GEA Grasso V 300, Grasso V 300T, Grasso V 450, Grasso V 600, Grasso V 450T Installation And Maintenance Instructions Manual

...

Reciprocating Compressors for industrial refrigeration

GEA Grasso V
Installation and Maintenance instructions
0089288gbr_11
COPYRIGHT
LEGAL NOTICE
All Rights reserved. No part of this publication may be copied or published by means of printing, photocopying, microfilm or otherwise without prior written consent of GEA.
This restriction also applies to the corresponding drawings and diagrams.
This publication has been written in good faith. However, GEA cannot be held responsible, neither for any errors occurring in this publication nor for their consequences.
2 30.10.2017
0089288gbr_11
SYMBOLS USED
Danger
Stands for an immediate danger leading to severe physical injuries or death.
► Description for avoiding the danger.
Warning!
Stands for a potentially dangerous situation leading to severe physical injuries or death.
► Description for avoiding the dangerous situation.
Caution!
Stands for a potentially dangerous situation which could lead to minor physical injuries or damage to property.
► Description for avoiding the dangerous situation.
Notice!
Stands for important information that must be observed for the intended use and function of the product.
► Description of the required action for the intended function of the product.
SAFETY INSTRUCTIONS
Hint!
This manual must be carefull read and understood prior to installing and servicing the compressor (package)
Safety
This manual is written with great care, but the contractor/installer is held responsible to examine this information and to take care of possible additional and/ or deviated safety measures.
Safety instructions
It is the task of the contractor/installer to inform and explain to his client the operation of the compressor (Package).
Do respect all federal, state or local safety regulations/legislations during installing, connecting and operating this compressor (package).
Construction changes
Warning!
In compliance with the regulations of the Pressure Equipment Directive it is mandatory that no changes be made to the construction of pressurised parts such as the crankcase housing, suction filter housing etc.
0089288gbr_11
30.10.2017 3
Installer oriented information
The compressor (package) is filled with nitrogen to prevent penetration of moisture. Therefore, keep the compressor closed until the compressor (package) is being installed.
Warning!
The compressor is not filled with oil.
Hint!
After the successful initial run of the compressor (package) the warranty chart must be filled in and returned to Grasso. A warranty chart is attached to each compressor.
4 30.10.2017
0089288gbr_11
PREFACE
General
1.
All documentation can be downloaded via our web site.
2.
GEA technical manuals includes “generic paragraphs”; this means that it can occur that not all data as described is relevant for the current compressor series as mentioned in this manual. (For instance, not all compressor series are suitable for all mentioned refrigerants or not all compressor series includes two-stage compressors)
Directives
Equipment is based on Pressure Equipment Directive (PED 97/23/EG) regulations and according to Machine Directive (MD 2006/42/EG) regulations.
The applied standards are:
NEN-EN-IEC 60204, NEN-EN-ISO 12100, NEN-EN-ISO 13857, NEN-EN 378
0089288gbr_11
30.10.2017 5
6 30.10.2017
0089288gbr_11
CYLINDER NUMBERING, BOOSTER AND SINGLE-STAGE OPERATION
Cylinder numbering
Fig.1: Example cylinder numbering 6 cylinder compressor
Booster or single-stage operation
1.
Booster operation applies if condensing temperature < +5 oC
2.
Single-stage operation applies if condensing temperature >= +5 oC
0089288gbr_11
30.10.2017 7
8 30.10.2017
0089288gbr_11
GENERAL INFO
Main setup data
Description
Start frequency max. 6 starts per hour
Time interval between stopping
and re-starting
Time interval between starting
and re-starting
Time interval between loading
and unloading
Oil level 25-75% crankcase sight glass
Min. oil temperature
Max. oil temperature Refer to oil selection table/applied type of oil
Control oil pressure suction pressure + 8 bar (g)
Lubricating oil pressure
difference
Max. discharge temperature 170 °C
Min. suction pressure 0.3 bar(a)
Max. intermediate pressure
Max. suction pressure
Pdischarge - Psuction ≤ 25.0 bar (g) ≤ 19.0 bar (g)
Superheat >0 K
Oil discharge - running in -
filter
Oil discharge filter Supplied loose; replacement for factory mounted running in filter
Grasso V 300 (T) .. V 600 (T) Grasso V 700 (T) .. V 1800 (T)
> 30 oC and > P
between 1.3 and 4.5 bar Setting approx. 2.0 bar (g)
8.5 bar (a) 7 bar (a)
Factory mounted; to be replaced after max. 100 running hours by “normal” oil discharge filter element
Value
min. 2 minutes
min. 10 minutes
min. 3 minutes
saturated crankcase pressure
+ 15 K
Remark
The NO-solenoid has to be
de-energised 20 seconds
after starting the compressor
motor to enabel the motor to reach the minimum speed and the compressor to develop the
required oil pressure.
For continuous minimum part-
load (i.e. more than 30
minutes) consult Grasso.
Adjust the steps between up
and down loading, in such a
way that the system is running
stable.
Indicated minimum value is the
lowest oil temp. at which the
compressor is allowed to be
started.
Required oil viscosity;
≥ 10 cSt during operation at
location of bearings.
The maximum temp. depends on the operating conditions of
the compressor, the oil type
used and (A minimum actual oil
viscosity of 10 cSt in the
bearings is always requried;
bearing temp. to determine oil
viscosity is approx. oil
temperature + 15K)
After a mimimum of 15 minutes
running time at an oil
temperature of approx. 50 oC
0089288gbr_11
30.10.2017 9
10 30.10.2017
0089288gbr_11

TABLE OF CONTENTS

1 INSTALLATION AND PREPARATION FOR USE 13
1.1 Running-in oil filter has to be installed after an overhaul or big repair
1.2 INSTALLATION 13
1.2.1 Moving instructions and storage 14
1.2.2 Storage 14
1.2.3 Hoisting and moving instructions 14
1.2.4 Required free space 15
1.2.5 Foundation requirements 16 Concrete structure 16 Anchoring 17 Mounting the base frame on a concrete block 18 Mounting bare compressor on a concrete block 19
1.2.6 Connecting to refrigerating system pipework 20
1.2.7 Connecting the power supply 21
1.2.8 Earthing connections 21
1.2.9 Separately delivered components 21
1.3 PREPARATIONS FOR USE 22
1.3.1 Leak test of compressor and system 22
1.3.2 EVACUATION/DRYING THE REFRIGERATING SYSTEM 22
1.3.3 Initial oil charge 22 Oil quantities 23
1.3.4 Initial refrigerant charge 24
1.3.5 Adjustment of instruments and safety devices 24 CONTROL DEVICES 24 PRESSURE SETTINGS 24 RE-ADJUSTMENT OF OIL PRESSURE REGULATORS 25
1.3.6 Checking direction of rotation of motor shaft 27
1.3.7 Installing the drive guards (if present) 27
1.3.8 Initial oil warm up 27
1.3.9 Initial start-up 27 Limitations of part load operation and start-up 27 WIRING LOGIC NORMALLY OPEN UNLOADED START SOLENOID 27 Frequency controlled compressor 28 Pre-start check list 28
1.3.10 Starting and stopping procedures 28 First start 28 Restart 29 Restart after a short standstill period of time (less than 1 month) 29 Restart after a long standstill period of time 29 Stopping the compressor 30
2 INSPECTION AND TROUBLE SHOOTING 31
2.1 Periodical inspection 31
2.2 Survey of periodical inspections 31
2.2.1 Check list periodical inspection 32
2.3 STEPS FOR LONGER SHUT-DOWN PERIODS (> 6 months) 32
2.4 LUBRICATION DATA 33
2.4.1 Topping up oil with compressor operating 33
2.5 EVACUATION, LEAK TESTING AND START-UP OF THE COMPRESSOR/PACKAGE 33
2.5.1 EVACUATION OF REFRIGERANT BEFORE SERVICING 34
2.5.2 LEAK-TIGHTNESS AFTER SERVICING 34
2.5.3 EVACUATION AFTER SERVICING 34
2.5.4 START-UP AFTER SERVICING 34
2.6 DRAINING AND CHANGE OF OIL 35
2.7 REPLACEMENT OF OIL FILTERS 35
2.8 DISMANTLING, INSPECTION AND RE-ASSEMBLY OF SUCTION AND DISCHARGE VALVES 36
2.9 COMPRESSOR PURGING 36
2.10 TROUBLESHOOTING TABLE GRASSO RECIPROCATING COMPRESSORS 37
3 MAINTENANCE 40
3.1 Spare parts manual 40
3.2 Post start-up maintenance 40
13
0089288gbr_11
30.10.2017 11
3.3 First maintenance 40
3.4 SMS FACTOR 41
3.5 Legend 41
3.6 Description Maintenance ABC when GMM is applied 42
3.6.1 Compressor 43
3.6.2 Package components 44
3.7 Grasso V 300 .. 1800 (T), WITHOUT GMM 46
4 APPENDIX; Product Information (PI)
4.1 GRASSO MAINTENANCE MONITOR
4.2 GENERAL LIMITS OF OPERATION GRASSO V 51
4.3 STARTING UP OF TWO-STAGE COMPRESSORS 52
4.4 DIAGRAMS SINGLE STAGE AND BOOSTER 54
4.5 DIAGRAMS TWO STAGE 55
4.6 LUBRICATING OILS (choice and recommendations) 58
4.6.1 STRONGLY RECOMMENDED OIL TYPES 58
4.6.2 ACCEPTED NH3 OIL TYPES 59
4.7 Pre-lubrication oil system 60
50
50
12 30.10.2017
0089288gbr_11
INSTALLATION AND PREPARATION FOR USE
Running-in oil filter has to be installed after an overhaul or big repair

1 INSTALLATION AND PREPARATION FOR USE

1.1 Running-in oil filter has to be installed after an overhaul or big repair

Hint!
This is why and when the running in oil filters are required:
Warning!
A running in oil filter has always to be installed after an overhaul or big repair for the 1st 100 hours of operation!
The oil and oil oil filters have to be replaced by new oil and filters.
Due to running-in wear of liners and piston rings, it's normal that the oil becomes grey during the 1st 100 operating hours.
After 100 operating hours, the oil could slightly become clear again.

1.2 INSTALLATION

Warning!
The compressor is not charged with oil, therefore, DO NOT start the compressor before it has been installed and prepared according to Grasso’s instructions.
This section contains instructions for the proper installation of a Grasso compressor (package). Before the compressor (package) is ready for the initial start up, the installation instructions in the following paragraphs must be followed:
1.
The Compressor (Package) should be levelled and securely anchored to the foundation.
2.
All piping should be completed.
3.
The system and the compressor are to be pressure tested for leaks (see. Section 1.3.1, Page 22)
4.
The system should be evacuated to remove air and moisture.
5.
The electric wiring should be completed as per wiring diagrams. Do not energise the main power control cabinet until oil is added and the direction of rotation has been checked.
6.
The compressor is to be filled with the correct type and amount of lubricating oil and has to be pre-lubricated (Refer Section 4.7, Page 60) before the first start.
7.
‘Open compressors’ only;
7.1
Open compressors;
The drive system should be installed.
7.2
(Semi) hermitic compressors;
Mark R-S-T-N power supply in the terminal box of the motor.
0089288gbr_11
30.10.2017 13
INSTALLATION AND PREPARATION FOR USE
INSTALLATION
8.
The system should be charged with the correct amount of refrigerant.
9.
The oil should be warmed up above minimum start up oil temperature (see "Product Information").
10.
The control cabinet should be energised to check the package controls.
Hint!
Do not forget to charge the oil separator (if present) initially with oil, to the level of the float assembly

1.2.1 Moving instructions and storage

For loose component or compressor package weights, refer either to the relevant component type plate or package lay-out or to the suppliers document. For bare compressor weights, see "Product Information".
Caution!
Every precaution must be taken while moving the package to its final location. Pushing, pulling or climbing on any package component or piping, can easily create damage.

1.2.2 Storage

The compressor (package) is filled with dry nitrogen. Keep the system closed until the package is installed. If the compressor (package) is stored, it should be kept at all times in a dry location to prevent corrosion damage. If the compressor (package) is to be stored for a prolonged period of time, it should be checked weekly to ensure that the holding charge of dry nitrogen remains above atmospheric pressure.

1.2.3 Hoisting and moving instructions

Fig.2: Hoisting a compressor package
14 30.10.2017
0089288gbr_11
INSTALLATION AND PREPARATION FOR USE
INSTALLATION
Packaged base frame:
The only places that can be used for safe hoisting of the package are the four hoisting eyes on the steel base frame as shown in the above figure. Prior to hoisting a compressor package with a V-belt drive arrangement, the factory mounted drive guard has to be removed. Attach spreader bars to the slings so as to prevent damage to piping and components.
Warning!
DO NOT use the compressor or motor or oil separator hoisting eyes to move the package! These hoisting eyes are intended for lifting loose components only and not for the entire package!
Bare compressor or loose components:
Determine the dead weight of the particular component (see "Product Information (ED)"), prior to moving a bare compressor or loose component. Use the hoisting eyes only, DO NOT sling from other compressor parts (see Figure 3, Page 15).
Fig.3: Hoisting angle
Moving by fork-lift truck
The bare compressor or package can be transported with a fork-lift truck with the forks spread as much as possible between the skids. To simplify moving, the 2 wooden transport beams must still be mounted underneath the base frame and stored in this way, until the package is positioned above its approximate location.

1.2.4 Required free space

For easy operating, servicing and maintenance access, the compressor (package) should be installed with sufficient free space around it.
Hint!
Refer to “Product Information“ for minimum requirements.
0089288gbr_11
30.10.2017 15
INSTALLATION AND PREPARATION FOR USE
INSTALLATION

1.2.5 Foundation requirements

Hint!
Compressor (package) has to be mounted on a concreted block. On request, Grasso can calculate the exact dimensions of the concrete block, based on the compressor size and operating conditions.
This paragraph covers measures to be taken for a compressor (package) mounting on a concrete block.
Two foundation arrangements are described:
1.
Compressor package with steel base frame mounted on a concrete block.
Following base frames are possible;
1.a
Frame designed for mounting on concrete block.
For more instalation details refer to; Section 1.2.5.1, Page 16, Section 1.2.5.2, Page 17, Section 1.2.5.3, Page 18, Section , Page 19, Section , Page 19.
1.b
Frame designed for mounting on vibration dampers.
For more details in case mounting base frames on vibration dampers is applied, refer to separate instruction sheet and other order documentation like package drawing, supplied with the compressor package and consult Grasso if required.
2.
Bare compressor direct mounted on a concrete block via grouted anchors.
For more installation details refer to; Section 1.2.5.1, Page 16, Section 1.2.5.2, Page 17, Section 1.2.5.4, Page 19.
1.2.5.1 Concrete structure
Fig.4: Concrete block
1 Cork board
2 Concrete base
3 (Concrete) Floor
4 Sand
The concrete block for compressor and motor or compressor package should have a profile as illustrated in Page 16 and made according to the following recommendations:
16 30.10.2017
0089288gbr_11
INSTALLATION AND PREPARATION FOR USE
INSTALLATION
The concrete block should be set on firm footings or on a floor capable of carrying the weight of the concrete block and capable of absorbing the free forces and gas forces of the compressor during operation. The ground under the concrete block should be horizontal and flat.
The top surface of the block should be level and even.
There should be sufficient free space around the block to install corkboard (or similar).
The block should be provided with anchor bolt recesses or holes according to the anchor bolt spacing as per package lay out drawing.
Fig.5
It is recommended to consult a concrete specialist/ constructor for the following items:
1.2.5.2 Anchoring
After the concrete block has cured the anchors should be installed as shown above and in case of a package in accordance with the package lay out drawing. Templates should be made to locate the anchor bolts or chemical anchors to match the holes in the bottom flange of the base frame.
Grout the mortar according to the supplier instructions. Install chemical anchors as illustrated in Figure 6, Page 18 and according to the instructions of the anchor supplier.
A Chemical anchor
B Grouted anchor, grounded to reinforcing steel
The compound of the concrete with/without reinforcement.
The exact grouting depth (dependent on the soil conditions).
Installing foundation onto an existing floor, with sealing corkboard or vibration isolators.
0089288gbr_11
30.10.2017 17
INSTALLATION AND PREPARATION FOR USE
INSTALLATION
Fig.6: Anchoring details
A Drilled chemical anchor (M20)
B Grouted anchor recesses (M20)
1 Installed chemical anchor before placing the base frame
2
3 Drilling angle
Installing chemical anchor after placing the base frame (base frame cannot be removed
easily)
1.2.5.3 Mounting the base frame on a concrete block
General
After the space between base frame and concrete base has been filled-up with a filling grout, the package base frame must be secured tightly to the foundation block or floor.
18 30.10.2017
0089288gbr_11
Levelling the base frame
INSTALLATION AND PREPARATION FOR USE
INSTALLATION
Fig.7: Grouting details
1 Self-levelling grout
2 Adjusting bolts (4x)
3 Washer
4 Temporary barrier strip around and inside frame
5 Complete cured concrete block
6 Grout layer
Finishing with a self-levelling grout
After the anchor filling mortar has completely cured the frame should be levelled with a space between block and lower frame flange of 3 - 5 mm*. This space is necessary for levelling using the base frame adjusting bolts with metal washers (supplied separately). The base frame should be levelled on each frame side. Adjust the frame on each adjusting place until all frame sides are horizontal.
This space largely depends on the sort of grout or mortar used. Determine this space according to the instructions of the grout or mortar supplier.
After levelling has been completed the adjusting bolt ends must be greased to avoid bonding to the self-levelling grout. The space between concrete block and frame must be completely filled with the self-levelling grout to ensure that the complete bottom surface of the base frame will be supported. Therefore, it is not allowed to use shims between concrete base and base frame.
Grouting must be carried out in accordance with the instructions provided by the grouting supplier. After complete de-aeration of the grouted layer, secure the base frame by tightening the anchor bolt nuts and remove all adjusting bolts. At this stage the drive system can be installed. These (accessories) installation instructions can be found in the order manual.
1.2.5.4 Mounting bare compressor on a concrete block
0089288gbr_11
30.10.2017 19
INSTALLATION AND PREPARATION FOR USE
INSTALLATION
If base frame is not applied the approximately the same procedure of levelling the base frame has to be applied for the bare shaft compressor (refer Section 1.2.5.3, Page 18).
The mounting surfaces of the compressor feet must be level without any deviation and projecting at least 10 mm above the concrete base.
Fig.8: Grouting details of bare compressor on concrete block
1 Self leveling grout
2 Foundation anchor
3 Layer of self leveling grout (10 - 15 mm)
4 Temporary barrier strip aroud each compressor foot
5 Complete cured concrete block
CF Compressor foot
WL
WC

1.2.6 Connecting to refrigerating system pipework

Warning!
DO NOT ground through the compressor when arc welding
After the compressor (package) has been levelled and secured to the foundation, the system piping may be connected. The suction line(s) and discharge line(s) should be installed and supported such that there is no load exerted on the compressor. The size and location of the suction and discharge connections, can be found in the "Product Information" (bare compressor) and in case of a package, the package lay out drawing.
Legend
Width of grout layer
(WL-WC > 40 mm)
Width of compressor foot
(WL-WC > 40 mm)
Hint!
If an oil rectifier system is applied in the refrigeration system, the oil return line must be connected to the oil return connection (see "Product Information").
20 30.10.2017
0089288gbr_11
Suspension of system pipework
To eliminate vibration transmission to the system piping, the following is recommended:
Install all piping free of tension.
Secure the piping by clips or brackets in two directions.
Install (stop) valves, piping and accessories such, that there is no load exerted on the compressor.

1.2.7 Connecting the power supply

Information about further electrical connections to be made (e.g. crankcase heater, drive motor starting equipment, thermal protection of drive motor, automatic start/ stop and other external electrical devices) can be found in the plant manual (not supplied by Grasso).

1.2.8 Earthing connections

INSTALLATION AND PREPARATION FOR USE
INSTALLATION
Grasso compressors and packages are equipped with litz-wires and earth connecting points.
To avoid leakage current flowing through the components, disconnect all litz­wires when arc-welding. After all installation functions are completed, reconnect the litz-wires and ground the package to earth.

1.2.9 Separately delivered components

Hint!
Check whether the sets/parts/components belonging to this compressor are supplied loose! (Refer to order confirmation)
Mount these separately delivered sets, components and/or parts, according to the instructions as supplied with this compressor (package).
0089288gbr_11
30.10.2017 21
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE

1.3 PREPARATIONS FOR USE

After the Compressor (Package) has been installed (excluding final connection of drive device), the following actions should be followed in the order given:

1.3.1 Leak test of compressor and system

The compressor (package) has been pressure tested prior to leaving the factory. In case an additional leak test is required, this test is should be carried out with dry nitrogen.
Hint!
DO NOT add oil to the compressor prior to pressure testing
A system leak test should be carried out over 24 hours to ensure that the system is tightly sealed.
Record during the pressure test, the pressure, ambient temperature and outside temperature. During the initial 6 hours a pressure drop of 2% is permissable. With respect to temperature variations, no further pressure loss should be detected in the remaining 18 hours.

1.3.2 EVACUATION/DRYING THE REFRIGERATING SYSTEM

For evacuation of compressor only, refer to Section 2.5, Page 33
Procedure to evacuate and to dry a system:
i.
STATUS: System is filled with nitrogen and no oil has been added (oil prevents any trapped moisture from boiling off).
ii.
Verify that all valves in that part of the system to be evacuated are opened (refer also to the plant manual).
iii.
Connect vacuum pump to the evacuation/purging valve(s) of the compressor (for location of these valves refer to the "Product Information" or to a connection as mentioned in the plant manual and evacuate the system to approx. 6 mBar.
iv.
Break vacuum by charging dry nitrogen into the system.
v.
Repeat step iii, "Connect vacuum pump ...".
vi.
Wait approx. 24 hours.
vii.
If pressure has increased (system still contains moisture), repeat steps iv, and vi. Otherwise, continue with the "Initial oil charge" procedure.

1.3.3 Initial oil charge

22 30.10.2017
0089288gbr_11
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE
Warning!
Oil charging via the suction line of the compressor is not allowed.
Used or filtered oil should NEVER BE added to a compressor under any circumstance.
Use only new oil as selected from the Grasso oil table. (Refer Chapter 4, Page 50)
Procedure:
i.
STATUS: System is dried and still evacuated.
ii.
Charge the oil separator (if present) initially with oil .
iii.
Close suction and discharge stop valves of compressor and oil return line of oil separator (if present).
iv.
Charge the compressor crankcase with oil via the oil charge valve.
Warning!
1.3.3.1 Oil quantities
Number of cylinders
Pre-lubrication just before the first start is obligatory.
Hint!
Filling of the afore mentioned components is also possible by means of a separate oil filling pump via the oil charge valves mounted onto the oil pump housing.
Shaft seal housing incl.
internal circuit of
crankshaft
V 300(T)
V 450 23.9 / 17.6
V 600(T) 34.6 / 25.5
V 700(T) 22.4 / 16.5
V 1100(T) 31.9 / 23.5
V 1400(T) 45.6/ 33.6
V 1800(T) 55.1/40.6
0.7 1.5 0.9
Oil filter
Oil pump
Crankcase
(max/min)
17.0 / 12.5
0089288gbr_11
30.10.2017 23
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE
Fig.9: Pre-lubrication valve (P), Oil control pressure regulator (B)
Caution!
Pre-lubrication just before the first start is obligatory.

1.3.4 Initial refrigerant charge

Refrigerant charging should be done in accordance with the plant manual by qualified refrigeration engineers.

1.3.5 Adjustment of instruments and safety devices

1.3.5.1 CONTROL DEVICES
Hint!
Refer to separate user manuals, in case an electrionic control device is installed.
1.3.5.2 PRESSURE SETTINGS
Pressure safety limit switches
Suction pressure *
Suction and
intermediate
pressure
Discharge pressure
Page 24
Setting
1
Min. 0.3 bar(a)
Setting Max.= refer to Product Information (PI)
Setting
Max.
5oC below design evaporating temp.
5oC above design condensing temp.
26 bar(a)
Grasso V 300(T) Grasso V 450(T) Grasso V 600(T)
1 Settings Pdischarge - Psuction must never exceed max. value as mentioned in Product Information
24 30.10.2017
0089288gbr_11
INSTALLATION AND PREPARATION FOR USE
Pressure safety limit switches
24 bar(a)
Lubrication oil
pressure difference
Lubrication oil pressure
difference *
Control oil pressure difference Setting 8.0 bar
Setting Min. =1.3 bar
Oil pressure regulators
Setting 2.0 bar
2
Min. and max.
at 50 oC oil temp.
1.3.5.3 RE-ADJUSTMENT OF OIL PRESSURE REGULATORS
It is possible that after the compressor has been installed, the lubrication oil pressure regulator needs to be adjusted.
PREPARATIONS FOR USE
Grasso V 700(T) Grasso V 1100(T) Grasso V 1400(T) Grasso V 1800(T)
Min.=1.3 bar
Max.=4.5 bar
Location pressure regulators (control and lubricaton)
Fig.10: Oil lubrication pressure regulator (A)
2 The oil pressure regulator is adjusted at the works, but it may occur that this setting should be corrected
during the initial run and also if the value <1.5 or >2.5 bar. The re-adjustment procedure is given in section “Re-adjustment of oil pressure regulator.
0089288gbr_11
30.10.2017 25
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE
Fig.11: Oil control pressure regulator (B), Pre-lubrication valve (P)
Caution!
Oil charge valve (P) for lubrication circuit. this connection to be used for pre-lubrication of the oil circuit
Re-adjustment procedure:
i.
Run the compressor for 15 minutes until the crankcase oil is at its stable operating temperature [Toil] of 50 oC and check:
1) The lubricating oil pressure difference (A)
2) The control oil pressure difference (B)
After the initial run the oil pressure differences should be slightly higher.
ii.
Determine the lubricating oil pressure difference (difference between the pressure gauges of the oil and suction or [dOil]).
iii.
Determine the control oil pressure difference (difference between the pressure gauges of oil pump discharge 3 and suction.
iv.
Remove the plug of both oil pressure regulators if the pressures need to be re-adjusted.
v.
Turn the slotted pin with a screwdriver clockwise or counter clockwise for a higher or lower oil pressure respectively, until the required control &
lubricating oil pressure differences have been achieved 4.
vi.
Replace both plugs.
Hint!
If the valve lifting fails, check the control oil pressure regulator!
3 To be measured by means of a special control oil pressure gauge to be connected on the oil
pump.
4 Re-adjusting one regulator will affect the other one, so be sure that both regulators are
properly (re-)adjusted.
26 30.10.2017
0089288gbr_11

1.3.6 Checking direction of rotation of motor shaft

Prior to installing the intermediate coupling element or V-belts, the direction of rotation of the motor shaft must be checked. The direction of rotation can be determined from the arrow-sticker at the oil pump.

1.3.7 Installing the drive guards (if present)

Only after the compressor is ready for the initial startup! Refer to the drive guard installing procedures included in the order documentation.

1.3.8 Initial oil warm up

Prior to the initial start-up, the crankcase heater (if present) must be energised. For the min. oil temperature refer to “Product Information (PI)“.

1.3.9 Initial start-up

1.3.9.1 Limitations of part load operation and start-up
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE
The capacity control serves to adapt the compressor capacity at any moment as closely as possible to the refrigerating capacity. In order to adjust the capacity, a number of cylinders can be put in or out of action either individually or collectively by means of solenoid valves.
Warning!
Due to start-up limitations and to limitations of part load operation it may be that not all available part load steps are allowed under certain conditions. Use of incorrect control steps can damage compressor and/or components.
For a detailed description about start-up and part load limitations refer to GEA Grasso Selection Software.
1.3.9.2 WIRING LOGIC NORMALLY OPEN UNLOADED START SOLENOID
1.
If compessor is NOT running then NO-solenoid is not energised.
2.
Energise the NO-solenoid 10 - 20 seconds before starting.
3.
If compressor starts then NO-solenoid is energised and de-energised by means of an auxiliary time relay.
4.
Ensure that the NO-solenoid valve is not de-energised until the minimum allowed compressor speed has been achieved and the specified lubrication oil pressure has been established.
5.
Energise the NO-solenoid 5 seconds before stopping until the compressor is stopped completely.
0089288gbr_11
30.10.2017 27
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE
1.3.9.3 Frequency controlled compressor
Hint!
In case of frequency controlled compressors, a separate instruction
00.87.041 is required. If you don’t have this instruction consult Grasso.
1.3.9.4 Pre-start check list
The following Paragraph covers only the initial start of the compressor and not the complete refrigeration plant.
Be sure that all necessary system valves are open and that the refrigeration system is ready for start up. Use the following check to guarantee that no items of importance regarding the compressor (package) have been overlooked.
i.
System is charged with refrigerant.
ii.
Settings of safety limit switches are adjusted properly.
iii.
Direction of rotation of compressor crankshaft is correct.
iv.
Check capacity control: Set the electrical capacity control to the position of the lowest part load step.
v.
Oil level established in sight glass.
vi.
Stop valves to the pressure gauges are open.
vii.
Suction stop valve is closed (in case the evaporating temperature is much higher than the design evaporating temperature) and the discharge stop valve is open and in case of two- stage compressors that the stop valves in the intermediate circuit lines are open.
viii
Stop valve in the oil return line of the oil separator (if present) is closed.
.
When all items are verified, the compressor (package) is ready for the start-up.

1.3.10 Starting and stopping procedures

Hint!
For all limitations refer to "Main setup data"-overview! The values in the main setup data tables, overrules the values as mentioned in the text.
When starting the compressor a distinction should be made between:
1.3.10.1 First start
1.
Notice "Pre-start check list", also consult the plant manual and verify the following items:
Check the oil temperature (refer to the "Product Information").
Check crankcase oil level (refer to Section 2.4.1, Page 33).
28 30.10.2017
0089288gbr_11
INSTALLATION AND PREPARATION FOR USE
PREPARATIONS FOR USE
2.
Start the compressor and check whether the oil pressure increases.
Warning!
The time interval between stopping and starting should be at least 2 minutes and between starting and re-starting 10 minutes.
3.
Slowly open suction stop valve and watch suction pressure, which may not exceed the max. value.
Warning!
Refrigerant liquid hammer, will damage the compressor; Dry gas (superheat) is always necessary!
4.
In case of electrically operated capacity control:
One or more cylinders will be energized.
5.
Watch maximum allowable motor current (refer to motor type plate).
6.
Watch discharge temperature and max. allowable motor current (refer to motor type plate).
7.
Adjust pressure gauge stop valves, in order to avoid vibration of the pointers. (if present)
8.
Open the stop valve in the oil return line from the oil separator (if present).
9.
After 50 hours of operation retighten the coupling bolts or check and/or correct the tension of the V-belts and retighten the foundation bolts (with due respect to the torque settings given by the supplier of the fasteners!).
1.3.10.2 Restart
Hint!
For the time interval between stopping and starting refer to "Main setup data"-overview.
Proceed to the complete starting procedure like “First start“
1.3.10.3 Restart after a short standstill period of time (less than 1 month)
Refer to Section 1.3.10.2, Page 29.
1.3.10.4 Restart after a long standstill period of time
After a seasonal standstill (1 till 6 months) or maintenance operations;
Warning!
After a standstill period of time more than 1 month, pre-lubrication just before starting is always obligatory. Refer Section 4.7, Page 60
Check settings of control and safety equipment.
Proceed to the complete starting procedure.
0089288gbr_11
30.10.2017 29
INSTALLATION AND PREPARATION FOR USE
Warning!
Restarting compressor after a standstill period of time more than 6 months, consult your supplier. It is recommended to proceed with the initial start up procedure.
1.3.10.5 Stopping the compressor
The compressor can be stopped at any moment, however, consult the supplier if further actions are required.
30 30.10.2017
0089288gbr_11

2 INSPECTION AND TROUBLE SHOOTING

2.1 Periodical inspection

These inspections should be made during the normal shut-down periods as much as possible, so the compressor is always ready to operate when required. If, at that time, the number of running hours slightly differs from the scheduled period below, the inspection should nevertheless be carried out.
In this way it will not be necessary to stop the compressor at inconvenient times.
The frequency of inspections is dependent on the type of installation, operating conditions and local regulations. In the case of automatically controlled plants, the periodical inspection are particularly important. The table below sums up all the points on the compressor that have to be inspected or maintained along with inspection and maintenance frequencies.

2.2 Survey of periodical inspections

Apart from the check points in the table below, the sound produced by the compressor also provides an indication of its mechanical condition. If abnormal sounds are audible, their cause should be traced and removed immediately in order to prevent serious breakdowns.
INSPECTION AND TROUBLE SHOOTING
Periodical inspection
0089288gbr_11
30.10.2017 31
INSPECTION AND TROUBLE SHOOTING
STEPS FOR LONGER SHUT-DOWN PERIODS (> 6 months)

2.2.1 Check list periodical inspection

Check list periodical inspection
CHECK POINTS *
5
FREQUENCY REMARKS
Oil level in crankcase
Colour of the oil
Lubricating oil pressure
difference
Min. control oil pressure
Oil temperature max.
Oil leakage of shaft seal
max.
Suction pressure
Discharge pressure
Suction superheat
Intermediate superheat
Discharge temperature
max.
Oil temperature min.
Condition of V-belts
Adjustment and
operation of pressure
safety switches
Capacity control (if
provided)
Switching frequency of
the compressor
Number of operating
hours
daily
weekly
monthly
Between 25% and 75% height of the sight glass. For topping up oil, refer to Section 2.4.1, Page 33.
The oil should be transparently clear. A
disappearing white colour points to dissolved refrigerant.
Refer to the "Product Information"
In case of more than 1 cc/hr contact
• supplier.
Check against design conditions. Refer to plant manual.
Refer to plant manual. For the max. allowable discharge pressure refer to the technical data of compressor.
During compressor standstill the lower part of the crankcase must remain warmer than
• the surroundings: ≥ 20 °C (NH3)
Check belts for:
1) Wear (fraying, cuts etc.) and ensure that they do not touch the groove bottom.
2) Tension. Too low a tension gives rise to excessive flapping or oscillation in operation. For correct tension consult Grasso instruction 0087516
Refer also to instructions of switch
• manufacturer.
≥0 K (NH3)
170 °C.
Check the number of operating hours in
view of any maintenance operations to be carried out.

2.3 STEPS FOR LONGER SHUT-DOWN PERIODS (> 6 months)

5 During the first 50 operating hours the compressor should be checked regularly for all the points
mentioned above, at least twice every 24 hours and more frequently in cases where irregularities are found.
32 30.10.2017
0089288gbr_11
To shut down a compressor for long term periods, proceed as follows:
i.
Tightly shut both the suction and discharge stop valves and the stop valve of the oil return line (if present).
ii.
Disconnect the power source from the compressor drive motor and the electrical control cabinet.
iii.
Place a moisture absorbing compound (eg a dessicant such as silica gel) inside the control cabinet.
iv.
Place warning tags on the electric system and all closed stop valves.
Prior to starting up after a shut down, change the oil and exchange the oil filters. Determine the starting and stopping procedure from prior to start the compressor.

2.4 LUBRICATION DATA

Determine max Toil and set this value in the safety device.
Change the oil as soon as an oil analysis indicates contaminated oil.
INSPECTION AND TROUBLE SHOOTING
LUBRICATION DATA
Warning!
It is expressly pointed out that it is not permitted to mix different types of oil. If another type of oil is used, first remove all the stale oil in the filters, oil pump, crankcase, shaft seal, oil separator and oil drains of the installation.

2.4.1 Topping up oil with compressor operating

Hint!
Use Grasso’s hand-operated oil pump, part. no. 18.13.121
Topping up oil is permitted during compressor operation.
Be sure that this oil is the same as in the plant (refer to Section 2.4, Page 33).
Without affecting the operation of the compressor, the oil may be topped up by means of a separate oil pump. This pump enables the oil to be forced into the crankcase via the oil charging valve, against suction pressure.
Fig.12: Oil level in compressor sight glass

2.5 EVACUATION, LEAK TESTING AND START-UP OF THE COMPRESSOR/PACKAGE

To evacuate the refrigeration system refer to Section 1.3.2, Page 22,
0089288gbr_11
30.10.2017 33
INSPECTION AND TROUBLE SHOOTING
EVACUATION, LEAK TESTING AND START-UP OF THE COMPRESSOR/PACKAGE
Always use a vacuum pump or pump-down unit to evacuate the refrigerant from the compressor.

2.5.1 EVACUATION OF REFRIGERANT BEFORE SERVICING

Procedure to evacuate the compressor:
1.
Switch off main control panel
2.
Remove main fuses
3.
Close shut-off valves
4.
Remove the refrigerant by means of a vacuum pump or pump-down unit, via the evacuation/purging valve(s) as prescribed by local safety regulations. For the location of these valves refer to the "Product Information".
5.
Drain the oil from the compressor and oil separator, oil return /oil rectifier system if present.

2.5.2 LEAK-TIGHTNESS AFTER SERVICING

The necessary safety precautions should be taken before carrying out the leak­tightness test. To check leak-tightness use dry nitrogen at a positive pressure which is less than the admissible operating pressure of the low pressure stage.

2.5.3 EVACUATION AFTER SERVICING

After the pressure test has been completed, the compressor (package) must be evacuated and undergo a vacuum test. Evacuation is used to remove air and moisture from the compressor (package)

2.5.4 START-UP AFTER SERVICING

1.
STATUS: Compressor (package) is dried and still evacuated.
2.
Charge the oil separator, if present, with oil.
See the appropriate Product Information for the correct quantity.
3.
Charge the compressor crankcase with oil via the oil charge valve until the minimum level is seen at the sight glass at the level as indicated in IMM.
It is mandatory to pre-lubricate the oil circuit by adding the final quantity of oil via the charge valve mounted onto the oil pump by means of a separate oil filling pump. The required oil level is indicated in the IMM.
4.
Re-install all accessories such as coupling, V-belt guard etc.
5.
Open the shut-off valves.
6.
Check the start-stop procedure.
7.
Check all safeties and controls.
8.
Re-install the main fuses.
9.
Start up the compressor.
10.
Check running condition.
Note:
34 30.10.2017
0089288gbr_11
The job isn't finished until the paper work is done! Complete the service report, e.g. Grasso report 00.89.062.

2.6 DRAINING AND CHANGE OF OIL

To top up oil see Section 2.4.1, Page 33, Oil changing procedure:
i.
Evacuate the compressor (refer to Section 2.5, Page 33).
ii.
Drain the oil via the oil charging/drain valve. Remove the cover of one or more service openings on the compressor side.
iii.
Clean the inside of the crankcase with a non-fibrous cloth (do not use cotton waste!).
iv.
Replace the service cover(s) with a new seal.
v.
Charge crankcase with clean oil in accordance with the procedure.

2.7 REPLACEMENT OF OIL FILTERS

General
INSPECTION AND TROUBLE SHOOTING
DRAINING AND CHANGE OF OIL
The frequency of exchanging oil discharge filter, oil suction filter and compressor suction gas filter(s) depends on the condition of the refrigeration system. Besides the maintenance schedules, it is recommended to exchange all filters when the compressor is overhauled and also in case the refrigeration plant has been modified.
Hint!
An oil discharge oil running-in filter is factory mounted. This oil filter must be exchanged after max. 100 running hours. This oil filter cannot be cleaned.
Fig.13: Oil control pressure regulator (1), oil discharge filter(2), oil pump (3)
Oil discharge filter
Hint!
Use the special tool for (dis)mounting the oil discharge filter element
Evacuate the compressor prior to exchange any filters.
0089288gbr_11
30.10.2017 35
INSPECTION AND TROUBLE SHOOTING
DISMANTLING, INSPECTION AND RE-ASSEMBLY OF SUCTION AND DISCHARGE VALVES

2.8 DISMANTLING, INSPECTION AND RE-ASSEMBLY OF SUCTION AND DISCHARGE VALVES

Hint!
A high working temperature and rapid temperature variations shorten the life time of the valves, which, for this reason, require regular inspection.
The suction and discharge valves of a refrigeration compressor are parts that are heavily loaded both mechanically and thermally. Wear and life time of the valves strongly depend on the working conditions of the compressor. It is recommended that valve condition is regularly checked.For dismantling, inspection and re­assembly of the valves, refer to the relevant paragraph of the Compressor Service Instruction Manual.
Hint!
In order to reduce the downtime involved in the valve inspection, it is recommended to have as many complete valve assemblies in stock as there are cylinders on the compressor.These valves can be exchanged with the original valves; in this case, these original valves can be inspected and repaired or replaced if necessary later.

2.9 COMPRESSOR PURGING

Procedure to purge the compressor (after maintenance jobs):
STATUS:
Stop valves of suction, discharge and oil return line are still closed (refer to Section 2.5, Page 33) and compressor is filled with oil (refer to Section 2.6, Page 35).
i.
Connect a vacuum pump to the evacuation/purging valve(s) and evacuate as prescribed by local regulations. For the location of these valves refer to the "Product Information".
ii.
When evacuation is completed open the discharge stop valve.
iii.
Watch suction and discharge pressure.
Hint!
If suction pressure increases quickly, the discharge valve assy is leaking.
iv.
Start compressor.
v.
Slowly open suction stop valve.
vi.
Open the stop valve in the oil return line of the oil separator (if present).
vii.
For two stage compressor only;
vii.a
Two-stage system A/B: open liquid supply to interstage cooler.
vii.b
Two-stage system C/D: refer to the plant manual.
36 30.10.2017
0089288gbr_11
INSPECTION AND TROUBLE SHOOTING
TROUBLESHOOTING TABLE GRASSO RECIPROCATING COMPRESSORS
viii
If a Self-Limiting Automatic Purger is not installed, purge the refrigerating
.
system (refer to the plant manual).

2.10 TROUBLESHOOTING TABLE GRASSO RECIPROCATING COMPRESSORS

The troubleshooting table shown overleaf may be helpful to quickly trace and remedy failures that interfere with the proper operation of the compressor. It is emphatically pointed out that the cause of a failure must often be sought in the refrigeration installation itself. Therefore, it is necessary besides this table also to consult the plant manual.
0089288gbr_11
30.10.2017 37
INSPECTION AND TROUBLE SHOOTING
TROUBLESHOOTING TABLE GRASSO RECIPROCATING COMPRESSORS
Troubleshooting
FAULT CAUSE REMEDY
1. Discharge stop valve not fully
A Discharge pressure too
high
B Discharge temperature too
high
C Suction pressure too high
D Suction pressure too low
open
2. Discharge pressure gauge defective
3. Non-condensables in the system Purge with a Automatic Purger
1. Discharge pressure too high See A
2. Too many cylinders cut out Cut in more cylinders
3. Suction pressure too low See D
4. Excessive superheat of suction gas
5. For two-stage compressors: interstage cooling does not operate properly
6. Room temperature too high Ventilate engine room better
7. Discharge valve defective Repair or renew
8. Pressure relief valve is leaking Repair or renew
1. Capacity control does not operate
2. Compressor capacity too small Refer to plant design
3. Suction pressure gauge defective Repair or renew
4. One or more suction valves defective
5. One or more discharge valves defective
6. Pressure relief valve is leaking Repair or renew
1. Suction stop valve not fully open Open fully
2. Suction gas strainer blocked Renew
3. Injection control not adjusted correctly
4. Too little refrigerant in installation Top-up with refrigerant
5. Suction pressure gauge defective Renew
Open fully
Repair or replace
Eliminate excessive superheat
Repair
Repair
Renew suction valve rings
Repair or renew
Re-adjust control
Warning!
Stop compressor and contact installation engineer
1. Liquid refrigerant in crankcase E Crankcase frosted or wet
6
*
F
6 In case of R744 applications only, crankcase can be frosted or wet, during normal operating conditions.
due to:
1a. Room temperature too low
1b. Oil return from separator contains liquid refrigerant
1c. Installation operates too wet
1d. Liquid separator too small Consult plant manual
1. Oil pressure for valve lifting
mechanism too low
Provide for crankcase heating or, if provided, check it for proper operation
Consult plant manual
Re-adjust installation and provide for superheat
See J
0089288gbr_11
38 30.10.2017
INSPECTION AND TROUBLE SHOOTING
Troubleshooting
FAULT CAUSE REMEDY
All cylinders inactive while compressor is operating
G Too high oil consumption
H Too high oil pressure
during normal operation at working temperature
J Too low lubricating oil
pressure
K Too low or no control oil
pressure (Not or Grasso 5HP)
2. Incorrect wiring of capacity
control
1. Type of oil not according to oil
lubrication oil table (too thin oil)
2. Compressor operates unloaded
too frequently
3. No return from oil separator *
4. Restriction plug at the bottom of
suction chamber in cylinder clogged
5. Worn out oil scraper ring(s) Replace ring(s)
6. Loss of oil due to leakage Repair
7. Leaking shaft seal (max. 1 cc/hr)
8. Oil level in crankcase too high Drain/Refill with oil
9. Oil separator is not initially filled
with oil
1. Lubricating oil pressure regulator
not adjusted properly or defective
2. Defective oil pressure and/or
suction pressure gauge (if present)
1. Too little oil in crankcase Top up oil
2. Disturbed oil circuit: Oil suction
and/or discharge filter is dirty
3. Lubricating oil pressure regulator
not adjusted properly or defective
4. Liquid refrigerant in crankcase See E
5. Defective oil pressure and/or
suction pressure gauge (if present)
6. Worn bearings Renew bearings
1. Failure of control oil pressure
regulator in oil pump
2. A lack of oil in oil system Add oil to the system
3. Oil pump defect Repair or renew oil pump
Refer to the "Product Information”
Change oil type
Refer to design calculations
Check the operation of float valve in oil
7
separator
Clean plug
Repair shaft seal Refer to Section 2.2
Refer to section “Initial oil charge”
Re-adjust or renew
Repair or replace
Renew the element of oil suction filter and/or oil discharge filter
Re-adjust or renew
Repair or renew
Re-adjust or renew regulator
7 During the initial start-up, the oil separator (if present) consumes oil before the first oil will be returned.
0089288gbr_11
30.10.2017 39
MAINTENANCE
Spare parts manual

3 MAINTENANCE

3.1 Spare parts manual

Hint!
A complete spare parts overview is available as a separate manual. Download the parts list manual via internet (DocNav) or consult Grasso.

3.2 Post start-up maintenance

After the compressor has run for the initial 100 operating hours:
i.
Drain the oil and refill the compressor with the correct amount of fresh oil.
ii.
Replace the running oil discharge filter element with the “permanent“ filter element in accordance with the filter replacement instructions.
iii.
Inspect suction gas filter (refer to the Compressor Service Instruction Manual).
iv.
Exchange or clean oil suction filter element.
v.
Check the compressor shaft seal for leakage. If excessive (more than 1 cc/hr) replace the seal.
vi.
1) Retighten the coupling mounting bolts with the torque settings as given by the coupling manufacturer.
2) Verify and if necessary, correct the tension of the V-belts as given in the Grasso instruction 0087516.
vii.
Verify and if necessary, correct the torque settings of all foundation bolts as given in Compressor Service Instruction Manual.

3.3 First maintenance

Hint!
For complete conditional service schedules and service intervals, refer to Guideline for Conditional maintenance.
After the refrigerating plant has been modified, the suction gas filter(s), the oil filters and the oil must be changed.
Maintenance Number of operating hours
Renewal of oil discharge filter X
Inspection of suction gas filter(s) X
Inspection of oil suction filter
(strainer)
100
X
8
refer to Guideline for Conditional
> 100
Maintenance
8 Time dependent on pollution.
40 30.10.2017
0089288gbr_11
Inspection leakage shaft seal X

3.4 SMS FACTOR

General
The following maintenance has to be distinguished:
1.
Grasso Maintenance Monitor (GMM) is applied
Maintenance A, B and C, service intervals are determined on measured values of GMM
2.
GMM is not applied:
Service intervals according to Service and Maintenance Schedules (SMS) tables in combination with operating conditions
Maintenance Number of operating hours
Oil analysis
9
100
X
8
MAINTENANCE
SMS FACTOR
> 100

3.5 Legend

Warning!
GMM is not used: The running hours mentioned in the SMS tables should only be used as a reference for maintenance intervals.
The number of running hours mentioned in the SMS tables have to be adjusted accordingly depending on the operating conditions of the compressor (speed, evaporating temperature, condensing temperature, refrigerant, start frequency, capacity control steps, etc.. This means that the service intervals could be significantly different.
The running hours mentioned in the tables are based on a single stage compressor running at -10oC/+35oC, NH3 at nominal speed. In this case the SMS factor = 1, in all other cases the maintenance intervals
have to be adjusted accordingly.
Warning!
These operations cover routine maintenance and are meant as a guide only. Lack of maintenance, frequency of stop/starting, extreme operating conditions etc could lead to accelerated wear.
General;
The service and maintenance schedules use the codes as explained in the table below;
8 Time dependent on pollution. 9 Consult your oil supplier.
0089288gbr_11
30.10.2017 41
MAINTENANCE
Description Maintenance ABC when GMM is applied
Actions
Legend for service and maintenance schedules (SMS)
Item Code/Actions Description
1 IC Inspection / Alternatively renewal - correcting / Testing
2 IV Inspection Visual / Alternatively electrical testing
3 RE Renewal
4 ME Measure
5 CL Clean

3.6 Description Maintenance ABC when GMM is applied

The information in this section has to be used when GMM is applied.
Hint!
This section is only valid in case the Grasso Maintenance Monitor (GMM) is applied.
General
The following maintenance has to be distinguished;
1.
Small maintenance, Maintenance A, Yearly inspection
2.
Medium maintenance, Maintenance B
3.
Large maintenance, Maintenance C
Description maintenance A;
1.
Replace/clean oil discharge filter, clean oil suction filter
2.
Visual inspection of cylinders and crankcase
3.
Visual inspection of cylinder no. 1
4.
Check compressor running conditions
5.
Check/test safety equipment
Description maintenance B;
1.
Maintenance A +
2.
Replace suction and discharge valve rings and springs (“top end“ overhaul)
3.
Inspection of pistons and cylinder liners
Description maintenance C;
1.
Maintenance B +
2.
Major inspection/overhaul;
Depending on requirements and expectations, required actions have to be taken. (complete disassembly, replacement of bearings, inspection/ replacement of all main components like crankshaft, cylinder liners, pistons, ...)
42 30.10.2017
0089288gbr_11

3.6.1 Compressor

General remarks about check list;
1.
2.
3.
4.
5.
MAINTENANCE
Description Maintenance ABC when GMM is applied
Check list for compressor only; all other components have to be maintained according to their specific manuals (IMM and SIM).
All items of the list below marked “check“, have to be checked visually and checked for proper working.
Some components have to be measured.
For measuring details refer to SIM.
Measuring means also that visual inspection is required.
Visual inspections:
The visual inspections during maintenance are of importance; measurements should be carried out at the moment that visually abnormalities are detected. The result of the inspection determines whether one or more parts have to be replaced. For more detailed information refer (SIM) and Installation and Maintenance Manual (IMM).
6.
Oil and oil return systems:
The quality of the oil effects the oil consumption and the life time of the moving parts. For oil return systems or systems in which soluble oil is being used, we advise to check (or have checked) the quality of the oil every 5000 hours and - if necessary - to renew the oil and/or filters. If there is no oil analysis available, we advise to renew the oil. By regularly carrying out oil analyses and registering them in a log, aberrations will be noticed in an early stage, which may prevent or reduce resultant damage(s).
Note 1:
When renewing the oil, in the crankcase the oil in the oil separator and the oil return or oil rectifier system (if fitted) has to be renewed.
Note 2:
Pre-lubricate the compressor before re-starting. Used or filtered oil should NEVER be added to a compressor under any circumstance. Use only new oil as selected from the Grasso oil table. Oil charging via the suction line of the compressor is not allowed.
Grasso Maintenance Monitor (GMM) is applied
Maintenance compressor
A B C
Check Check Check
Check Check Check
Check Check Check Crankcase heater
Visual
inspection
Check Replace Seals of cap control piston / lifting mechanism
Measure Crankshaft
Capacity control
Compressor
housing
Connecting rod
Description
Solenoid valve and coils
Oil return orifice (LP and) HP
Main (and intermediate) bearings, running
surface
Cylinder located nearest to the shaft-end of the
compressor:
0089288gbr_11
30.10.2017 43
MAINTENANCE
Description Maintenance ABC when GMM is applied
Grasso Maintenance Monitor (GMM) is applied
Maintenance compressor
A B C
Clean Clean Clean
Visual
inspection
Visual
inspection
Measure
Check Check Check Drive Coupling alignment
Check Check Check Interstage cooler Inspections and injection valves
Clean Clean Clean
Replace. Replace Replace Oil discharge filter
Check Clean Clean Suction gas
Check Check Check
If
hygroscop
ic oil is
applied:
Replace
Check Check Check Lubrication and control system
Check Clean Clean Oil separator, test oil return system
Clean Clean Clean Oil cooler fan / heat exchanger
Check Check Check Shaft seal Oil & Refrigerant leak range
Visual
inspection
Check Replace Replace Suction and discharge compressor valves
Replace Replace
Visual
inspection
Visual
inspection
Visual
inspection
Visual
inspection
+ TEST
Measure Big and small end bearing, running surface
Compressor
housing
Measure All cylinder liners
Visual
inspection
Replace
Measure Gudgeon pin
Visual
inspection
+ TEST
Check Thrust bearing Running surface
Cylinder liners
Filters
Oil
Piston
Relief valve(s)
Compressor valves
Description
Inside and outside
Cylinder located nearest to the shaft-end of the
compressor
Oil suction filter
Oil analysis recommended
Oil refreshment compresssor, oil separator and
oil system
Oil pump element, oil control and lubrication
pressure regulator
Rings
Cylinder located nearest to the shaft-end of the
compressor:
Suction and discharge valves, springs, damper
rings

3.6.2 Package components

Checklist package components
Description/checkpoint
1 Drive guard
2 V-belts and alignment
3 Coupling alignment
4 Oil level float switch on compressor and oil separator
44 30.10.2017
0089288gbr_11
Description Maintenance ABC when GMM is applied
Checklist package components
Description/checkpoint
5 Pressure safety switches
6 Pressure gauges
7 Thermostats and thermometers
8 Electrical control system
9 Oil return protection and oil return system
10
11 Base frame, vibration dampers and bolts
12 Piping
13 Interstage cooler, interstage injection
15 Oil cooler (oil side and air side) and fan
16 Thermo-Master
Electric motor and thermistors
(Consult motor manufacturer)
MAINTENANCE
0089288gbr_11
30.10.2017 45
MAINTENANCE
Grasso V 300 .. 1800 (T), WITHOUT GMM

3.7 Grasso V 300 .. 1800 (T), WITHOUT GMM

The schedule below has to be used when GMM is not applied.
Hint!
In case Grasso Maintenance Monitor (GMM) is applied, the maintenance intervals will be based on actual measured values. If GMM is applied, refer to Section 3.6, Page 42
Service and maintenance schedules Grasso V 300 .. 1800 (T), excl. GMM
Actions
Running hours * 1000
Description
Item
0.1
1
2
3 - ME ME ME ME ME ME ME Oil analysis
Oil
4 RE RE - RE RE RE RE RE
5
Oil pump
6 - IC/CL - IC/CL IC/CL IC/CL IC/CL IC/CL
7a
Crankshaft
CL RE CL RE RE RE RE RE Oil suction filter
11
RE
RE RE RE RE RE RE RE
- IC/CL - IC/CL IC/CL IC/CL IC/CL IC/CL
- - - - - -
3 6 - - -
9 - 12 - -
Yearly
15 - 18 -
21 - - 24 - -
27 30 - - -
33 - - - 36
10
Checkpoint
Oil discharge
filter
Oil refreshment
(If hygroscopical
oil is used
replace this
always after each
opening of
compressor or
installation)
Housing and
element
Control and
lubrication oil
pressure regulator
IC/MEIC/M
E
Main and
intermediate
bearing bushes
10 Check after every maintenance job the settings and working of all safety devices, regulators and the
running conditions according to the Service Instruction Manual (SIM)
11 A running-in oil discharge filter is factory mounted. This running-in filter has to be replaced after max. 100
running hours by a permanent filter. One permanent filter is supplied together with the compressor.
0089288gbr_11
46 30.10.2017
Grasso V 300 .. 1800 (T), WITHOUT GMM
Service and maintenance schedules Grasso V 300 .. 1800 (T), excl. GMM
Actions
MAINTENANCE
Running hours * 1000
Description
Item
0.1
7b - - - - - -
8 -
9 Shaft seal - IC IC IC IC IC IC IC
10 Conrod -
11
12 - IC - IC IC IC IC IC Piston rings
13 -
14 Thrust bearing -
15
16 - RE - RE IV IV RE RE
17 - IC - IC IC IC IC IC
18
19 CL CL - CL CL CL CL CL Crankcase
20 - - - - IC IC IC IC
21 - IV - IV IV IV IV IV Relief valves
Pistons
Capacity control
Compressor
housing
IC/M
IC/M
- IC - IC IC IC IC IC Piston
IC/M
IV/M
IC/IV IC/IV IC/IV IC/IV IC/IV IC/IV IC/IV IC/IV
IC/IV IC/IV IC/IV IC/IV IC/IV IC/IV IC/IV IC/IV
3 6 - - -
9 - 12 - -
Yearly
15 - 18 -
21 - - 24 - -
27 30 - - -
33 - - - 36
IC/MEIC/MEIC/MEIC/MEIC/MERunning surfaces
E
E
E
E
-
IC/MEIC/MEIC/MEIC/MEIC/MEBig and small
-
IC/MEIC/MEIC/MEIC/MEIC/M
-
IV/MEIV/MEIV/MEIV/MEIV/M
-
10
Checkpoint
Running surfaces
IC/MEIC/M
E
E
E
main and
intermediate
bearings
crankshaft
con. rods
Oil/refrigerant
leakage
end bearings
Gudgeon pin
Running
surfaces/Axial
play
Solenoid valves
and coils
Seals of cap.
control piston
Cap. Control
mechanism
Crankcase
heater
Non return valves LP/
Restrictions HP
10 Check after every maintenance job the settings and working of all safety devices, regulators and the
running conditions according to the Service Instruction Manual (SIM)
0089288gbr_11
30.10.2017 47
MAINTENANCE
Grasso V 300 .. 1800 (T), WITHOUT GMM
Service and maintenance schedules Grasso V 300 .. 1800 (T), excl. GMM
Actions
Running hours * 1000
Description
Item
0.1
22
23
Discharge valves
24 - IC/CL - IC/CL IC/CL IC/CL IC/CL IC/CL
25 Suction valves - IC - IC RE RE IC RE
26
Cylinder liners
27 -
28
29 IC IC IC IC IC IC IC IC V-belts
30 Electric motor Refer to specifications of motor manufacturer
31
32 IC IC IC IC IC IC IC IC Safety switches
33 IC IC IC IC IC IC IC IC Gauges
34 IC IC IC IC IC IC IC IC Thermostats
35 IC IC IC IC IC IC IC IC Thermometers
36 IC IC IC IC IC IC IC IC
37 IC IC IC IC IC IC CL/IC CL/IC
38 IV IV IV IV IV IV IV IV Thermistors
39 IC IC IC IC IC IC IC IC
Drive
Optionals
12
IC/CL IC/CL IC/CL IC/CL IC/CL IC/CL IC/CL Suction gas filter
RE
- IC - IC RE RE IC RE
- IV - IV IV IV IV IV
IV/M
IC IC IC IC IC IC IC IC Alignment
IC IC IC IC IC IC CL/IC CL/IC Oil level switch
3 6 - - -
9 - 12 - -
Yearly
15 - 18 -
21 - - 24 - -
27 30 - - -
33 - - - 36
IV/MEIV/MEIV/MEIV/MEIV/MEDimension and
E
-
10
Checkpoint
Valves, springs
and damper rings
Stroke limitor/
Discharge valve
seat
Valves, springs
and damper rings
Cap. Control
lifting mechanism
running profile
Electrical control
system
Valve oil return
protection
Vibration
dampers and
bolts
10 Check after every maintenance job the settings and working of all safety devices, regulators and the
running conditions according to the Service Instruction Manual (SIM)
0089288gbr_11
48 30.10.2017
Service and maintenance schedules Grasso V 300 .. 1800 (T), excl. GMM
Actions
MAINTENANCE
Running hours * 1000
Description
Item
0.1
40
41 CL CL - CL CL CL CL CL
42 - IC IC IC IC RE IC IC
43 CL CL CL CL CL CL CL CL
44 RE RE - RE RE RE RE RE
45 Refer to specifications of motor manufacturer
46 ME
IC/MEIC/MEIC/MEIC/MEIC/MEIC/MEIC/MEIC/M
ME/CLME/CLME/CLME/CLME/CLME/CLME/C
3 6 - - -
9 - 12 - -
Yearly
15 - 18 -
21 - - 24 - -
27 30 - - -
33 - - - 36
10
E
L
Checkpoint
Intermediate
cooler and
injection valve
Oil separator
refreshing oil and
cleaning/testing
of float valve
Heavy duty thrust
bearing
Oil cooler, air
side
Oil cooler, oil
side, refrigeration
oil
Oil cooler, electic
motor (fan)
Cylinder head
water cooling
system
10 Check after every maintenance job the settings and working of all safety devices, regulators and the
running conditions according to the Service Instruction Manual (SIM)
12 A running-in suction gas filter is factory mounted. This running-in filter has to be replaced after max. 100
running hours by a permanent filter. One permanent filter is supplied together with the compressor
0089288gbr_11
30.10.2017 49
APPENDIX; Product Information (PI)
GRASSO MAINTENANCE MONITOR

4 APPENDIX; Product Information (PI)

4.1 GRASSO MAINTENANCE MONITOR

Hint!
In case the GSC-TP is included, the GMM hardware is not required, since the GSC-TP includes the GMM software.
Fig.14: Grasso Maintenance Monitor
GMM connections
1 Ethernet
2 Power input (10 .. 30 VDC)
3 Compressor speed sensor
4 Discharge temperature sensor
5 Oil temperature sensor
The Grasso micro processor controlled maintenance monitor is a unique standalone device for flexible maintenance. This equipment strongly recommended to fit on V series compressors to be able to tune the maintenance to the actual running conditions. In other words: “On time maintenance”
This results in (nearly) all cases in longer service intervals and significantly less maintenance costs. For industrial refrigeration compressors this is a unique development. To maintain the highest level of reliability, even with extended service intervals, this series is fitted with the best possible components available.
This standalone device works independent from compressor controls like the Grasso GSC OP/TP and must be seen as an addition on the normal compressor control. In separate documents the complete maintenance philosophy and how to handle is explained in detail.
50 30.10.2017
0089288gbr_11
Besides this practical instrument Grasso is able to make, in advance, an analyses based on a theoretical profile of the compressor and the running conditions. In this way an indication of the running costs ( Total Costs of Ownership, TCO) can be produced.

4.2 GENERAL LIMITS OF OPERATION GRASSO V

When operating the compressor, none of the limits of operation as stated in the table below must be exceeded. *
13
The diagrams overleaf represent the overall fields of application in which the individual operation limits are taken into account.
General limits and fields of operation
APPENDIX; Product Information (PI)
GENERAL LIMITS OF OPERATION GRASSO V
REFRIGERANT
Compressor speed n
Suction pressure = evaporating
pressure =crankcase pressure
Suction superheat
Superheat LP suction Grasso VT
Actual suction temperature
Discharge pressure =
condensing pressure
tc = saturated condensing
temperature *
Discharge pressure =
condensing pressure *
14
15
*
17
18
*
300(T) .. 600(T)
300(T) .. 600(T)
po/t
delta-t
Ps *16/
o
t
a
t
c
300(T) .. 600(T)
300(T) .. 600(T)
NH
Grasso V
Grasso V
700(T) ..
1800(T)
Grasso V
Grasso V
700(T) ..
1800(T)
Grasso V min.
Grasso V
Grasso V
700(T) ..
1800(T)
Grasso V
Grasso V(T) min. -50 °C
Grasso V
Grasso V
700(T) ..
1800(T)
min.
max.
max.
min. >0 °C
max.
500 min-1 for direct drive
600 min-1 for V-belt drive
500 min-1 for direct drive
700 min-1 for V-belt drive
1500 min
1200 min
0.3 bar(a)
-55 °C
8.5 bar(a) 19 °C
7.0 bar(a) 13 °C
26.0 bar(a) 60 °C
24.0 bar(a) 56 °C
3
-1
-1
13 In practice, it is not so much the individual operation limits as combinations of them that are
decisive for the conditions under which a compressor may operate. To check the various
possibilities in this respect, use should be made of the "fields of application" ).
14 This pressure is also the maximum allowable pre-set value of the HP safety switch. 15 CAUTION!: When adjusting the HP and/or LP safety switch, care should be taken that the pressure
difference Δp=(pC-po) never exceeds 26.0 bar(g).
16 “Ps“ is mentioned on type plate of the compressor 17 This pressure is also the maximum allowable pre-set value of the HP safety switch. 18 CAUTION!: When adjusting the HP and/or LP safety switch, care should be taken that the pressure
difference Δp=(pC-po) never exceeds 19.0 bar (g).
0089288gbr_11
30.10.2017 51
APPENDIX; Product Information (PI)
STARTING UP OF TWO-STAGE COMPRESSORS
General limits and fields of operation
REFRIGERANT
Design pressure
Discharge temperature
Discharge temperature LP Grasso VT
Pressure ratio per stage (pc/p
or pc/pm or pm/po)
Pressure ratio limits are not
absolute but arbitrary values
based on practical
considerations
Pressure difference delta-p
Oil temperature in crankcase
19
PSs *
t
o
t
oil
Grasso V(T) -
Grasso V
e
j -
Grasso V
300(T) .. 600(T)
Grasso V
700(T) ..
1800(T)
°C
NH
26.5 bar(a)
This pressure deviates from the so
called max. discharge
pressure=condensing pressure
(allowed during operation) as stated
in the table.
+170 °C
This is the actual discharge
temperature, measured directly in
max.
min. 1.5
max. 10
max.
max.
min.
max.
the gas flow just before the
discharge connection. The given
value also applies to the LP stage
of two-stage compressors.
(pc - po) <= 25.5 bar
The standard built-in overflow
safety valve(s)
(pc - p
ambient
(pc - po) <= 19.0 bar
The standard built-in overflow
safety valve(s)
(pc - p
ambient
>10oC and > T
pressure at stand still
Indicated minimum value is the lowest oil temperature at which the compressor is allowed to be started.
< 70 oC, depending on type of oil The maximum oil temperature
depends on the operating conditions of the compressor and the oil type used.
A minimum actual oil viscosity of 10 cSt in the bearings is always required.
saturated crankcase
+ 15 K
3
) <= 25.5 bar
) <= 25.5 bar

4.3 STARTING UP OF TWO-STAGE COMPRESSORS

Procedure for starting from compressor standstill
In the case of two-stage compressors it is very important that immediately after the period of automatic fully unloaded start (ensured by the corresponding three­way solenoid valve in the control pressure supply line from the oil pump; only one or more H.P. cylinders become operative, viz. only those cylinders of which the suction valve lifting mechanism is directly and permanently connected to the
19 “PSs“ is mentioned on type plate of the compressor (Possibly "Pd" is mentioned for compressors
delivered before 1-Mar-2013)
52 30.10.2017
0089288gbr_11
APPENDIX; Product Information (PI)
STARTING UP OF TWO-STAGE COMPRESSORS
control pressure supply of the oil pump via the starting solenoid valve mentioned. This means that during starting none of the three-way solenoid valves for the capacity control are allowed to be energized.
Procedure to move on to two-stage operation and to increase capacity.
Once properly started, as indicated in the previous paragraph, the compressor has to be switched over to two-stage operation with minimum capacity, followed, if and when required, by gradual stepping up to maximum capacity.
The procedure thereby to be applied depends on the installation operating conditions during starting which give rise to two distinct possibilities, viz.:
1.
The compressor is started at low evaporating temperatures, this being approx. the (design) value during normal (full-load) operation.
This situation occurs after the compressor has been stopped for a certain period of time because of low capacity requirements of the installation. Under these circumstances it is permitted to switch over to the two-stage part-load step of minimum capacity immediately after proper starting with H.P. cylinders in operation.
In the case of NH3, this is even a necessity, for otherwise the compressor would be running in single-stage under two-stage conditions, resulting in too
high a discharge temperature.
2.
The compressor is started at a relatively high evaporating temperature, that is to say much higher than under design conditions and in any case not suitable for two-stage operation.
Such a situation may occur after a prolonged period of compressor standstill or when the compressor operates on a batch type freezing tunnel, just loaded with warm products. Under these circumstances it is not permitted to switch over to two-stage operation with minimum capacity until the H.P. cylinders already in operation have lowered (in single-stage) the evaporating temperature so that the corresponding working point at the condensing temperature tc, lies inside the field of application of the two-stage minimum
part-load step concerned. Only then, after this step has been energized, the saturation intermediate temperature tm will be below its maximum value.
Consequently, the maximum value of to at which it is allowed to switch over to two-stage operation, is determined by the intersection of the near-vertical line
which represents the right hand limitation of the relevant field of application and the horizontal line which represents the condensing temperature tc.
Likewise, during further stepping up to maximum capacity, the evaporating temperature has to be pulled down by each intermediate part-load step so far that the corresponding working point at given condensing temperature lies each time just inside the field of application of the next part-load step of higher capacity, before that step is energized.
Fast pull-down part-load control steps
When using the standard capacity control steps of the two-stage compressor types, the pull-down procedure to achieve full-load operation at design conditions, as described in the previous paragraph, is rather often very time consuming. This is due to the fact that all compressor types are always started
0089288gbr_11
30.10.2017 53
APPENDIX; Product Information (PI)
DIAGRAMS SINGLE STAGE AND BOOSTER
with only one HP cylinder in operation and that the minimum LP/HP swept volume ratio for any part-load step is ϕ = 2.
Therefore, for all Grasso two-stage types a fast pull- down electric capacity control system has been developed, which allows the compressors to be started with two or more HP cylinders in operation and which includes one or more part­load steps with volume ratio ϕ = 1.

4.4 DIAGRAMS SINGLE STAGE AND BOOSTER

Solenoid valve/cylinder numbering for electric capacity control
Solenoid
type
Compressor
300 &
700
450 &
1100
600 &
1400
1800
Before Sept. 2014
1800
From Sept.
2014
Capacity control steps
Compressor
type
V 300
&
V 700
V 450
&
V 1100
V 600
&
V 1400
UNL
NO
1 2 3 4 -
(3+4) 2 (5+6) 1 -
(5+6) 7 8 (2+4) (1+3)
(7+8) 5 6 (9+10) (1+2+3+4)
(5+7+8) (9+10) (1+2) (3+4) 6
Capacity %
No. 1
NC
Cylinder number / solenoid valves
20
25 1 -
50 1 + 2 1
75 1 + 2 + 3 1 + 2
100 1 + 2 + 3 + 4 1 + 2 + 3
33 (3+4) -
50 (3+4) + 2 1
67 (3+4) + (5+6) 2
83 (3+4) + (5+6) + 1 2 + 3
100 (3+4) +2 + (5+6) + 1 1 + 2 + 3
25 (5+6) -
37 (5+6) + 8 2
50 (5+6) + 8 + 7 1 + 2
62 (5+6) + 8 + (1+3) 2 + 4
75 (5+6) + (2+4) + (1+3) 3 + 4
No. 2
NC
Cylinders Solenoids
No. 3
NC
No. 4
NC
20 Refer to the swept volume expressed as a percentage of the full-load swept volume
0089288gbr_11
54 30.10.2017
Capacity control steps
APPENDIX; Product Information (PI)
DIAGRAMS TWO STAGE
Compressor
type
V 1800
Before Sept. 2014
V 1800
From Sept. 2014
Capacity %
20
Cylinders Solenoids
87 (5+6) + 7 + (2+4) + (1+3) 1 + 3 + 4
100
20 (7+8) -
30 (7+8) + 5 1
40 (7+8) + 5 + 6 1 + 2
50 (7+8) + 6 + (9+10) 2 + 3
60 (7+8) + 5 + 6 + (9+10) 1 + 2 + 3
70 (7+8) + 5 + (1+2+3+4) 1 +4
80 (7+8) + 5 + 6 + (1+2+3+4) 1 + 2 + 4
90 (7+8) + 6 + (9+10) + (1+2+3+4) 2 + 3 + 4
100
(5+6) + 7 + 8 + (2+4) +
(1+3)
(7+8) + 5 + 6 + (9+10) +
(1+2+3+4)
30 (5+7+8) -
40 (5+7+8) + 6 4
50 (5+7+8) + (9+10) 1
60 (5+7+8) + (9+10) + 6 1 + 4
70 (5+7+8) +(9+10) + (1+2) 1 + 2
80
90
100
(5+7+8) + 6 + (3+4) +
(1+2)
(5+7+8) + (3+4) + (9+10)
+ (1+2)
(5+7+8) + (3+4) + (9+10)
+ (1+2) + 6
1 + 2 + 3 + 4
1 + 2 + 3 + 4
2 + 3 + 4
1 + 2 + 3
1 + 2 + 3 + 4

4.5 DIAGRAMS TWO STAGE

Solenoid valve/cylinder numbering for electric capacity control
type
Compressor
300T &
700T
450T &
1100T
20 Refer to the swept volume expressed as a percentage of the full-load swept volume 21 UNL, Unloaded start 22 Numbers between brackets [] are HP cylinders
UNL
NO
[4hp ]
[4hp ]
Solenoid
21
NC
No. 1
No. 2
NC
No. 3
NC
No. 4
NC
Cylinder number 22 / solenoid valves
1 2 3 -
1 2, 3
5, [6hp]
-
0089288gbr_11
30.10.2017 55
APPENDIX; Product Information (PI)
DIAGRAMS TWO STAGE
Solenoid valve/cylinder numbering for electric capacity control
Solenoid
type
Compressor
600T &
1400T
1800T
Capacity control steps
Compressor
type
300T
&
700T
450T
&
1100T
600T
&
1400T
Capacity %
UNL
21
NO
[6hp ]
[6hp ]
23
0 [4] - 0.0
33 1 + [4] 1 1.0
67 1 + 2 + [4] 1 + 2 2.0 -
100 1 + 2 + 3 + [4] 1 + 2 + 3 3.0 -
0 [4] - 0.0
25 1 + [4] 1 1.0
50 (2 + 3) + [4] 2 2.0 -
50
75
75
100
0 [6] - 0.0
33 (1 + 2) + [6] 1 2.0 -
33
50
50
67
No. 1
NC
Cylinder number 22 / solenoid valves
1, 2 3
1, 2
Cylinders Solenoids
1 + [4] +(5 +
[6])
1 + (2 + 3) +
[4]
(2 + 3 )+ [4] +
(5 + [6])
1+ 2 + 3 + [4]
+ (5 + [6])
3 + [6] + (4 +
[8])
(1 + 2) + 3 +
[6]
(1 + 2) + [6] +
(4 + [8])
(1 + 2) + [6] +
(4 + [8])
1 + 3 1.0
1 + 2 3.0 -
2 + 3 1.5
1 + 2 + 3 2.0 -
2 + 3 1.0
1 + 2 3.0 -
1 + 3 1.5
1 + 2 + 3 2.0 -
No. 2
NC
7, [8hp], 9
No. 3
NC
4, [8hp]
5
Qty HP / Qty LP
cylinders
24
3, 4, [10hp]
Remark 25)
Starting only/ Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
No. 4
NC
5, 7
21 UNL, Unloaded start 22 Numbers between brackets [] are HP cylinders 23 Refer to the swept volume expressed as a percentage of the full-load swept volume of the LP cylinders 24 Each phi has its own field of application! Refer Page 56 25 For starting up procedure, refer Section 4.3, Page 52
0089288gbr_11
56 30.10.2017
Capacity control steps
APPENDIX; Product Information (PI)
DIAGRAMS TWO STAGE
Compressor
type
1800T
23
Capacity %
83
100
0 [6] - 0.0
29 (1 + 2) + [6] 1 2.0 -
29
43
43
57
71
86
100
Cylinders Solenoids
(1 + 2) + (5 +
7) + [6] + (4 + [8])
(1 + 2) +3 + (5
+ 7) + [6] + (4
+ [8])
(3 + 4 + [10]) +
[6]
(1 + 2) + 5 +
[6]
(3 + 4 + [10]) +
5 + [6]
(1 + 2) + [6] +
(7 + [8] + 9)
1 + 2 + 5 + [6]
+ (7 + [8] + 9)
(1 + 2) + (3 +
4 + [10]) + (7 +
[8] + 9) + [6]
(1 + 2) + (3 + 4 + [10]) + +5
+ [6] + (7 + [8]
+ 9)
1 + 3 + 4 2.5 -
1 + 2 + 3 + 4 3.0 -
1 + 3 3.0 -
3 + 4 1.5
1 + 2 2.0 -
1 + 2 + 3 2.5 -
1 + 2 + 4 2.0 -
1 + 2 + 3 + 4 2.3 -
4 1.0
Qty HP / Qty LP
cylinders
24
Remark 25)
Starting only/Fast
pull down
Starting only/Fast
pull down
Starting only/Fast
pull down
23 Refer to the swept volume expressed as a percentage of the full-load swept volume of the LP cylinders 24 Each phi has its own field of application! Refer Page 56 25 For starting up procedure, refer Section 4.3, Page 52
0089288gbr_11
30.10.2017 57
APPENDIX; Product Information (PI)
LUBRICATING OILS (choice and recommendations)

4.6 LUBRICATING OILS (choice and recommendations)

Caution!
In case a Grasso compressor is used inside a GEA Grasso produced chiller, the applicable oils could be limited compared with the oils mentioned in this chapter for use with NH3 as refrigerant. The oils to
be used will then be specified in the Chiller Product information.
Warning!
The choice of oil for a refrigeration compressor should be made by taking into account the entire refrigeration system design and operation as well as the operating conditions of the compressor.
For lubrication of refrigeration compressors, several brands and types of specially developed lubricating oils are on the market. The choice of oil depends not only on its good lubrication properties (viscosity) and chemical stability at the operating conditions of the compressor, but also on the operating conditions of the refrigerating plant (solidifying and floc point, solubility).
Grasso has tested and approved for use in its reciprocating-compressors the brands and types of oil as listed tables below.
The choice of the lubricating oil depends on type of refrigerant and the operating conditions of the compressor.
The oil viscosity should always be more than 10 cSt. Assumed is that the oil temperature at the bearing surfaces = 15 K above crankcase oil temperature.
A higher ISO-VG number should be chosen when refrigerant solubility in crankcase is expected.
Remarks
1.
Using ISO VG100 oils to increase viscosity at high expected cranckcase­temperatures makes no sense as the friction-heat will increase that much, that the oil-temperature limit related to the minimum viscosity of 10 cSt will also be exceeded. Only in case of expected high refrigerant-concentrations in the cranckcase this viscosity-gradeoil is an alternative!
2.
Using ISO VG46 oils to meet low pour point requirements is only acceptable if coupled to a high viscosity-index of at least 100, otherwise the working limits are so limited (again concerning the minimum required oil-viscosity of 10 cSt) that it can be used in medium evaporation-pressures, making no sense to use them al a low pourpoint alternative!
Hint!
Some of the oil types listed in the tables may be marketed under other names and/or designations; these oils can also be used, provided their identity can be proved beyond any doubt. Application of other/ alternavive oils is not permitted without the written consent of Grasso.

4.6.1 STRONGLY RECOMMENDED OIL TYPES

58 30.10.2017
0089288gbr_11
Strongly recommended oil types for Grasso reciprocating compressors
Refrigerant used Brand Type designation Food Grade
NH
3

4.6.2 ACCEPTED NH3 OIL TYPES

Accepted NH3 oil types for Grasso reciprocating compressors
APPENDIX; Product Information (PI)
LUBRICATING OILS (choice and recommendations)
GEA
CPI CP-1009-68 H2
PETRO CANADA
Klüber Summit RHT-68 H2
TEXACO Capella Premium 68 -
SHELL
PR-OLEO C-MH68A H2
PR-OLEO C-MH68A-FG H1
Reflo 68A
Reflo XL H2
Clavus S-68 -
Refrigeration Oil S2 FR-A 68 -
H2 H2
Brand Type designation
AVIA
BP
CASTROL Icematic 299 56 -
CPI CP-1009-68 69 H2
EXXON MOBIL
FUCHS
KROON OIL Carsinus FC 46/68 46 -
PETRO CANADA
GEA
Klüber Summit RHT-68 68 H2
Kuwait Petroleum Q8 Stravinsky C 55 -
SHELL Refrigeration Oil S2 FR-A 68 -
SUN-OIL
TEXACO
TOTAL Luneria FR 68 68 -
PR-OLEO C-MH68A-FG
FC 46 FC 68
Energol LPT-F 46
Energol LPT 68
Zerice S46 Zerice S68
Arctic 300
Reniso KS 46
Reniso KC 68
Reflo 68A
Reflo XL
PR-OLEO C-MH68A
Suniso 3.5 GS
Suniso 4 GS
Suniso 5 G
Suniso 4 SA
Capella WF 68
Capella Premium 68
ISO VG
number *
44 65
54 68
48 68 68 47 68
58
68 68
43 55 94 57
65 67
26
Food Grade
-
-
-
-
-
-
-
-
-
H2 H2
H2 H1
-
-
-
-
H2
-
26 Viscosity grade number designation according to ISO Standard 3448.
0089288gbr_11
30.10.2017 59
APPENDIX; Product Information (PI)
Pre-lubrication oil system

4.7 Pre-lubrication oil system

Why pre-lubrication?
Pre-lubrication is necessary in situations listed below, in order to provide sufficient lubricating oil at locations where this is most needed (oil pump, bearings, pistons en piston rings) to ensure that any risk on 'dry running' is minimized or even better eliminated. Dry-running of oil pump bearings pistons and piston rings will initiate and after initiation worsen the wear of the parts mentioned and eventually even damage the crank shaft and cylinder liners or even more parts.
When pre-lubrication?
1.
Before initial start-up
2.
Before start-up after overhauling compressor
3.
Before start-up after renewal of oil
4.
Before start-up after standstill period of more than 1 month
Pre-lubrication procedure
Location pre-lubrication valve, refer Figure 15, Page 60/ Figure 16, Page 61
1.
Top up crankcase to the minimum required oil level
2.
Connect oil filling pump to stop valve and top up oil to 50-75% level (Hand operated oil filling pump can be supplied by Grasso)
Fig.15: Grasso 5HP
6
Pre-lubrication valve
60 30.10.2017
0089288gbr_11
Fig.16: Grasso V
6 Pre-lubrication valve
APPENDIX; Product Information (PI)
0089288gbr_11
30.10.2017 61
GEA Group is a global engineering company with multi-billion euro sales and operations in more than
50 countries. Founded in 1881, the company is one of the largest providers of innovative equipment and
process technology. GEA Group is listed in the STOXX® Europe 600 Index.
We live our values.
Excellence • Passion • Integrity • Responsibility • GEA-versity
GEA Refrigeration
GEA Refrigeration Netherlands N.V.
Parallelweg 25
5223 AL ‘s-Hertogenbosch,
Netherlands
Phone +31 (0)73 6203 911
info@gea.com
gea.com
Loading...