of the bar displays the current vibration level read by the sensor at the associated point.
•
Gray: This portion of the bar represents the safe range of vibration levels that the associated point may
operate under. As long as the measured value remains within this range, no warnings or shutdowns will be
annunciated.
•
Yellow: This portion of the bar represents the range of vibration levels where the monitored component is in
danger of being damaged if the vibrations continue to increase. If the measured value ever falls within this
range, a warning condition will be annunciated for the component in question.
•
Red: This portion of the bar represents the range of vibration levels within which the monitored component is
in immediate danger of damage due to the vibrations. If the measured value ever falls within or exceeds this
range, a shutdown condition will be annunciated.
By default, the measurements from all channels of the VTrac are viewed simultaneously. However, the drop
down list displayed at the bottom of the screen may be used to limit the display to a single channel. When a
channel is selected from the list, the graph will rescale to display only the measurement point or points associated with it.
34GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.27:VTrac Spectrum view
User interface
Compressor
The spectrum view, as shown above, displays the raw reading from the channel selected in the drop down list at
the bottom of the screen. Multiple channels may not be displayed simultaneously in this view. The vertical axis of
the graph displays the vibration measurement and the horizontal axis displays the frequency. Both measurements are displayed in the current units as selected in the Options screen described below. The second drop
down list is used to select the scale of the measurements. The selected value indicates the distance between
each tick on the vibration level axis. The options are dependent on the selected panel units.
fig.28:VTrac Options display
Touching the Options button displayed in the bottom right hand corner in either view will bring up the options
screen shown above. The options are:
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201635
User interface
Compressor
1.
Analysis Mode
Instruction Manual | GEA Omni™
This drop down list is used to select the vibration analysis method that will be used. The vibration analysis is
always carried out using a variant of the Fast Fourier Transform. The options are used to select whether an
envelope will be used in the analysis. The options are:
–
FFT
This option is used to select a normal Fast Fourier Transform.
–
H-FFT
This option is used to select a Fast Fourier Transform with an envelope.
2.
Units
This drop down list is used to select the units that will be used for measuring vibration. The options are:
–
inches/s
This option is used when vibration should be measured in terms of velocity.
–
mg
This option is used when vibration should be measured in terms of acceleration.
3.
Frequency
This drop down list is used to select the units that will be used for measuring frequency. The options are:
Control panel
–
CPM
This option is used when frequency should be measured in Cycles per minute.
–
Hz
This option is used when frequency should be measured in Hertz.
2.5.4Starter tab
fig.29:Starter tab display
36GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
Condenser
This screen is used to control the compressor starter. It is only displayed if motor starter communication is enabled.
1.
Starter information
This tile displays the current status, runtime, amperage and rpm of the starter. The color of the tile indicates
the current status of the starter.
1.1
Gray: This color indicates that the starter is not currently communicating with the panel.
1.2
Dark Green: This color indicates that the starter is currently stopped.
1.3
Light Green: This color indicates that the starter is currently running.
1.4
Red: This color indicates that the starter is currently in a shutdown state.
2.
Starter faults
The Clear Faults button may be used to clear any active faults found in the starter.
3.
Default settings
The Load Default Settings button may be used to restore the starter to its factory default settings.
4.
Starter parameters
This table displays the control parameters read from the starter. Each starter has its own unique parameters
list. For more information regarding the specific function of each parameter, refer to the manual associated
with the starter in use by the panel.
2.6Condenser
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201637
User interface
Condenser
2.6.1Overview tab (Condenser sequencer)
Instruction Manual | GEA Omni™
Control panel
fig.30:Condenser overview tab
This screen contains a tile display which represents the condenser system and devices. The tile in the upper left
corner represents the condenser sequencer. The sequencer tile, as shown below, displays important information
relating to the condenser control, including, status, set point, control value, the number of fans running and the
number pumps running.
fig.31:Condenser sequencer tile
All other tiles shown on the overview display represent different condenser devices. Each tile displays the current status of the device and whether control is currently enabled. For variable speed devices, the current speed
will also be displayed. The type of device is indicated by the symbol. The different types of devices are:
Fans
38GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.32:Condenser fan tile
Pumps
User interface
Condenser
fig.33:Condenser water pump tile
Touching any tile will open the Main Tab of the Condenser Screen, detailed in Section 2.6.2, Page 39 below.
2.6.2Main tab (Condenser sequencer)
This screen is used to display the current status and control parameters of the condenser sequencer and individual devices. The display will change depending on whether it is currently showing the status of the sequencer or
an individual device.
When the sequencer tile is touched, the main tab will display the screen shown below:
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201639
User interface
Condenser
fig.34:Main condenser tab (Condenser sequencer)
Instruction Manual | GEA Omni™
Control panel
1.
Sequencer information
This tile displays the current status, set point and control value of the sequencer.
2.
Device enabled
This switch is used to toggle whether or not the condenser sequencing is currently permitted to run.
3.
Control parameters
This table contains the parameters used during condenser sequencing. The values may be manually
changed by touching a row.
For more information regarding the specific function of each parameter, refer to Section 3.3, Page 157.
When a device tile is touched, the main tab display will instead appear as shown below.
40GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.35:Main condenser tab (Condenser device)
User interface
Condenser
1.
Device information
This tile displays the name, current status, set point and control value of the selected device. The current
speed will also be displayed here for variable speed devices.
2.
Device enabled
This switch is used to toggle whether or not the device is currently permitted to run.
3.
Control parameters
This table contains parameters containing basic information regarding the selected condenser. The values
may be manually changed by touching a row.
For more information regarding the specific function of each parameter, refer to Section 3.4, Page 163.
Touching the Main tab displayed at the top of the screen will bring up the display corresponding to the most
recently selected tile. If no tile has been previously selected in the Overview tab, the panel will bring up the information of the condenser sequencer by default.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201641
User interface
Condenser
2.6.3Schedule tab
Instruction Manual | GEA Omni™
Control panel
fig.36:Condenser schedule tab
This screen is used to display and modify the condenser sequencer schedule. The main portion of the display
contains the currently selected control schedule, which is displayed in table format with each condenser device
assigned to a column and each row corresponding to a different step. The sequencer supports four independent
schedules, each containing up to fifty steps. The components of the display are:
1.Schedule information
This section contains the user defined name for the currently selected schedule, the target set point
and the current condenser status.
2.Control value
This section displays the current value of the condenser control value.
3.Hide/ show timers
This button controls whether or not the three initial columns of the schedule table, containing the
time delays used while the sequencer is running automatically, are displayed.
4.Schedule selection
This drop down list is used to select which schedule is currently displayed.
42GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
5.Schedule table
This table displays all steps that will be executed by the condenser sequencer during normal panel
operation.
fig.37:Condenser schedule table
a.
Current step
This icon indicates which step is currently being executed by the sequencer.
User interface
Condenser
b.
Previous timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the previous step. This column will not appear if the HideTimers button has been clicked.
c.
Soak timer
This column contains the period of time that the sequencer must remain on the current step
before determining if it should step ahead to the next step, step back to the previous step, or
remain on the current step. This column will not appear if the Hide Timers button has been
clicked.
d.
Next timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the next step. This column will not appear if the Hide Timers
button has been clicked.
e.
Condenser devices
These columns each correspond to an individual condenser device. The contents of each cell
dictate what action the device will take during the associated step. The options are:
–
Run
This option is only available for single speed fans and pumps. It will cause the device to
activate during the associated step.
–
Stop
This option is available for all devices. It will cause the device to deactivate during the associated step.
–
Hold
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201643
User interface
Condenser
This option is only available for variable speed devices. Whenever it is selected, the device
will continue to run at its current speed during the associated step.
–
Auto
This option is only available for variable speed devices. Whenever it is selected, a percentage value may be entered, corresponding to a percent of the device’s maximum speed. The
device adjusts its speed automatically to match the chosen value and continue to make
adjustments to maintain the chosen value during the associated step.
6.Control buttons
fig.38:Condenser control buttons
Instruction Manual | GEA Omni™
Control panel
These buttons are used to control the sequencer. The buttons are:
a.
Auto
As long as this button is illuminated, the sequencer will run automatically based on the values
entered in the three timer columns.
b.
Hold
As long as this button is illuminated, the sequencer will remain on the currently selected step.
c.
Next
When this button is touched, the sequencer will immediately switch from the current step to the
next step below it in the table. If the sequencer is already on the final step, touching this button
will have no effect.
d.
Previous
When this button is touched, the sequencer will immediately switch from the current step to the
previous step above it in the table. If the sequencer is already on the first step, touching this
button will have no effect.
The values in the table display may be modified by touching the appropriate cell of the table. Whenever a cell containing a timer is touched, the sub-window below will be displayed.
44GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.39:Condenser timer control display
The value of the timer may be changed with the number pad, and the units may be changed with
the drop down list in the middle. If the Apply to all Timers box is checked, any change made to one
timer will affect all timers in the same column. The arrow keys may be used to navigate through the
table.
Whenever a cell in a condenser device column is touched, the sub window will instead appear as
shown below:
User interface
Condenser
fig.40:Condenser device control display
The state the condenser should enter in the given step may be selected in the central options block.
For certain options which require a percentage of the maximum capacity to be specified, the second
options block will be enabled. A percentage between 0% and 100 %, incremented in values of 5%,
may be selected from this list.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201645
User interface
Evaporator
Instruction Manual | GEA Omni™
Control panel
2.6.4Main tab (Condenser water cooled)
This screen is used to display the current status and control parameters of the condenser (water cooled).
If a water cooled condenser is used only the main tab is available.
The main tab will display the screen shown below:
fig.41:Main condenser tab (water cooled)
1.
Condenser (water cooled) information
This tile displays the current status of the condenser and the discharge pressure.
2.
Operating Data
This table displays the name, I/O slice location and current state of the digital points associated with the
zone.
3.
Control parameters
This table contains the parameters used. The value can be manually changed by touching a row.
For more information regarding the specific function of each parameter, refer to Section 3.4.3, Page 164.
2.7Evaporator
Evaporator control is based on temperature. The evaporator temperature controls the operation of the zone
based on its set point and related parameters.
A reset delay prevents all solenoids in the system from turning on at the same time. Any time the control panel is
powered-up, reset, or after a shutdown condition, all evaporator zones will be placed into a reset delay condition.
The first zone placed into operation is given a five second reset delay, and each subsequent zone that is enabled and not currently in a shutdown will be assigned a reset delay equal to the previous zone’s delay plus five
seconds. This allows the evaporator zones to come out of reset delay in any order. A zone that is in reset delay
will be represented by a dark green tile on the overview screen, and will display the remaining time until it will be
permitted to start.
The defrost cycle for an Evaporator zone may be initiated in one of three ways:
46GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
•
A manual initiate triggered through either the touch screen or communications.
•
An automatic defrost based on the run time of the zone’s liquid solenoid.
•
A daily defrost based on the current time of day.
User interface
Evaporator
With any of the modes of defrosting, the zone is placed into defrost immediately if no other zone on the same
group is defrosting. If another zone on the same group is in defrost, the zone will instead be placed into pending
defrost until the zone currently defrosting has completed the cycle.
The defrosting cycle may contain up to twelve stages. The amount of time the zone will remain in each stage is
user adjustable.
2.7.1Overview tab
fig.42:Evaporator Overview Tab
This screen normally contains a tile display which represents the evaporator system. Each tile represents an
individual zone and displays the zone name, current temperature, set point, current status and defrost group.
The color of each tile indicates the current status of the associated zone. The colors are:
•
Grey: Disabled
•
Dark Green: Stopped/ Waiting to Start
•
Light Green: Starting
•
Light Blue:Cooling
•
Dark Red: -Defrost
•
Light Red: Zone Shutdown
•
Yellow: Zone Warning
Touching a tile will open the Main Tab of the Evaporator Screen, detailed in Section 2.7.2, Page 48 below.
The behavior and view on this screen may be modified using the buttons found in the lower right hand corner of
the window. The functions of the buttons are detailed below.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201647
User interface
Evaporator
1.
Enable Scrolling/Swap Position
Instruction Manual | GEA Omni™
Control panel
This button is used to determine the touch and drag functionality of the screen. Touching the button will
switch the mode and change the button text to the disabled mode. While scrolling is enabled, the touch and
drag functionality will slide the tile display in the opposite direction.
This will only function is the system contains too many tiles to display them all on the screen at once. While
swapping is enabled, touching and holding a tile will allow it to be dragged to a new location in the display. In
either mode, touching and releasing any tile in the display will open the Main Tab of the Evaporator screen.
2.
Compare
This button will only be enabled while swapping tile locations is enabled, as detailed above. It is used to
change the display of the overview screen so that it will show a detailed view of two zones side by side.
When it is touched, the button text will change to read Select. Until the button is touched again, touching a
tile will mark it with a check in its upper right hand corner rather than opening the Main Tab. When two tiles
are selected and the button is touched a second time, the screen will change to display the parameters and
operating data of the selected zones.
fig.43:Zone Comparison Display
Touching the Close button in the bottom right hand corner of the screen will return the Overview screen to the
main tile display.
2.7.2Main tab
This screen is used to display the current status and control parameters of an individual evaporator zone.
48GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.44:Evaporator Main Tab
User interface
Evaporator
1.
Zone Information
This tile displays name, temperature set point, current temperature and status of the zone.
2.
Operating Data
This table displays the name, I/O slice location and current state of the digital points associated with the
zone.
3.
Control Parameters
This table contains the parameters used to control the zone. The values may be manually changed by touching a row. For more information regarding the specific function of each parameter, refer to Section 3.5,
Page 165
4.
Control Buttons
These buttons are used to manually control the functions of the zone.
•
Enabled/ Disabled
This button controls whether the zone is currently permitted to run. The button will appear light grey
while the zone is enabled, and dark grey while it is disabled.
•
Defrost Start/ Defrost Stop
This button is used to manually initiate a defrost cycle for the zone. If no zones are currently defrosting,
touching the button will cause the zone to begin its defrost cycle. During normal operation, only one zone
per group may be in defrost mode at a time. If another zone is already in defrost, the zone information
tile will display a Pending Defrost timer. Once the zone currently in defrost finishes the cycle, the zone
that has been waiting for the longest period of time will begin defrosting.
Touching the button a second time will override the Pending Defrost timer and begin the defrost cycle
regardless of whether other zones in the group are defrosting. The defrost group a zone is associated
with is selected in the control parameters. While the zone is defrosting, the button will be colored red and
the text will change to Defrost Stop. Touching the button again will immediately stop the zone from
defrosting.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201649
User interface
Sequencer
Instruction Manual | GEA Omni™
2.7.3Evaporator for chiller
This screen is used to display the current status and control parameters of an evaporator for chiller.
If a chiller evaporator is used only the main tab is available.
Control panel
fig.45:Main evaporator for chiller
1.
Evaporator Information
This tile displays name, temperature set point, current temperature and the status of the evaporator.
2.
Operating Data
This table displays the name, I/O slice location and current state of the digital points associated with the
evaporator.
3.
Control Parameters
This table contains the parameters used to control the evaporator. The values can be manually changed by
touching a row.
For more information regarding the specific function of each parameter refer Section 3.5.6, Page 171.
2.8Sequencer
50GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.8.1Overview tab
User interface
Sequencer
fig.46:Sequencer overview tab
This screen contains a tile display which represents the compressor sequencing system. The blue tiles located
on the left side of the display represent the individual control levels and display the current status, set point, control value, current step and number of compressor devices for each. A sample control level tile is shown below.
fig.47:Control level tile
All other tiles represent individual compressors. Each tile contains the compressor name, its current status and
the control value. The number in the upper right hand corner of the tile indicates which control level the compressor is associated with. A sample compressor tile is shown below.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201651
User interface
Sequencer
fig.48:Compressor device tile
Instruction Manual | GEA Omni™
Control panel
The color of the tile is dependent on the current state of the compressor. The colors are:
•
Gray: This color indicates that the associated compressor is not currently communicating with the panel.
•
Dark green: This color indicates that the associated compressor is currently stopped.
•
Light green: This color indicates that the associated compressor is currently running.
•
Yellow: This color indicates that the associated compressor is currently in a Warning state.
•
Red: This color indicates that the associated compressor is currently in a Shutdown state.
Compressor tiles may be added or removed from the display using the buttons in the bottom right hand corner of
the tile display. Clicking the Add button will bring up the sub window shown below, which may be used to configure a new compressor.
fig.49:Add compressor display
1.
This panel
This switch is used to select whether the control for the associated compressor is local to the panel or if the
sequencer can only control the compressor remotely through a network connection.
2.
Brand ID
This drop down list is used to select the type of panel associated with the tile. This field will only be enabled
if the This Panel switch is disabled.
3.
IP address
This text box is used to enter the network location where the local panel controlling the compressor may be
found. This field will only be enabled if the This Panel switch is disabled.
52GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
4.
Compressor selection
User interface
Sequencer
This drop down list is used to select the number of the compressor. The options are dependent on the type
of panel affiliated with the compressor.
5.
Level
This drop down list is used to select which of the available control levels the compressor will be sequenced
on. Any level that is currently enabled will appear in the options.
6.
Unit ID
This drop down list is used to select the Modbus ID of the panel. This option will only be used if the
sequencer utilizes an Ethernet to Serial communication convertor.
7.
Device tag
This drop down list is used to select the name that will be associated with the compressor.
Clicking any tile will open the main tab for the compressor sequencer as detailed in Section 2.8.2, Page 53.
2.8.2Main tab
This screen is used to display the current status and control parameters of the compressor sequencer and individual devices. The display will change depending on whether it is currently showing the status of a control level
or a specific compressor.
When a control level tile is touched, the main tab will display the screen shown below:
fig.50:Main sequencer tab (Control level)
1.
Control level information
This tile displays the current status, set point, current step and control value of the control level.
2.
Level enabled
This switch is used to toggle whether or not compressors on the selected level are currently permitted to be
sequenced.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201653
User interface
Sequencer
3.
Control Parameters
Instruction Manual | GEA Omni™
This table contains the parameters used during compressor sequencing. The values may be manually
changed by touching a row.
For more information regarding the specific function of each parameter, refer to Section 3.5, Page 165.
4.
Arrow Buttons
These buttons may be used to navigate between the displays for each control level.
When a device tile is touched, the main tab display will instead appear as shown below.
Control panel
fig.51:Main sequencer tab (Compressor device)
1.
Device information
This tile displays the Name, current status, set point and control value of the selected device. The color of
the tile is dependent on the current status of the compressor. Refer back to Section 2.8.1, Page 51 for a list
of the colors and their meanings.
2.
Device enabled
This switch is used to toggle whether or not the Device is currently permitted to run.
3.
Compressor device
This section contains the information that was entered when the compressor in question was added to the
overview display. Refer back to Section 2.8.1, Page 51 for the functions of each field. The fields are:
•
This panel
•
Brand ID
•
IP address
•
Compressor selection
•
Level
•
Unit ID
•
Device Name
54GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
4.
Arrow buttons
User interface
Sequencer
These buttons may be used to navigate between all compressor devices.
Touching the Main tab displayed at the top of the screen will bring up the display corresponding to the most
recently selected tile. If no tile has been previously selected in the Overview tab, the panel will bring up the information of the compressor sequencer by default.
2.8.3Schedule Tab
fig.52:Sequencer Schedule Tab
This screen is used to display and modify the control behavior of the compressor sequencer. The main portion of
the display contains the control schedule, which is displayed in table format with each compressor device
assigned to a column and each row corresponding to a different step. The sequencer supports up to fifty steps.
The components of the display are:
1.Current Level
This section contains the user defined name for the currently selected level, the target set point and
the current level status.
2.Control value
This section displays the current control value of the level.
3.Hide/ show timers
This button controls whether or not the three initial columns of the schedule table, containing the
time delays used while the sequencer is running automatically, are displayed.
4.Level Selection
This drop down list is used to select which level is currently displayed.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201655
User interface
Sequencer
5.Schedule table
This table displays all steps that will be executed by the compressor sequencer on the currently
selected level during normal panel operation.
fig.53:Sequencer Schedule Table
a.
Current step
This icon indicates which step is currently being executed by the sequencer.
Instruction Manual | GEA Omni™
Control panel
b.
Previous timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the previous step. This column will not appear if the HideTimers button has been clicked.
c.
Soak timer
This column contains the period of time that the sequencer must remain on the current step
before determining if it should step ahead to the next step, step back to the previous step, or
remain on the current step. This column will not appear if the Hide Timers button has been
clicked.
d.
Next timer
This column contains the period of time that the sequencer will wait before changing steps once
it has been instructed to switch to the next step. This column will not appear if the Hide Timers
button has been clicked.
e.
Compressor Devices
These columns each correspond to an individual compressor on the currently selected level.
The contents of each cell dictate what action the device will take during the associated step.
The options are:
–
Stop
This option will cause the compressor to deactivate during the associated step.
–
Stop With Wait on Drive Timers
This option will cause the compressor to stop if the period of time determined by the motor
start to start timer has fully elapsed. If the timer has not fully elapsed, the sequencer will
wait for the timer to finish before instructing the compressor to stop.
–
Load
56GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
This option will cause the compressor to increase its capacity during the associated step.
–
Unload
This option will cause the compressor to decrease its capacity during the associated step.
–
Auto
This option will cause the compressor to automatically take steps to maintain a specific percent capacity. The compressor will automatically load or unload to maintain the chosen
value during the associated step.
–
Hold
This option will cause the compressor to remain at a selected capacity during the associated step.
–
Standby
This option will cause the compressor to monitor all other compressors on the same level. If
any monitored compressor enters a shutdown state or cannot be started remotely, the compressor will start. If multiple compressors are in standby mode at the same time, the compressor that is most similar to the failed or inaccessible compressor will start.
User interface
Sequencer
6.Control buttons
fig.54:Sequencer Control Buttons
These buttons are used to control the operating mode sequencer. The buttons are:
a.
Auto
As long as this button is illuminated, the sequencer will run automatically based on the values
entered in the three timer columns.
b.
Hold
As long as this button is illuminated, the sequencer will remain on the currently selected step.
c.
Next
When this button is touched, the sequencer will immediately switch from the current step to the
next step below it in the table. If the sequencer is already on the final step, touching this button
will have no effect.
d.
Previous
When this button is touched, the sequencer will immediately switch from the current step to the
previous step above it in the table. If the sequencer is already on the first step, touching this
button will have no effect.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201657
User interface
OmniNet
Instruction Manual | GEA Omni™
Control panel
The values in the table display may be modified by touching the appropriate cell of the table. Whenever a cell containing a time is touched, the sub-window below will be displayed.
fig.55:Sequencer Timer Control Display
The value of the timer may be changed with the number pad, and the units may be changed with
the drop down list in the middle. If the Apply to all Timers box is checked, any change made to one
timer will affect all timers in the same column. The arrow keys may be used to navigate through the
table.
Whenever a cell in a condenser device column is touched, the sub window will instead appear as
shown below:
fig.56:Compressor Device Control Display
The state the compressor should enter in the given step may be selected in the central options
block. For certain options which require a percentage of the maximum capacity to be specified, the
second options block will be enabled. A percentage between 0% and 100 %, incremented in values
of 5%, may be selected from this list.
2.9OmniNet
58GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.9.1OmniLink™ Tab
User interface
OmniNet
fig.57:OmniLink™ tab display
This screen is used to remotely view and operate other panels on the same network.
The main portion of the screen contains a tile display detailing each individual panel connected to the system.
Panel types that are compatible with OmniLink™ include other GEA Omni™, GForce™ and GSC TP panels.
The color of a tile corresponds to the current status of the associated panel, as described in the OmniView tile
display.
The networked panels may be accessed through the four buttons displayed in the bottom right of the screen.
The buttons are:
1.Connect
This button is enabled as long as at least one of the tiles is selected. Touching it will allow the user to
remotely view the display of the selected panel and control it remotely. Only one external panel may be
viewed at a time. If multiple tiles are selected, this button will be disabled. While a panel is connected,
this button will change to Disconnect, which will return the user to the tile display when clicked.
2.Find Network Panel(s)
This button will query the network and locate any other GEA Omni™ panels. Any panel found in this
manner will appear as a new tile in the display and may be viewed or controlled normally.
3.Add Panel
This button will bring up a keypad display, which will prompt the user to enter an IP address to manually
add a panel to the tile display.
4.Remove Selected Panel
This button is enabled as long as at least one of the tiles is selected. Touching it will remove the selected
panel or panels from the tile display.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201659
User interface
OmniNet
2.9.2Modbus TCP Tab
Instruction Manual | GEA Omni™
Control panel
fig.58:Modbus TCP tab display
This screen displays any Modbus devices defined in the custom logic of the panel.
All applicable Modbus devices are displayed on the table in the center of the screen. Each row contains the
default Name, IP Address and Node Number of the device.
The Edit column contains a check box, which is used if the user wishes to modify the connections of the device.
Checking a row and touching the Edit Connections button will populate the fields in the upper right hand corner
of the screen. The Name field is locked, but the IP Address and Node Number fields may be modified.
60GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
History
2.10History
The History screen is used to display operating data for the panel over time. The historical data of the panel is
divided across five tabs, as detailed in the sections below.
2.10.1Bottom Menu Navigation
The detail and format of the data displayed in the RT-Trend, Chart and Annunciations tabs may be customized
using the buttons arranged in the bottom row of the screen. The buttons displayed differ depending on the current tab. While in the RT-Trend tab, the buttons appear in the arrangement shown below.
fig.59:The RT Trend button display
From left to right, the buttons are:
1.Reset Zoom
When viewing data within a graph, the user may zoom in and out to better view the information. This
button resets the viewing pane back to the default zoom. Zooming is controlled through pinch and zoom
functionality.
2.Show Annunciations
This button is used to toggle whether annunciation conditions are displayed in historical graphs displays.
It is only enabled as long as the data is being displayed in graph view. When this button is clicked, vertical lines will be added to the display, which correspond to any annunciations that have been triggered
during the time period represented on the graph. After the button has been clicked, the text will change
to Hide Annunciations. Touching the button a second time will remove the annunciation lines and change
the text back to Show Annunciations.
3.Save Data
This button is used to save the current range of RT-Trend data displayed in the graph. Clicking it will
save a snapshot of the current ten minute interval in table format. These snapshots may be accessed
from the annunciation tab, as detailed in Section 2.10.4, Page 66.
4.View - Table
This button is used to toggle how the historical data is displayed on screen. It is only enabled in the RT-Trend and Chart tabs. Touching the button will cause the data to be displayed in table format, with rows
corresponding to the time increments and columns corresponding to the values that are being monitored.
As long as the data is displayed in table mode, the text on the button will instead read View - Graph,
which will return the display to the graphical display and change the text back to View - Table when
clicked.
5.Edit View
This button is used to customize what data is displayed in the RT-Trend, Chart and Annunciations tabs.
Touching the button will display the screen shown below.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201661
User interface
History
fig.60:Edit view display
Instruction Manual | GEA Omni™
Control panel
The screen is divided into three sections which may be used to customize the historical display:
1.Viewing Options
The panel always displays forty eight hours’ worth of historical data. By default, the check box Past 2Days is checked, which instructs the panel to display historical data from two days previous until the
present moment. If this box is unchecked, the drop down list will become enabled and may be used to
select a custom end date, which will cause the panel to display two days’ worth of historical data ending
on the selected date.
2.Select Pens
These check boxes are used to select which values are tracked on the RT-Trend and historical graphs.
3.Saved Pens
Specific groupings of pens may be saved for easy access later through this section. Entering a group
name in the upper text field and touching the Save Pens button will add the selection of pens to the list of
pen groups shown in the lower box. If no name is entered, the selection will be saved using the current
date and time as a name.
Individual selections may be checked in the same manner as specific pens. Selections may be deleted
from the list of saved pens by checking them and touching the Delete Pens button.
The Chart tab displays a slightly different selection of buttons, as shown below.
fig.61:Chart tab button display
The Reset Zoom, Show Annunciations, View - Table and Edit buttons are identical in functionality to those used
in the RT-Trend tab. The Save Data button is not used in this tab, and it is replaced with a date range field which
displays the period of time shown in the current view. The field will always contain a forty eight hour period. The
62GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
History
arrow buttons to the right and left of the date range are used to change the displayed period. Clicking the left
arrow will move the range back by one day, while clicking the right arrow will move it forward by one day.
The Annunciations tab displays only the date range and Edit buttons, which retain their functionality from the
Chart tab. The Analysis and Report tabs do not contain a row of buttons at the bottom of the screen. For more
detailed information regarding the functionality of each tab, refer to the specific sections below.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201663
User interface
History
2.10.2RT-Trend Tab
Instruction Manual | GEA Omni™
Control panel
fig.62:RT-Trend tab display (View - Graph)
This screen displays real time (RT) panel data. This information can be displayed in either graph or table format.
Up to ten different sets of data may be displayed at once. The chosen pens are listed in the legend panel if viewing in graph format and at the top of the columns in grid format. All pens are updated every five seconds while
viewing this screen. The total range of time displayed at any given time is ten minutes.
fig.63:RT-Trend tab display (View - Table)
64GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.10.3Chart Tab
User interface
History
fig.64:Chart tab display (View - Graph)
This screen allows the user to view different sets of I/O information. This information can be displayed in either
graph or table format. Up to ten different pieces of data information may be displayed at once. The I/O is listed in
the legend panel if viewing in graph format and at the top of the columns in grid format. The total range displayed
by default on this screen covers a period of forty eight hours.
fig.65:Chart tab display (View - Table)
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201665
User interface
History
Instruction Manual | GEA Omni™
Control panel
2.10.4Annunciations Tab
The Annunciations tab displays common notifications, warnings and shutdowns that have been triggered on the
panel. The figure below displays a sample annunciations control.
fig.66:Annunciations tab display
66GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
1.
Viewable Grid Area
From here, the user can view the annunciation table. The table is divided into seven columns as detailed
below.
•
Type
The graphic displayed here is determined by the type of the triggered annunciations. Red indicates shutdown, yellow indicates warning and blue indicates a notification.
•
Description
Displays the name of the annunciation that was triggered.
•
Time
The time when the annunciation was either issued or cleared.
•
Parameter
The current value of the warning or shutdown set point which triggered the annunciation, where applicable.
•
Action
The text displayed here indicates whether the annunciation was issued or cleared.
User interface
History
•
Clear
This column will be filled only if the action column displays Cleared. It indicates whether the annunciation
was cleared manually or automatically.
•
RT-Trend
When a shutdown or warning annunciation is issued, the last fifteen minutes of historical data is
recorded. The user may view this information by selecting the picture embedded into the grid’s cell.
These will not be generated during panel startup. Manual RT-Trend snapshots are also displayed in this
format and appear in the table as notifications.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201667
User interface
History
Instruction Manual | GEA Omni™
Control panel
2.10.5Analysis Tab
The Analysis tab may be used to quickly identify common annunciations that have been generated by the panel.
It lists frequent shutdowns and warnings and the number of times each has occurred over a selected time range.
fig.67:Analysis tab display
1.Frequent Shutdowns
This section displays the five most common shutdowns that have occurred over the shown time period.
The information displayed here indicates the annunciation name and the total number of times it was
issued. It also calculates what percentage of the total number of shutdowns the annunciation in question
accounts for.
2.Frequent Warnings
This section is similar in functionality to the Frequent Shutdowns section, displaying the same information and analysis for warnings.
3.Annunciations Graph
This area displays the distribution of shutdowns and warnings across the selected range. For each day,
the yellow bar indicates the total number of warnings that occurred and the red bar indicates the total
number of shutdowns.
4.Date Range
The user can select between any of these preset time periods to change the date range. The DateRange option is also available, which displays the entire period that the panel has been active.
68GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.10.6Reporting Tab
This screen is used to generate custom reports from the panel’s historical data.
User interface
History
fig.68:Reporting tab display
1.Date Range
This is the time period to be included in the report.
2.Data Selection
These options are used to select what information should be included in the report. Alternatively, all
options may be selected or deselected through the Check All and Uncheck All buttons respectively.
•
Min/Max/Mean
This will calculate the min/max and mean for any of the selected I/O. The I/O is selected on the right
side of this tool.
•
Shutdown
This will display every shutdown that has been issued or cleared. It will list the description, type and
date.
•
Warning
This will display every warning that has been issued or cleared. It will list the description, type and
date.
•
Notification
This will display every notification that has been issued or cleared. It will list the description, type and
date.
3.Preview Report
This will generate a temporary pdf file displaying all of the selected information.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201669
User interface
Documentation
Instruction Manual | GEA Omni™
Control panel
4.Save Report
This will save the report to the connected USB drive.
5.Select Pens
This section is used to select which specific sets of data will be included in the report. A check mark in
the box to the left will indicate that the pen in question is selected.
2.11Documentation
The Documentation screen contains reference materials regarding panel or system functionality. The information
displayed here is divided across two tabs, as detailed in the sections below.
2.11.1Documents Tab
fig.69:Documents tile display
This screen is used to display all manuals and supplementary documents associated with the panel arranged in
a tile display. Touching a tile will bring up a new screen which will display the associated document. A sample
screen is shown below.
70GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.70:Sample document display
User interface
Documentation
1.Main Display
This section displays the selected document. The user may scroll through the document using touch and
drag functionality. Pinch and zoom functionality is also included.
2.Find
This field may be used to quickly search through the document for a given word or phrase. Touching the
field will bring up the keyboard, which will allow the user to enter the desired word or phrase. Touching
the magnifying glass icon to the right of the find field will search the document and highlight the first time
the chosen text appears. Subsequently touching the magnifying glass will cause the viewer to step
through the document, highlighting the next instance of the chosen text, until the end of the document is
reached. This search function is not case sensitive.
3.Bookmarks
This list displays the major section headings of the document currently being displayed. Touching a
bookmark will scroll the document to the chosen section.
4.Zoom
This slider is used to change the magnification of the document. The value may be varied from 25% to
400%.
5.Document Information
This section shows the page that is currently displayed, the total number of pages in the document and
the document title.
6.Close
This button exits the document viewer and returns the user to the tile display.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201671
User interface
Documentation
2.11.2Videos Tab
Instruction Manual | GEA Omni™
Control panel
fig.71:Videos tile display
This screen is used to display all instructional videos associated with the panel arranged in a tile display. Touching a tile will play the associated video. A sample screen is shown below.
fig.72:Sample video display
This screen is shown whenever a video is playing. The bar on the bottom left indicates the progress of the video.
The button in the center is used to pause and play, and the time stamp indicates the progress of the video. The
video title is displayed to the right of the time stamp. When the video is finished playing, the screen will automatically close and return to the tile display, but the user may exit the video early by touching the close button.
72GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.12Service
The service screen contains five tabs that are used to monitor and maintain the panel.
2.12.1I/O Status Tab
User interface
Service
fig.73:I/O Status tab display
This tab is used to display the current layout of the I/O system. Additionally, output slices may be forced to specific values, but this functionality may only be accessed by a user with service level or higher permissions.
The current status of the I/O system may be viewed through the LED indicators shown in the upper portions of
each slice. Slices that do not transmit or receive I/O signals, such as power and end slices are grayed out in the
display. Any other slice may be clicked to display a detailed view like the ones shown below.
The scopes shown on the outer edges of all the displays illustrate the raw signal received or transmitted by each
point.
Warning!
Caution should be exercised when forcing the value of outputs within the I/O status tab. Forcing a module to an improper value may cause harm to personnel or damage to equipment. If in
doubt, contact trained personnel.
Hint!
If outputs are forced, the module will return to its original value after a thirty minute interval.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201673
User interface
Service
fig.74:Sample digital input slice display
Instruction Manual | GEA Omni™
Control panel
The above image displays the detailed view of a digital input slice. Each channel that is configured to receive an
input signal will display its name to the side of the image. Unassigned channels will be blank. A channel receiving an energized signal will be illuminated green while a de-energized signal will cause the channel to appear
gray.
fig.75:Sample digital output slice display
The above image displays the detailed view of a digital output slice. Each channel that is configured to transmit
an output signal will display its name to the side of the image. Unassigned channels will be blank. A channel
transmitting an energized signal will be illuminated green while a de-energized signal will cause the channel to
appear gray. Output may be controlled automatically through the program or manually by a user with service
level or higher permissions. To enable manual control, the switch displayed next to the channel must be
touched. While a channel is in manual mode, its state may be changed by touching the LED on the display.
fig.76:Compressor motor start notification
74GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
Service
Compressor Motor Start outputs may not be switched into manual mode, but they may be pulsed using the button next to the channel. When the button is touched, the warning shown to the right will appear in the upper right
hand corner, which will warn the user to verify that the motor is uncoupled from the compressor before the
starter is pulsed. Touching the button next to the notification will then energize the motor starter for two seconds.
fig.77:Sample analog input slice display
The above image displays the detailed view of an analog input slice. Each channel that is configured to receive
an input signal will display its name to the side of the image. Unassigned channels will be blank. The current
value read at each input will be displayed below the name of the channel.
fig.78:Sample analog output slice display
The above image displays the detailed view of an analog output slice. Each channel that is configured to transmit an output signal will display its name to the side of the image. Unassigned channels will be blank. Output
may be controlled automatically through the program or manually by a user with service level or higher permissions using the drop down list displayed below the name of the channel. The options in the drop down list
include Auto and manual output values measured in mA. The manual values range from 0 mA to 20 mA in increments of 4 mA.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201675
User interface
Service
2.12.2Maintenance Tab
Instruction Manual | GEA Omni™
Control panel
fig.79:Maintenance tab display
This tab is used to display a grid detailing current and upcoming maintenance tasks. The information in this tab
may only be modified by a user with service level or higher permissions.
A grid is provided for each compressor in the system. If the panel controls multiple compressors, the selected
compressor may be changed using the drop down list in the upper right hand corner. Each row of the grid corresponds to a specific maintenance task and each column corresponds to a specific time interval. The column for
the current time period is highlighted orange. The selected compressor’s run time is displayed directly above the
grid. Check boxes populate the grid to indicate whether the task in question has been completed for the given
time period. If a check box is not present, the task in question need not be performed for the current interval.
The grid itself may not be modified from this view, but it may be updated using the four buttons that appear
below the grid.
1.Complete Current Service Interval
This button displays the screen shown below, which contains a list of all tasks associated with the given
interval. Touching the check box next to a task will mark it as complete.
76GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.80:Service task form display
User interface
Service
The upper left field contains a description of the task in question. The description is entered at startup for
standard tasks, and upon creation for custom tasks. The lower left field may be used to enter the procedure taken when the service task is performed. The Save Service Interval button displayed in the bottom
right corner will update the main maintenance chart.
2.Service Report
3.Edit Service Tasks
This button is used to create or edit custom maintenance tasks for the selected compressor. Touching it
will bring up the display shown below.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201677
User interface
Service
fig.81:Edit service tasks display
Instruction Manual | GEA Omni™
Control panel
The drop down list in the upper left hand corner contains all custom tasks associated with the selected
compressor. Selecting a task will populate the remaining fields, which may be modified freely. The fields
are:
A Service Task Name
The text that will be associated with the task in question. This field also determines the name that will be
displayed in the drop down list.
B Service Type Selection
This field is used to specify the type of maintenance that will be needed for the task. The options are:
–
Check
–
Clean
–
Replace
–
Measure
–
Visual Inspection
–
Tighten
C Service Unit Selection
This field will only be enabled if the Service Type selection is set to Measure. It contains a drop down list
which may be used to select the units of the desired measurement.
78GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
D Task Note
User interface
Service
This field may be used to enter details relating to the completion of the selected task. The information
entered here will be displayed in the Service Task description section of the main display.
E Service Levels
This section contains check boxes corresponding to each service interval. Selecting a box will add the
custom task to the list of required tasks for the given interval. The Check All option is displayed above
the checkboxes, which will add the task to all service intervals. Clicking the option a second time will
remove the task from all service intervals.
The buttons shown at the bottom of the display are used to add, remove or change custom service tasks. The
buttons are:
F New Service Task
Touching this button will clear all fields and allow the user to enter the details of a new service task. The
user will be prompted to select a name for the task, which will automatically be added to the options in
the drop down list.
G Delete Service Task
This button is only enabled when a service task is selected in the drop down list. Touching it will erase
the service task currently selected in the drop down list.
H Save Service Task
This button is only enabled when a service task is selected in the drop down list. Touching it will create
or edit the selected service task based on the information entered in the fields.
4.Edit Service Intervals
This button is used to modify the amount of time the compressor must run before each service interval
comes due. Touching it will bring up the dialog box displayed below. Any of the existing service intervals
may be selected using the drop down list on the left. The hours of the interval may be changed by entering the desired interval into the text box to the right and touching the Save Service Change button. If the
Ignore Service Notifications option is checked, the panel will not annunciate notifications relating to service intervals.
fig.82:Service maintenance display
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201679
User interface
Service
Instruction Manual | GEA Omni™
Control panel
2.12.3Activity Log Tab
This tab is used to display a log of all events and auditing information for the panel. It is also used to monitor the
network status of the panel.
fig.83:Activity log tab display
1.General Log
This table displays the date and details of any user activity logged in the panel. It also records which
user was logged in when each entry was recorded. The data to be displayed is selected through the
fields in the upper right corner of the screen. The lower two fields are used to select a date range to display. The upper field contains a drop down list which is used to select the type of data to be displayed.
The options are displayed below:
•
All Data
•
Parameter Changed
•
Configuration Changed
•
Settings Changed
•
Commands
•
File Handling
•
Power
•
Network
•
Error Log
This option is only available for a user with service level or higher permissions.
80GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.Network Status
This section contains two tables used to display information regarding networked devices. The network monitored may be either an ethernet network or a serial network. The type of network to monitor
is selected using the drop down list above the table. The table on the left displays the name and IP
address of each device. Touching an IP address in this list will filter the Devices and only display
ones with a matching IP address. The table on the right displays any messages received from a networked device and displays the Time, Message, Address, Length and Value received. The message
table may be cleared with the Clear Messages button, or halted temporarily with the Pause Messages
button, both found in the bottom right hand corner of the display. A count is also kept of any errors
found in packets received from the networked devices. Both types of network may receive a bad
packet, and a serial network may also have packets time out. A count for each of these conditions
can be found to the left of the buttons, and the Clear Packets button may be used to return the count
to zero.
User interface
Service
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201681
User interface
Service
2.12.4Touch Panel Tab
This tab contains a number of functions used for panel maintenance.
Instruction Manual | GEA Omni™
Control panel
fig.84:Touch panel tab display
fig.85:Wash down icon
1.Wash Down
This feature allows the user to clean the screen without accidentally making changes to the panel. When
this button is touched, the screen will become blank except for the button displayed above, which will
appear in the upper left hand corner of the display. Each time the button is touched, it will move to
another location on the screen. The button will cycle through five locations on the screen. Once the button has moved through all of its locations, touching it again will exit the wash down screen and return the
user to the main Touch Panel screen. Alternatively, the panel will automatically exit the wash down
screen if five minutes have elapsed since the screen was opened.
2.Calibrate Touch Screen
When this button is touched, the screen become blank and a crosshair will appear in the upper left hand
corner. Tapping the crosshair will cause it to move to a new location. This pattern will continue as the
crosshair moves through a total of sixteen locations, ending in the bottom right hand corner of the display. A message box will then prompt the user to choose whether to save the new calibration data. This
feature is used if the touch screen is not properly registering the location touched by the user. This feature may only be accessed by a user with Service level or higher permissions.
82GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
3.Lamp Test
Holding this button will turn on all lamps connected to the panel. This function is used to ensure that all
lamps and their associated wiring are working properly.
4.Move Commissioned Files
This button is used during startup once the panel has been installed. When this button is pressed, the
panel will clear out all erroneous data, warning and log reports generated during the installation process.
This button may only be used once, and only a user with Service level or higher permissions may access
it.
Hint!
It is mandatory to press the Move Commissioned Files button once installation of the
panel has been completed.
2.12.5Logic Tab
User interface
Service
This tab is only visible if the panel contains custom programming. It displays a real time representation of the
logic diagram used for custom controls.
fig.86:Logic diagram tab display
The user may switch between pages of the diagram using the tabs at the bottom of the display, navigate through
the selected page by clicking and dragging along the display and zoom in or out using the slider beneath the
page tabs.
The node on the blocks displayed in the diagram are color coded based on the type of signal they transmit or
receive. An analog node is black, a digital node is blue and a node that may transmit or receive either type is
colored orange. The lines between nodes also change to display their current value or state. Connections
between digital nodes will either appear as a solid green line for an energized signal, or a dotted red line for a
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201683
User interface
File Manager
Instruction Manual | GEA Omni™
Control panel
de-energized signal. Connections between analog points will always appear as black lines, but the current value
will be displayed above the output node from which the line originates.
2.13File Manager
The file manager screen is used to manipulate the files and applications that are stored on the panel’s hard
drive. Certain files may be copied to or from a USB memory device or removed entirely as detailed below. All
options in this screen may only be accessed be a user with service level or higher permissions.
2.13.1Support Files
fig.87:Support files tab display
This tab is used to export historical or control data from the panel. Data exported from this screen is automatically saved to a USB plugged into the panel, if applicable. The functions that may be accessed from this screen
are detailed below.
84GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
1.Historical Data
This section contains a drop down list which is used to select a range of time from which to export historical data to a USB. The options are:
•
All Data
•
One Week
•
Two Weeks
•
One Month
•
Date Range
If the Date Range option is selected, two additional fields will appear which will prompt the user to enter
a custom start and end date for the historical data range. Once a date range has been chosen, the Backup Historical Data button displayed to the far right of the section may be clicked, which will save a historian file, of file type .ohist, to the GEA RT folder of the USB. If no GEA RT folder is found, one will be
created automatically. The name the file is saved under is generated using the project number and the
current date.
User interface
File Manager
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201685
User interface
File Manager
2.Panel Data Report
Touching the button to the right of this section will generate a pdf document containing important information on all analog and digital I/O associated with the panel. The information in the panel data report
includes:
•
AB
The Allen Bradley address of the given data point.
•
Modbus Address
The Modbus location which the user may read from or write to for the given data point.
•
Description
The name associated with the given data point.
•
Designation/ Value
The I/O slice and channel associated with the given data point, if applicable. Designation is used for
analog data while Value is used for digital data.
•
Range
The maximum and minimum value that the given data point may contain. This column is only shown
for Analog data.
Instruction Manual | GEA Omni™
Control panel
•
State
The reading that will be displayed for the given data point when it is energized or de-energized. This
column is only shown for digital data.
•
Scale
This column indicates the number of decimal points the chosen data point is configured to read.
•
R/W
This column determines whether the user may read or write to the given data point. An R indicates
that the data point is read-only, and may be viewed but not modified by the user. R/W indicates that
the data point is Read/Write enabled, meaning that the user may view and modify the value freely. W
would indicate write-only, but is not used in the panel data report.
3.Control Parameters
This section allows the user to save a specific set of parameter values to a USB or the panel. The table
to the left of the section displays all .oprms files found on the USB and panel memory which may be
used to restore parameters to the panel or delete parameter files from either location. The parameters
may be manipulated through the four buttons displayed at the bottom right of the screen. The buttons
are:
•
Back up to USB
This button is used to save the current values of all custom parameters on the panel to an .oprms file
in the GEA RT folder on the USB. If such a folder does not exist, it will be created automatically. The
default name of the file is the number of the configuration, but a custom name may be entered into
the text field above the button.
86GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
•
Back up to Panel
This button is used to save the current values of all custom parameters on the panel to an .oprms file
in the GEA RT folder on the panel hard drive. If such a folder does not exist, it will be created automatically. The default name of the file is the number of the configuration, but a custom name may be
entered into the text field above the button.
•
Restore Parameters
This button is only available if a file is selected in the table to the left. Touching it will load the parameters in the selected parameter file to the panel.
•
Delete Parameter
This button is only available if a file is selected in the table to the left. Touching it will erase the
selected parameter file from the USB or panel.
2.13.2Documents Tab
User interface
File Manager
fig.88:Documents tab display
This tab is used to move supplementary documents to or from the panel, such as manuals or instructional videos. The green bar in the upper right hand corner of the screen represents the current available panel memory.
1.
Copying Files to the Panel
The list in the upper portion of the screen displays all files available to be copied to the panel’s memory.
Whenever a USB is plugged into the panel, any files of a panel compatible type type will be displayed. Files
that may be copied are .pdf documents and videos of .wmv, .avi and .mp4 formats. Each row in the list contains the name of the file, the file size and a checkbox used to select the file. To copy files, the row corresponding to each desired file must be checked. Alternatively, the table has a Check All button which will
allow the user to select every file on the USB. As long as at least one row is checked, the Copy File(s) button
shown to the upper right of the table will be enabled. Touching this button will save a copy of all selected
files into the panel’s memory.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201687
User interface
File Manager
2.
Copying or Deleting Files from the Panel
Instruction Manual | GEA Omni™
Control panel
The list in the lower portion of the screen displays all files currently saved to the panel’s memory. Each row
in the list contains the name of the file, the file size and a checkbox used to select the file. Files may be
selected from the list using the checkboxes in the rightmost column. Alternatively, the table has a Check All
button which will allow the user to select every file on the panel. As long as at least one row is checked, the
Delete File(s) and Copy File(s) buttons shown to the upper right of the table will be enabled. Touching the
Delete File(s) button will remove all selected files from the panel’s memory. Touching the Copy File(s) button
will save a copy of each selected file to a USB plugged into the panel.
88GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
2.13.3Program Tab
User interface
File Manager
fig.89:Program tab display
This tab may be used to update or save a back up of the GEA Omni™ software and the configuration file. Back
up data may be saved to either an external USB or to the panel itself.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201689
User interface
File Manager
→Update/Back up Software
The table in the upper portion of the screen, shown below, displays all existing version of the GEA
Omni™ software found on the panel or a connected USB. The table displays the file location and software version number of the file. The buttons displayed to the right of the table are used to handle the
programs.
fig.90:Update/Back up software display
Instruction Manual | GEA Omni™
Control panel
1.
Download Update
The panel will retrieve the most recent version of the software from the GEA server and automatically save it to the IPC Download Folder on the panel.
2.
Back up to USB
A back up of the current software loaded on the panel will be saved to the attached USB. The back
up folder will be saved to the GEA RT folder. If no such folder exists, one will be created automatically. The back up folder will be named with the project number.
3.
Back up to Panel
A back up of the current software loaded on the panel will be saved to the IPC Back up Folder.
4.
Restore Program
This button is only enabled if a back up file is selected from the table using the check boxes on the
far right of each row. Touching it will cause the selected program to be loaded onto the panel.
→Update/Back up Configuration
The table in the lower portion of the screen, shown below, displays all available configuration files currently existing on the panel or an attached USB. The table displays an icon indicating the file location,
the project number and the version number of each configuration. The buttons displayed to the right of
the table are used to update or back up the configuration.
90GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
fig.91:Update/Back up configuration display
1.
Back up to USB
A back up of the current configuration loaded on the panel will be saved to the attached USB. The
back up folder will be saved to the GEA RT folder. If no such folder exists, one will be created automatically. The back up folder will be named with the project number.
User interface
File Manager
2.
Back up to Panel
A back up of the current configuration loaded on the panel will be saved to the panel.
3.
Restore Configuration
This button is only enabled if a back up file is selected from the table using the check boxes on the
far right of each row. Touching it will cause the selected configuration to be loaded onto the panel.
4.
Delete Configuration
This button is only enabled if a backup file is selected from the table using the check boxes on the
far right of each row. Touching it will cause a message box to appear which will prompt the user to
confirm the delete. Touching Yes will cause the selected configurations to be removed from the
selected location.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201691
User interface
File Manager
2.13.4System Tab
Instruction Manual | GEA Omni™
Control panel
fig.92:System tab display
This tab is used to back up or restore all files on the panel or set the panel to its factory default settings.
92GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
→Update/Back Up System
The table in the upper portion of the screen, shown below, displays all existing system backup data
stored on a connected USB. The table displays the project number and date of the file. The buttons displayed to the right of the table are used to create or load a system back up.
fig.93:Update/Back up system display
1.
Back Up System
This button will save all panel data files to an attached USB. The files will be saved in a System
Backup folder located in a subfolder of the GEA RT folder corresponding to the project number of the
panel. If any or all of these folders are not present, they will be created automatically.
User interface
File Manager
2.
Restore System
This button is only available if a system back up is selected from the table using the check boxes in
the far right column. Touching it will cause the system to replace its current data files with those
stored in the selected back up.
Hint!
Restoring the system may cause data loss. Ensure that a system backup has been
saved prior to restoring the system.
→Factory Default Files
The table in the lower portion of the screen, shown below, is used to restore the panel to its factory
default settings. The system will search an attached USB for any factory default files, containing the
extension .ofds, and will display any such files in the table.
fig.94:Factory default files display
The user may select a factory default file using the check boxes in the rightmost column of the table. As
long as at least one file is selected, the Upload Factory Default Files button will be enabled. Touching it
will load the chosen defaults in place of the corresponding files on the panel.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201693
User interface
File Manager
2.13.5Apps Tab
Instruction Manual | GEA Omni™
Control panel
fig.95:Apps tab display
This tab allows the user to download GEA applications to an attached USB so they may be installed on a separate PC. Each button will copy the installer for the chosen application to the USB. The upper button corresponds
to the GEA OmniLink™ (Section 2.9, Page 58), and the lower button corresponds to the GEA OmniHistorian™
(Section 2.10, Page 61).
94GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
Configuration
2.14Configuration
The Configuration screen is used to modify system options for either the panel as a whole or individual devices
or sensors. If a change will invalidate a portion of the associated drawings, a notification will be triggered reminding the user to contact GEA for revised drawings.
2.14.1System Tab
fig.96:System tab display
This tab contains a tile display used to select which set of options the user wishes to modify. The first tile corresponds to the configuration options of the panel as a whole and will display the project number and customer
name. Subsequent tiles correspond to individual devices controlled from the panel. When a tile is clicked, it will
bring up a scrollable screen containing all of the configurable options for the given system or device. Only a user
with admin level permissions may change these options, and only while no compressors are running.
For more information on individual configuration options, refer to Section 3.8, Page 183.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201695
User interface
Configuration
2.14.2Sensors Tab
Instruction Manual | GEA Omni™
Control panel
fig.97:Sensors tab display
This tab is used to adjust the range of sensors monitored by the panel. The table is divided into nine columns.
The leftmost column contains an icon that indicates whether the chosen point is an input or output. A green
arrow pointing to the right indicates that the point is an input, and a blue arrow pointing to the left indicates that
the point is an output. The remaining channels are detailed below.
1.
Channel
The text in this column indicates the slice number and channel that the chosen point occupies in the I/O system.
2.
Description
This column contains the name of the chosen point.
3.
Min
This column contains the lowest allowable value for the chosen point during normal panel operation.
4.
Measured
This column contains the calibrated value read from or transmitted to the chosen point.
5.
Max
This column contains the highest allowable value for the chosen point during normal panel operation.
6.
Raw Scaled
This column contains the Raw Signal received by associated sensor scaled between the selected minimum
and maximum values.
7.
Offset
This column contains the value that is added to the reading displayed in the Raw Scaled column to obtain
the measured value for the sensor.
8.
Raw Signal
This column contains the unscaled value received by the sensor.
96GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
User interface
Panel Settings
Touching a cell in the Min and Max columns will bring up a sub screen which will allow the user to change the
range measured by the associated sensor. The Measured column is used during the calibration process for the
sensor. For more information on calibrating specific types of sensors, refer to Chapter 5, Page 225.
2.15Panel Settings
The Panel Settings screen is used to customize the appearance and display of the GEA Omni™ panel. The
options are divided across four tabs which are detailed below.
2.15.1Localization Tab
fig.98:Localization tab display
This tab contains options that may be changed to make the panel more convenient to use based on panel location. There are seven sections as detailed below.
1.
Language
This section contains a single drop down list containing all supported languages. A change in this field will
trigger a corresponding change to all of the text within the panel.
2.
Units
This section contains three drop down lists, one each for pressure, temperature and length. The selections in
these fields will change the units displayed after any value of the appropriate type.
3.
Date and Time
This section contains two drop down boxes which may be used to change the current date and time displayed in the bottom right hand corner of the panel. The drop down box on the left is used to input the current date and the drop down box on the right is used to enter the current time.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201697
User interface
Panel Settings
4.
Date and Time Format
Instruction Manual | GEA Omni™
Control panel
This section contains two drop down lists which may be used to select how the date and time is displayed on
the panel. The list on the left is used to select whether the date is displayed mm/dd/yyyy, dd/mm/yyyy or
yyyy/mm/dd, and the list on the right is used to select whether the time is displayed in twelve or twenty-four
hour format.
5.
Theme
This section contains a single drop down list which is used to select the color display for the panel. The
default choice, Indoor/Dark displays white text on a dark gray background, while Outdoor/Light displays
black text on a white background.
6.
Screen Saver Timeout
This section contains a single drop down list which is used to select the amount of time that the panel may
remain idle before switching to the screen saver. The options are 1, 5, 10, 15 and 20 minutes. This option
may only be changed by a user with service level or higher permissions.
7.
Historical Trend Interval
This section contains a single drop down list which is used to select for what amount of time the panel will
wait before adding a new set of data to the historical display. The options are 1, 2, 5 and 10 minutes. This
option may only be changed by a user with service level or higher permissions.
2.15.2Users Tab
fig.99:Users tab display
This tab displays information regarding all users that may log into the panel. It also contains functionality to add
or remove users.
98GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Instruction Manual | GEA Omni™
Control panel
1.Create New User
The fields on the far right of the screen may be used to enter information for a new user. Each user will
be given a unique User Name and may be assigned a unique Email Address and Password. The access
level selected will be either Service or Operator. Admin access level may not be created. If the user level
is set to Operator, three additional fields will be displayed which are used to select to what degree the
user may control the system. Service users automatically have full access to all three of these options,
so these fields will not display if the access level is set to Service.
•
Start/ Stop Access
This field contains a drop down list which is used to select whether the user has permission to start
or stop the compressor. It may be set to No Access, Stop Access, Start and Stop or Start and Stopwith Capacity Control Access. The default option is Start and Stop with Capacity Control Access.
•
Set Point Access
This field contains a switch which is used to toggle whether or not the user is permitted to access or
change the control set points of the panel. By default, this option is set to true.
•
Clear Motor Start Timers
This field contains a switch which is used to toggle whether or not the user is permitted to reset the
built in delay timers before the motor starts. By default, this option is set to false. Touching the SaveUser button below the fields will create a user using the information in the fields and add it to the
table of current users.
Touching the Save User button below the fields will create a user using the information in the fields and
add it to the table of current users.
User interface
Panel Settings
2.Current Users
This section contains a table displaying all users that may log in to the panel. By default, there are two
users: Service and Operator, though any custom users added in the manner described above will be displayed in the table as well. The table contains three columns; the leftmost containing the name of the
user, the middle containing the access level and the rightmost containing a checkbox which is used to
select a user to be edited or removed. The rows corresponding to the two default users do not contain
the checkbox in the leftmost column because they may not be modified or removed. When the checkbox
corresponding to a user is selected, the fields used to create a user will automatically be filled in with the
corresponding information. This will also enable the Save User and Delete User buttons. Any changes
made to a custom user may be confirmed by touching the Save User button. Touching the Delete User
button will remove the selected user from the table entirely. Only custom users may be deleted or have
their access level modified.
3.User Timeout
This section is used to select whether the panel will automatically log a user out after a period of inactivity. User timeout is not set by default, and must be enabled with the Timeout Enabled switch shown to
the right of the screen. Toggling the switch on will enable the field shown below it.
•
User Access Timeout
This field contains a drop down list which is used to select the amount of time the panel must remain
idle before the current user is logged out.
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.201699
User interface
Panel Settings
2.15.3Network Tab
Instruction Manual | GEA Omni™
Control panel
fig.100: Network tab display
This tab is used to display the status of the panel’s network connections. It also allows the user to modify certain
settings. These options may only be modified by a user with service level or higher permissions.
1.
Customer Network
This section displays the current network connection, if applicable. The switch displayed in this section is
used to select whether DHCP, Dynamic Host Configuration Protocol, is enabled. If DHCP is enabled, the
panel will automatically search for a network connection and will fill in the IP Address, Subnet Mask, Gate-way and DNS Server fields without user input. If DCHP is disabled, the values in these fields must be
entered manually. If the panel successfully connects to the chosen network, the title of this section will display Customer Network – Connected. Otherwise, it will display Customer Network – Disconnected.
Hint!
The IP Address Range 192.168.254.0 through 192.168.254.255 is reserved for the I/O Ethernet
network Setup. To ensure the functionality of both networks, do not use this range for the customer LAN Connection.
2.
I/O Network
This section is used to display the IP Address and MAC Address of the panel’s I/O network coupler, if applicable. These values may not be modified and are only visible for users with access level of Service or
higher. If the panel successfully connects to an appropriate network location, the title of this section will display I/O Network – Connected. Otherwise, it will display I/O Network – Disconnected.
3.
VNC Server Settings
This section is used to select whether a user may remotely log into the panel using VNC and whether a
password is required to do so. This section contains two switches. The switch on the left toggles whether
VNC client access is enabled for the panel and the switch on the right toggles whether a password is
required. If a password is required, it may be changed by typing a new password into the Password and
Confirm Password fields and touching the Change Password button below.
100GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.